| 2021-01-27 10:38:03 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 21010798 |
| | 1/27/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A01: PLEASE INDICATE THE GAS METER AS EITHER |
| | NEW OR EXISTING AND PROVIDE THE GAS DELIVERY PRESSURE. |
| | IS THIS A 2 PSI SYSTEM OR LOW-PRESSURE SYSTEM? SECTION |
| | G2412.1 FBC RES. |
| | |
| | 2) A01: PROVIDE THE PIPE SIZING METHOD OR SIZING TABLES |
| | USED IN ACCORDANCE WITH SECTION- G2413.3 FBC RES. |
| | |
| | 3) A01: PROVIDE THE TOTAL DEVELOPED LENGTH OF THE |
| | SYSTEM FROM THE METER TO THE RANGE. THE ISO APPEARS TO |
| | INDICATE 44 FT.- G2413.4.1. |
| | |
| | 4) A01: CSST PIPE SIZING IS BY EHD NOT INCHES- PLEASE |
| | PROVIDE THE EHD OF THE 3/4 IN. PIPING- G2415.2 |
| | |
| | 5) A01: PROVIDE AN ENLARGED GAS MANIFOLD DETAIL AND |
| | SUBMIT A PRODUCT SPECIFICATION IF THIS IS A |
| | MANUFACTURED AND LISTED PIPE CONNECTOR- SECTION |
| | G2415.17.2. |
| | |
| | 6) A01: SHOW THE TYPE OF PIPING FOR THE FUTURE |
| | GENERATOR AND SHOW A GAS TIGHT CAP WILL BE INSTALLED- |
| | G2414.1 & G2415.15. PLEASE NOTE THAT THE FUTURE |
| | GENERATOR SHALL BE INSTALLED A MINIMUM OF 10 FT. FROM |
| | MECHANICAL AND NATURAL AIR INTAKE OPENINGS INTO THE |
| | BUILDING INCLUDING DOORS AND OPERABLE WINDOWS- SECTION |
| | R303.5.1 FBC RES. |
| | |
| | 7) SUBMIT PRODUCT DATA SHEETS FOR THE WATER HEATER AND |
| | THE RANGE WITH MARKINGS TO SHOW THE BTUH CAPACITIES AND |
| | GAS INPUT PRESSURES- G2408.1 & G2448.1. PLEASE NOTE |
| | THAT REGULATORS MAY BE REQUIRED BASED ON THE PRESSURE |
| | OF THE SYSTEM AND INPUT PRESSURES OF THE APPLIANCES. |
| | |
| | 8) WHERE REGULATORS ARE REQUIRED, THEY SHALL BE SHOWN |
| | ON THE RISER WITH INPUT AND OUTPUT PRESSURES NOTED, AND |
| | MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED- |
| | G2421. |
| | |
| | 9) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR THE |
| | NEW RANGE AND PROVIDE A CALCULATION IF INDOOR AIR IS TO |
| | BE USED- G2407.1, G2407.5. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |