Plan Review Details - Permit 21010809
Plan Review Stops For Permit 21010809
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-03-03 Cont ID  
Sent By shill Date 2021-03-03 Time 06:56 Rev Time 0.00
Received By shill Date 2021-03-03 Time 06:56 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-02-22 Cont ID  
Sent By jwitmer Date 2021-02-22 Time 08:58 Rev Time 0.00
Received By jwitmer Date 2021-02-22 Time 08:32 Sent To  
Notes
2021-02-22 08:58:26COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-03 Cont ID  
Sent By jwitmer Date 2021-02-03 Time 09:27 Rev Time 0.00
Received By jwitmer Date 2021-02-03 Time 08:43 Sent To  
Notes
2021-02-03 09:26:30COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By jwitmer Date 2021-02-22 Time 08:55 Rev Time 0.00
Received By jwitmer Date 2021-02-22 Time 08:32 Sent To  
Notes
2021-02-22 08:55:46WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010809
 ADD: 3200 N. MILITARY TRL. / REMODEL OF THE GRACE
 PAVILION
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: 561-833-4441
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. FEB. 22ND/2021
 ACTION: BUILDING PROVISOS
 BUILDING PROVISOS:
  
 1) THE DUMPSTER ENCLOSURE AND PARKING LOT CHANGES
 REQUIRE SEPARATE PERMITS, REVIEWS AND ASSOCIATED FEES.
  
 2) CANOPY TO BE UNDER A DELEGATE ENGINEER. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW BEFORE SUBMITTING TO THE
 BUILDING DEPARTMENT.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-02-03 Cont ID  
Sent By jwitmer Date 2021-02-03 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2021-02-03 Time 08:43 Sent To  
Notes
2021-02-03 09:43:30WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010809
 ADD: 3200 N. MILITARY TRL. / REMODEL OF THE GRACE
 PAVILION
 CONT: CONKLING & LEWIS CONSTRUCTION
 TEL: 561-833-4441
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 03/2021
 ACTION: BUILDING PROVISOS
 BUILDING PROVISOS:
  
 1) THE DUMPSTER ENCLOSURE AND PARKING LOT CHANGES
 REQUIRE SEPARATE PERMITS, REVIEWS AND ASSOCIATED FEES.
  
 2) CANOPY TO BE UNDER A DELEGATE ENGINEER. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW BEFORE SUBMITTING TO THE
 BUILDING DEPARTMENT.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-03 Cont ID  
Sent By jleahy Date 2021-02-03 Time 15:45 Rev Time 0.00
Received By jleahy Date 2021-02-02 Time 12:53 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-02-03 Cont ID  
Sent By jleahy Date 2021-02-03 Time 15:45 Rev Time 0.00
Received By jleahy Date 2021-02-03 Time 15:45 Sent To  
Notes
2021-02-03 15:46:41VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By pleduc Date 2021-02-22 Time   Rev Time 0.00
Received By pleduc Date 2021-02-22 Time 11:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-28 Cont ID  
Sent By pleduc Date 2021-01-28 Time   Rev Time 0.00
Received By pleduc Date 2021-01-27 Time 12:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-15 Cont ID  
Sent By dbattles Date 2021-04-15 Time 13:47 Rev Time 0.00
Received By dbattles Date 2021-04-14 Time 16:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-03 Cont ID  
Sent By shill Date 2021-03-03 Time 06:56 Rev Time 0.00
Received By shill Date 2021-02-18 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-02-05 Time   Rev Time 0.00
Received By lmarchan Date 2021-01-22 Time 12:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 08:51 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 08:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-02-02 Cont ID  
Sent By medwards Date 2021-02-02 Time 07:07 Rev Time 0.00
Received By medwards Date 2021-02-02 Time 06:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By ccole Date 2021-03-01 Time 13:30 Rev Time 0.00
Received By ccole Date 2021-03-01 Time 12:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-05 Cont ID  
Sent By ccole Date 2021-02-05 Time 09:27 Rev Time 0.00
Received By ccole Date 2021-02-04 Time 16:44 Sent To  
Notes
2021-02-05 09:28:061ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21010809
 2/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET ALS1.0: THE PLUMBING FIXTURE CALCULATIONS ARE
 NOT IN COMPLIANCE WITH TABLE 403.3 FBC P. AN OCCUPANT
 LOAD OF 205 REQUIRES 4 MALE AND 4 FEMALE WATER CLOSETS,
 AND 3 MALE AND 3 FEMALE LAVATORIES. PLEASE CORRECT THE
 SCHEDULE AND THE PLANS.
  
 2) THE NEW SINGLE USER TOILET ROOMS SHOWN IN THE
 ARCHITECTURAL AND PLUMBING PLANS ARE NOT IDENTIFIED AS
 EITHER MALE, FEMALE, OR UNISEX, AND NO SIGNAGE DETAILS
 HAVE BEEN PROVIDED- SECTIONS 403.2 & 403.4 FBC P.
  
 3) SHEETS A2.1.3 & A2.1.4 SHOWING AREAS C & D DO NOT
 MATCH THE DEMO AND NEW WORK PLUMBING PLANS DESIGNATED
 FOR AREAS C & D. PLEASE CORRECT- SECTION 107.2.1 WPB.
  
 4) SHEETS A2.1.3 & P.1.1.4: SHOW THE CLEAR FLOOR SPACE
 DIAGRAM AND DIMENSIONS FOR THE NEW STERILIZER SINK-
 SECTIONS 212.3 & 696.2 FBC ACC.
  
 5) SHEET A4.02: PROVIDE AN ELEVATION DETAIL SHOWING THE
 KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION-
 606.2 FBC ACC.
  
 6) SHEETS P0.01, P1.1.2, P1.1.3, AND P1.1.4: SECTION
 419.5 FBC- 2020 PLUMBING WAS CHANGED TO ALLOW
 LAVATORIES TO BE SUPPLIED WITH EITHER COLD OR TEMPERED
 WATER. THE FIXTURE SCHEDULE INDICATES HOT AND COLD
 WATER AND TEMPERATURE MIXER FAUCET, HOWEVER THE PLANS
 APPEAR TO SHOW COLD WATER SUPPLY ONLY TO THE
 LAVATORIES. PLEASE CLARIFY THE DESIGN INTENTION.
  
 7) SHEET P1.1.5: PROVIDE VACUUM AND COMPRESSED AIR
 PIPING DIAGRAMS SHOWING POINTS OF CONNECTIONS AND NEW
 PIPING RUNS. PLEASE INCLUDE THE TYPES AND SIZES OF
 PIPING IN THE DRAWING. PROVIDE AN EQUIPMENT SCHEDULE
 FOR THE NEW OUTLET ENCLOSURE INDICATING MAKE, MODEL,
 AND LISTING, AND SUBMIT MANUFACTURER?S SPECIFICATIONS
 FOR THE ENCLOSURE AND THE PIPING- SECTION 107.2.1 WPB.
 PLEASE CLARIFY IF MEDICAL GAS ALTERATIONS ARE PROPOSED
 AND PROVIDE DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-04-15 Cont ID  
Sent By dbattles Date 2021-04-15 Time 13:47 Rev Time 0.00
Received By dbattles Date 2021-04-15 Time 09:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 08:55 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 08:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-02 Cont ID  
Sent By medwards Date 2021-02-02 Time 07:52 Rev Time 0.00
Received By medwards Date 2021-02-02 Time 07:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-27 Cont ID  
Sent By eschneid Date 2021-01-27 Time 15:42 Rev Time 0.50
Received By eschneid Date 2021-01-27 Time 15:41 Sent To  
Notes
2021-01-27 15:43:43THE DUMPSTER ENCLOSURE AND PARKING LOT CHANGES REQUIRE
 SEPARATE PERMITS WITH PLANS.
  
 THE CURRENTLY SUBMITTED MINOR AMENDMENT NEEDS TO BE
 APPROVED PRIOR TO THE FINAL INSPECITON FOR THIS PERMIT.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved