Plan Review Details - Permit 21010824
Plan Review Stops For Permit 21010824
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-03-09 Cont ID  
Sent By cpuell Date 2021-03-09 Time 12:28 Rev Time 0.00
Received By cpuell Date 2021-03-09 Time 12:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-22 Cont ID  
Sent By rmcphers Date 2021-03-22 Time 13:11 Rev Time 0.00
Received By rmcphers Date 2021-03-22 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By rmcphers Date 2021-03-09 Time 11:38 Rev Time 0.00
Received By rmcphers Date 2021-03-09 Time 11:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By rmcphers Date 2021-02-12 Time 10:43 Rev Time 0.00
Received By rmcphers Date 2021-02-12 Time 09:53 Sent To  
Notes
2021-02-12 10:42:35SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE COMPLETE PRODUCT APPROVALS AS LISTED
 ON THE DRAWINGS FOR THE NEW EXTERIOR WINDOWS AND DOORS.
 2) PLEASE SHOW THE WIDTH OF THE REAR BEDROOM. FBC
 R304.2
 3) PLEASE SHOW THE SPACE DIMENSIONS FOR THE BATHROOM
 FIXTURES (SHOWER, TOILET) FBC R307.1
 4) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW PLEASE SHOW THE TOTAL JOB COST (ALL
 MATERIAL AND LABOR AS IF PRICED BY A CONTRACTOR). FBC
 WPB AMENDMENTS ? FOR PERMITTING PURPOSES THE VALUE OF
 ALL LABOR AND MATERIALS REQUIRED TO COMPLETE THE
 PROJECT ARE REQUIRED TO BE INCLUDED IN THE COST. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL ? SWIFT, MEANS, ETC.) AS PUBLISHED
 BY INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 5) WINDOW AND DOOR PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-25 Cont ID  
Sent By equinone Date 2021-02-25 Time 13:50 Rev Time 0.00
Received By equinone Date 2021-02-25 Time 13:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-04 Cont ID  
Sent By equinone Date 2021-02-04 Time 09:34 Rev Time 0.00
Received By equinone Date 2021-02-04 Time 08:59 Sent To  
Notes
2021-02-04 09:34:39CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) RISER DIAGRAM: PLEASE SPECIFY SERVICE CONDUCTOR
 SIZE, GROUNDING ELECTRODE SYSTEM DETAILS, CONDUCTOR
 SIZE FEEDING 200 AMPS PANEL. FBC 107
 2) PLEASE SHOW LOCATION OF NEW 200 AMPS ELECTRICAL
 PANEL, SERVICE METER, AND SERVICE DISCONNECT. IS THE
 EXISTING 150 AMPS PANEL TO BE REMOVED? FBC 107
 3) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CURRENT AT
 SERVICE.
 4) NEW 200 AMPS PANEL. PLEASE SPECIFY AIC RATING,
 SPECIFY MCB SIZE.
 5) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16 (A NOTE WILL
 SUFFICE)
 6) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE
 E4002.14 (A NOTE WILL SUFFICE)
 7) PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 8) ELECTRICAL WORK MUST COMPLY WITH NEC 2017, FBC RE
 2020. (PLEASE ADD NOTE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2021-03-18 Cont ID  
Sent By ccole Date 2021-03-18 Time 08:21 Rev Time 0.00
Received By ccole Date 2021-03-17 Time 17:13 Sent To  
Notes
2021-03-18 08:25:32THE CONTRACTOR OF RECORD HAS REQUESTED THE GAS PIPING
 TO THE TANKLESS WATER HEATER AND RANGE TO BE UNDER
 SEPARATE PERMIT. A REVIEW OF THE SYSTEM WAS NOT
 PERFORMED AT THIS TIME. A NOTE HAS BEEN ADDED TO THE
 PLUMBING PLANS REQUIRING THAT COMPLETE GAS PLANS,
 SPECIFICATIONS, AND A RISER DRAWING SHALL BE SUBMITTED
 FOR REVIEW UNDER A SEPARATE PERMIT.
 CCOLE
 3/18/21

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-03-01 Cont ID  
Sent By ccole Date 2021-03-01 Time 10:21 Rev Time 0.00
Received By ccole Date 2021-03-01 Time 09:02 Sent To  
Notes
2021-03-01 10:21:422ND REVIEW FBC-2020 RES.
 PERMIT- 21010824
 2/3/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED STILL EXIST. NOTES
 HAVE BEEN ADDED IN CAP LETTERS.
  
 1) PROVIDE A GAS PIPING RISER DRAWING FOR INSTALLATION
 OF THE NEW GAS WATER HEATER AND ALL PROPOSED GAS-FIRED
 APPLIANCES AND EQUIPMENT- SECTION 107.3.5.3 WPB. NOT
 PROVIDED.
  
 GAS RISER- PROVIDE THE FOLLOWING- FBC-2020 RES. FUEL
 GAS.
 A) TOTAL LOAD OF THE SYSTEM AND INDIVIDUAL APPLIANCE
 LOADS.
 B) TOTAL DEVELOPED LENGTH OF THE SYSTEM AND INDIVIDUAL
 BRANCH LENGTH MEASURMENTS.
 C) TYPES AND SIZES OF PIPING AND RISERS.
 D) DELIVERY PRESSURE AT THE METER AND THE SYSTEM.
 E) LOCATIONS OF SHUTOFF VALVES AND REGULATORS.
 F) PIPE SIZING TABLES USED
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 NEW WATER HEATER AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS IN ACCORDANCE WITH SECTION G2448.1 FBC
 RES, AND TABLE C404.2 FBC EC. PLEASE NOTE THE PLAN
 SYMBOL IS INDICATING A STORAGE TANK TYPE WATER HEATER
 AT THE EXTERIOR OF THE BUILDING WHICH APPEARS TO BE A
 PLAN ERROR. TANKLESS WATER HEATERS RATED FOR EXTERIOR
 INSTALLATION ARE TYPICALLY INSTALLED INSTEAD OF TANK
 HEATERS WHICH WILL REQUIRE PROTECTION FROM WIND AND
 WATER INTRUSION. EQUIPMENT SCHEDULE AND SPECS NOT FOR
 THE WH PROVIDED. THE SCHEDULE AND SPECS MAY BE DEFERRED
 SUBMITTALS HOWEVER THE PLAN SHOWS AN INCORRECT GAS LOAD
 OF 19,000 BTU- PLEASE CORRECT.
  
 3) PROVIDE A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB. NOT PROVIDED. THE APPLICATION MAY BE DEFFERRED AND
 SUBMITTED AT A LATER DATE AFTER MASTER PERMIT ISSUANCE-
 SECTION 105.1 WPB.
  
 4) NEW SUBMITTED PLUMBING LAYOUT PLAN- SEE COMMENT #1
 AND #2 ABOVE AND CORRECT THE PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-03 Cont ID  
Sent By ccole Date 2021-02-03 Time 07:28 Rev Time 0.00
Received By ccole Date 2021-02-02 Time 17:54 Sent To  
Notes
2021-02-03 07:28:431ST REVIEW FBC-2020 RES.
 PERMIT- 21010824
 2/3/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS PIPING RISER DRAWING FOR INSTALLATION
 OF THE NEW GAS WATER HEATER AND ALL PROPOSED GAS-FIRED
 APPLIANCES AND EQUIPMENT- SECTION 107.3.5.3 WPB.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 NEW WATER HEATER AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS IN ACCORDANCE WITH SECTION G2448.1 FBC
 RES, AND TABLE C404.2 FBC EC. PLEASE NOTE THE PLAN
 SYMBOL IS INDICATING A STORAGE TANK TYPE WATER HEATER
 AT THE EXTERIOR OF THE BUILDING WHICH APPEARS TO BE A
 PLAN ERROR. TANKLESS WATER HEATERS RATED FOR EXTERIOR
 INSTALLATION ARE TYPICALLY INSTALLED INSTEAD OF TANK
 HEATERS WHICH WILL REQUIRE PROTECTION FROM WIND AND
 WATER INTRUSION.
  
 3) PROVIDE A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-03-11 Cont ID  
Sent By fmittner Date 2021-03-11 Time 08:27 Rev Time 0.00
Received By fmittner Date 2021-03-11 Time 08:27 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-02-03 Cont ID  
Sent By fmittner Date 2021-02-03 Time 08:48 Rev Time 0.00
Received By fmittner Date 2021-02-03 Time 08:48 Sent To  
Notes
2021-02-03 08:48:52NO WINDOW INFORMATION PROVIDED

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-22 Cont ID  
Sent By rmcphers Date 2021-03-22 Time 13:16 Rev Time 0.00
Received By rmcphers Date 2021-03-12 Time 16:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-11 Cont ID  
Sent By lmarchan Date 2021-03-11 Time 08:50 Rev Time 0.00
Received By lmarchan Date 2021-02-21 Time 13:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-12 Cont ID  
Sent By rmcphers Date 2021-02-12 Time 10:43 Rev Time 0.00
Received By rmcphers Date 2021-01-27 Time 21:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 07:01 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-01 Cont ID  
Sent By medwards Date 2021-02-01 Time 07:30 Rev Time 0.00
Received By medwards Date 2021-02-01 Time 07:07 Sent To  
Notes
2021-02-01 07:31:061ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21010824
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IF THIS IS A MECHANICAL LIKE FOR LIKE CHANGE OUT
 PLEASE SUBMIT THE REQUIRED LIKE FOR LIKE CHANGE OUT
 FORM. IF THIS IS NOT A LIKE FOR LIKE BUT IS A LARGER
 SYSTEM PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC 107.2.1
  
 2) PLEASE SHOW THE RETURN AIR PATH FROM THE BEDROOMS TO
 THE AHU. FBC RES M1602.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-18 Cont ID  
Sent By ccole Date 2021-03-18 Time 09:47 Rev Time 0.00
Received By ccole Date 2021-03-17 Time 17:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-03-01 Cont ID  
Sent By ccole Date 2021-03-01 Time 09:45 Rev Time 0.00
Received By ccole Date 2021-03-01 Time 09:02 Sent To  
Notes
2021-03-01 09:45:582ND REVIEW FBC-2020 RES.
 PERMIT- 21010824
 3/1/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED STILL EXIST. NOTES
 HAVE BEEN ADDED IN CAP LETTERS.
  
 1) THE KITCHEN PLUMBING RISER IS NOT DRAWN IN
 COMPLIANCE WITH THE CODE. RELOCATE THE WASHING MACHINE
 TO THE LEFT SIDE OF THE RISER AND REMOVE THE CONNECTION
 TO THE COMMON VENT SERVING THE KITCHEN SINK DRAINS.
 PROVIDE A 2 IN. STANDPIPE AND TRAP AND SHOW THE
 STANDPIPE CONNECTING TO EITHER A 3 IN. HORIZONTAL OR
 VERTICAL DRAIN- SECTIONS P3107.1 & P3201.7 FBC RES, AND
 SECTION 406.2 FBC FG. CONNECTION TO A VERTICAL STACK
 WILL REQUIRE A STACK VENT SIZED IN ACCORDANCE WITH
 SECTION P3109.3. THE NEW RISER SHOWS A 1-1/2 STANDPIPE
 AND A 2 IN. HORIZONTAL BRANCH DRAIN. THE SINKS NEED A
 COMMON VENT- SECTION P3701.1 FBC RES.
  
 4) PROVIDE THE DIMENSIONS OF THE MASTER BATH SHOWER AND
 THE WIDTH OF THE SHOWER DOOR- SECTION P2708.1 &
 P2708.1.1 FBC RES. THE REVISED PLAN SHOWS AN UNDERSIZED
 SHOWER DOOR WIDTH OF 18-7/8 IN. REFER TO SECTION
 P2708.1.1 FBC RES.- MINIMUM 22 IN. UNOBSTRUCTED WIDTH
 REQUIRED.
  
 7) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB. NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-02 Cont ID  
Sent By ccole Date 2021-02-02 Time 17:51 Rev Time 0.00
Received By ccole Date 2021-02-02 Time 16:20 Sent To  
Notes
2021-02-02 17:51:511ST REVIEW FBC-2020 RES.
 PERMIT- 21010824
 2/2/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE KITCHEN PLUMBING RISER IS NOT DRAWN IN
 COMPLIANCE WITH THE CODE. RELOCATE THE WASHING MACHINE
 TO THE LEFT SIDE OF THE RISER AND REMOVE THE CONNECTION
 TO THE COMMON VENT SERVING THE KITCHEN SINK DRAINS.
 PROVIDE A 2 IN. STANDPIPE AND TRAP AND SHOW THE
 STANDPIPE CONNECTING TO EITHER A 3 IN. HORIZONTAL OR
 VERTICAL DRAIN- SECTIONS P3107.1 & P3201.7 FBC RES, AND
 SECTION 406.2 FBC FG. CONNECTION TO A VERTICAL STACK
 WILL REQUIRE A STACK VENT SIZED IN ACCORDANCE WITH
 SECTION P3109.3.
  
 2) INDICATE IF A DISHWASHER WILL BE INSTALLED AND SHOW
 THE PLUMBING PIPING CONNECTIONS- SECTION P2717 FBC RES.
  
 3) PROVIDE THE WIDTH DIMENSION OF THE WATER CLOSET ROOM
 IN THE COMMON BATHROOM- SECTION R307.1 FBC RES.
  
 4) PROVIDE THE DIMENSIONS OF THE MASTER BATH SHOWER AND
 THE WIDTH OF THE SHOWER DOOR- SECTION P2708.1 &
 P2708.1.1 FBC RES.
  
 5) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.1 WPB.
  
 6) PLEASE NOTE THAT WATER HAMMER ARRESTORS ARE REQUIRED
 FOR THE WATER SUPPLY LINES TO THE WASHING MACHINE,
 DISHWASHER, AND REFRIGERATOR ICE MAKER. PLEASE PLACE
 NOTES ON THE PLAN- SECTION P2903.5 FBC RES.
  
 7) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-18 Cont ID  
Sent By ccole Date 2021-03-18 Time 08:33 Rev Time 0.00
Received By ccole Date 2021-03-17 Time 17:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 07:02 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 07:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-01 Cont ID  
Sent By medwards Date 2021-02-01 Time 07:32 Rev Time 0.00
Received By medwards Date 2021-02-01 Time 07:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-11 Cont ID  
Sent By fmittner Date 2021-03-11 Time 08:27 Rev Time 0.00
Received By fmittner Date 2021-03-11 Time 08:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-03 Cont ID  
Sent By fmittner Date 2021-02-03 Time 08:48 Rev Time 0.00
Received By fmittner Date 2021-02-03 Time 08:48 Sent To  
Notes
***NONE***