| 2021-01-27 10:40:00 | 01/27/21 1ST REVIEW PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW DEVICE |
| | WILL BE REQUIRED AT THE WATER METER BY A LICENSED |
| | CONTRACTOR WITH A SEPARATE PERMIT AND CERTIFIED BY THE |
| | CITY OF WEST PALM BEACH UTILITY DEPARTMENT PER THE |
| | CROSS CONNECTION CONTROL MANUAL PAGE 11 (C). THIS IS |
| | DUE TO THE AUTOFILL ON THE POOL, WHICH WILL REQUIRE A |
| | BACKFLOW DEVICE (P.V.B. ISOLATION), AND IT WILL BE |
| | REQUIRED TO BE CERTIFIED BY A LICENSED BACKFLOW |
| | CONTRACTOR. A REPORT MUST BE FILLED OUT FOR THE P.V.B. |
| | AND WILL NEED TO BE WITH THE PERMIT AT THE FINAL. THE |
| | INSPECTOR WILL TAKE THE CERTIFICATION FOR CITY RECORDS. |
| | THESE TWO BACKFLOWS CAN BE COMBINED IN THE SAME PERMIT. |
| | |
| | 2. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FILTER, |
| | GAS HEATER, AND THE PUMP PER THE WPB AMENDMENTS TO FBC |
| | SEC. 107.2.1. |
| | |
| | 3. THE POOL GAS HEATER SHALL HAVE A MINIMUM THERMAL |
| | EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC. |
| | R403.10.4. |
| | |
| | 4. HEATED SWIMMING POOLS AND INGROUND PERMANENTLY |
| | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| | OTHER MEANS PROVEN TO REDUCE HEAT LOSS PER THE 2017 |
| | FBC- ENERGY- SEC. R 403.10.3. |
| | |
| | 5. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| | MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM ITS |
| | PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| | DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| | EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE |
| | (G.P.M.). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE |
| | DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE |
| | SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE |
| | T.D.H. CALCULATIONS MUST INCLUDE ALL THE SYSTEM |
| | COMPONENTS, INCLUDING SUCTION AND RETURN PIPING, |
| | FITTINGS, VALVES, HEATER, FILTER, AND CHLORINATOR. ALL |
| | SYSTEM COMPONENTS EXCEPT THE PUMP. |
| | PLEASE SHOW YOUR WORK. |
| | |
| | 6. ONLY ONE PAGE WAS SIGNED AND SEALED, THE DRAWINGS |
| | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE |
| | ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN |
| | REVIEW - OR - IF YOUR ENGINEER DOES NOT HAVE AN |
| | ELECTRONIC OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY |
| | HALL DROPBOX) THE ORIGINAL SIGNED AND SEALED DOCUMENT |
| | ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE |
| | REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. THE |
| | PLAN REVIEW REQUEST FORM CAN BE OBTAINED BY EMAILING |
| | [email protected] AND ASKING FOR THE FORM. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |