Plan Review Details - Permit 21010836
Plan Review Stops For Permit 21010836
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-02-08 Cont ID  
Sent By cpuell Date 2021-02-08 Time 16:58 Rev Time 0.00
Received By cpuell Date 2021-02-08 Time 16:58 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-07 Cont ID  
Sent By pvalenti Date 2021-04-07 Time 09:33 Rev Time 0.00
Received By pvalenti Date 2021-04-07 Time 09:13 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-05 Cont ID  
Sent By pvalenti Date 2021-02-05 Time 17:08 Rev Time 0.00
Received By pvalenti Date 2021-02-05 Time 16:43 Sent To  
Notes
2021-02-05 17:08:56PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-05-10 Cont ID  
Sent By pvalenti Date 2021-05-10 Time 08:35 Rev Time 0.00
Received By pvalenti Date 2021-05-10 Time 08:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-04-30 Cont ID  
Sent By pvalenti Date 2021-04-30 Time 06:13 Rev Time 0.00
Received By pvalenti Date 2021-04-30 Time 06:06 Sent To  
Notes
2021-04-30 06:20:29****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 ITEM #3 STILL PENDING.
  
 PLEASE INCLUDE THE FOLLOWING IN THE WATER TRUCK LETTER:
  
 THE GALLON CAPACITY OF THE TANK AND STATEMENTS THAT
 ONLY POTABLE WATER WILL BE USED AND THE WATER WILL BE
 COMING FROM AN OFF-SITE LOCATION AND WILL BE ON-SITE AT
 ALL TIMES DURING DEMOLITION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-10 Cont ID  
Sent By pvalenti Date 2021-04-10 Time 10:19 Rev Time 0.00
Received By pvalenti Date 2021-04-10 Time 10:08 Sent To  
Notes
2021-04-10 10:20:27PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE
 NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 THIS ITEM (#3) IS STILL PENDING THE METHOD OF WATERING
 DOWN DURING CONSTRUCTION.
 IF THE ABOVE METHODS (HYDRANT METER OR BACKFLOW
 PREVENTER PERMIT) ARE NOT DESIRED, THEN A WATER TRUCK
 MAY BE USED IF A SIGNED STATEMENT BY THE CONTRACTOR IS
 SUBMITTED STATING THE TRUCK WILL BE SUPPLIED WITH
 POTABLE WATER FROM A DIFFERENT LOCATION AND ON-SITE AT
 ALL TIMES DURING WORK. ALSO INCLUDE THE TRUCK DETAILS
 SUCH AS THE WATER TANK CAPACITY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-07 Cont ID  
Sent By pvalenti Date 2021-04-07 Time 09:42 Rev Time 0.00
Received By pvalenti Date 2021-04-07 Time 09:12 Sent To  
Notes
2021-04-07 10:43:58PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE
 NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 6. COMPLETE THE DEMO DEBRIS FORM:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED,
 FBC 107.
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN
 COMPLETE WITH A SITE PLAN AND COPY OF A SURVEY. THE
 STRUCTURE AND OR STRUCTURES TO BE DEMOLISHED MUST BE
 INDICATED ON SITE-PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-05 Cont ID  
Sent By pvalenti Date 2021-02-05 Time 16:53 Rev Time 0.00
Received By pvalenti Date 2021-02-05 Time 16:44 Sent To  
Notes
2021-02-05 17:06:01PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 OK
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) OK
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE
 NOTED ON THEIR FORM.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4.SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY OK
  
 6. COMPLETE THE DEMO DEBRIS FORM:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED,
 FBC 107.
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN
 COMPLETE WITH A SITE PLAN AND COPY OF A SURVEY. THE
 STRUCTURE AND OR STRUCTURES TO BE DEMOLISHED MUST BE
 INDICATED ON SITE-PLAN.
  
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS
 DEMOLITION- RENOVATION.HTML
 BACKFLOW - BEFORE SCHEDULING THE 703, THE BACKFLOW
 DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S
 UTILITIES DEPT, 561-822-2244.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-04-05 Cont ID  
Sent By rrossano Date 2021-04-05 Time   Rev Time 0.00
Received By rrossano Date 2021-04-05 Time   Sent To  
Notes
2021-04-05 12:25:50PASSED WITH PROVISOS:
  
 PLEASE MAINTAIN POLLUTION CONTROL PLAN ONSITE SHOWING:
  
 A) WHERE SILT SCREENS WILL BE INSTALLED, INCLUDING A
 DETAIL SHOWING THE SILT FENCE INSTALLATION. THESE BMPS
 ARE TO BE USED AS PER THE FDEP EROSION AND SEDIMENT
 CONTROL MANUAL.
 B) SHOW THE PROTECTION OF ALL ON-SITE CATCH BASINS, IF
 ANY.
 C) SHOW PROTECTION OF ALL OFF-SITE CATCH BASINS, IF
 ANY.
 D) INCLUDE DETAILS AS TO THE TYPE OF PROTECTION USED ON
 THE CATCH BASINS, IF ANY.
 E) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE
 ROADS.
 F) SHOW HOW DUST CONTROL WILL BE PROVIDED.
  
 HTTP://WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/DOCS/
 CONST_ACTIVITY.PDF
  
 HTTP://WWW.PBCO-NPDES.ORG/CONSTRUN.ASP?MENU=SWMPMENU
  
 THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS
 PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES,
 YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL
 BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR
 DEMOLITION WORK. INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-02-15 Cont ID  
Sent By rrossano Date 2021-02-15 Time   Rev Time  
Received By rrossano Date 2021-02-15 Time   Sent To I
Notes
2021-02-15 19:42:43PLEASE ADDRESS BUILDING COMMENTS.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-02-05 Cont ID  
Sent By aborngra Date 2021-02-05 Time 09:18 Rev Time 0.00
Received By aborngra Date 2021-02-05 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-05-10 Cont ID  
Sent By pvalenti Date 2021-05-10 Time 08:37 Rev Time 0.00
Received By pvalenti Date 2021-05-05 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-30 Cont ID  
Sent By pvalenti Date 2021-04-30 Time 06:21 Rev Time 0.00
Received By pvalenti Date 2021-04-28 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-10 Cont ID  
Sent By pvalenti Date 2021-04-10 Time 10:32 Rev Time 0.00
Received By pvalenti Date 2021-04-08 Time 12:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-07 Cont ID  
Sent By pvalenti Date 2021-04-07 Time 10:44 Rev Time 0.00
Received By pvalenti Date 2021-03-31 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-16 Cont ID  
Sent By pvalenti Date 2021-02-16 Time 13:48 Rev Time 0.00
Received By pvalenti Date 2021-02-01 Time 12:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-02-16 Cont ID  
Sent By pvalenti Date 2021-02-16 Time 13:48 Rev Time 0.00
Received By pvalenti Date 2021-02-16 Time 13:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-02-05 Cont ID  
Sent By aborngra Date 2021-02-05 Time 09:16 Rev Time 0.00
Received By aborngra Date 2021-02-05 Time 09:16 Sent To  
Notes
***NONE***