Plan Review Details - Permit 21010779
Plan Review Stops For Permit 21010779
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-07 Cont ID  
Sent By equinone Date 2021-04-07 Time 10:25 Rev Time 0.00
Received By equinone Date 2021-04-07 Time 09:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-05 Cont ID  
Sent By equinone Date 2021-02-05 Time 16:45 Rev Time 0.00
Received By equinone Date 2021-02-05 Time 16:45 Sent To  
Notes
2021-02-05 16:45:42CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) NO ELECTRICAL DETAILS PROVIDED FOR THIS
 INSTALLATION. PLEASE SHOW CIRCUIT RUNS, CONDUCTOR AND
 BREAKER SIZES FOR ALL EQUIPMENT BEING INSTALLED. FBC
 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-08 Cont ID  
Sent By pleduc Date 2021-04-08 Time   Rev Time 0.00
Received By pleduc Date 2021-04-08 Time 11:17 Sent To  
Notes
2021-04-08 11:32:42FIRE PROVISO
  
 THE FIRE SUPPRESSION SYSTEM SHALL BE INSTALLED UNDER A
 SEPARATE PERMIT AND SHOP DRAWING.
  
 THE FIRE SUPPRSSION SYSTEM IS NOT APPROVED UNDER THIS
 PERMIT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-01-27 Cont ID  
Sent By pleduc Date 2021-01-27 Time   Rev Time 0.00
Received By pleduc Date 2021-01-27 Time 10:37 Sent To  
Notes
2021-01-27 10:52:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET HOOD 1 - THERE ARE NO INDICATIONS OF FLOOR
 PLAN SHOWING THE EXACT LOCATION WITHIN THE BUILDING
 SPACE, INCLUDING DIMENSIONS.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH NFPA 96
  
  
  
  
 2) SHEET KEF - THERE ARE NO INDICATIONS OF THE EXACT
 LOCATION ON THE ROOF, INCLUDING DIMENSIONS TO OTHER
 EQUIPMENT INCLUDING A/C AND AND OTHER VENTS.
  
 PLEASE PROVIDE DETAILS IN COMPLAINCE WITH NFPA 96
  
  
  
  
 3) SHEET MUA 1 - THERE ARE NO INDICATIONS OF THE
 CLEARENCES OR SUPPORTS GOING UP THROUGH THE TRUSS
 SYSTEM TO THE ROOF, INCLUDING DIMENSIONS.
  
 PLEASE PROVIDE DETAILS IN COMPLAINCE WITH NFPA 96
  
  
  
  
 4) SHEET FIRE SYSTEM 1 - THERE ARE INDICATIONS OF A
 FIRE SUPPRESSION SYSTEM.
  
 THE FIRE SUPPRSSION SYSTEM SHALL BE SUBMITTED THROUGH
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 THE FIRE SUPPRESSION SYSTEM IS NOT APPROVED WITH THIS
 PERMIT AND SHALL NOT BE INSTALLED UNDER THIS PERMIT.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGEMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-08-10 Cont ID  
Sent By medwards Date 2021-08-10 Time 08:08 Rev Time 0.00
Received By medwards Date 2021-07-30 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-16 Cont ID  
Sent By medwards Date 2021-07-16 Time 15:12 Rev Time 0.00
Received By medwards Date 2021-07-08 Time 12:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-22 Cont ID  
Sent By medwards Date 2021-06-22 Time 09:14 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 10:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 14:51 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-05 Cont ID  
Sent By equinone Date 2021-02-05 Time 16:45 Rev Time 0.00
Received By equinone Date 2021-01-22 Time 08:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-08-10 Cont ID  
Sent By medwards Date 2021-08-10 Time 08:02 Rev Time 0.00
Received By medwards Date 2021-08-10 Time 07:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-07-16 Cont ID  
Sent By medwards Date 2021-07-16 Time 15:01 Rev Time 0.00
Received By medwards Date 2021-07-16 Time 15:01 Sent To  
Notes
2021-07-16 15:01:384TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21010779
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE COMMENT 4 OF REVIEW CYCLE 3 BELOW:
 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE I.E. DINING ROOM, KITCHEN AND OFFICE BASED ON
 FBC M 403.3.1.1 AND TABLE 403.3.1.1 OR ASHRAE 62.1-
 2016
  
 2) IF ASHRAE 62.1-2016 IS USED PLEASE SUBMIT ENTIRE
 PROJECT BASED ON ASHRAE 62.1-2016 AS ALTERNATE MEANS
 AND METHODS. FBC M 104.11
  
 3) PLEASE HELP THIS REVIEWER UNDERSTAND THE ?SERVING
 AREA? LISTED IN THE OUTDOOR AIR CALCULATIONS, IS THIS
 NOT THE EXISTING DINING ROOM? BASED ON FBC M 403.3.1.1
 AND TABLE 403.3.1.1 THE DINING ROOM OCCUPANCY IS 61
 PEOPLE WITH 612 CFM OF REQUIRED OUTDOOR AIR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-06-22 Cont ID  
Sent By medwards Date 2021-06-22 Time 09:12 Rev Time 0.00
Received By medwards Date 2021-06-22 Time 09:12 Sent To  
Notes
2021-06-22 09:12:263RD REVIEW FBC-2020 MECHANICAL
 PERMIT-21010779
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1-V3 SHOWS OCCUPANCY AS MERCANTILE, IS THIS A
 CHANGE OF USE? AS THIS RESTAURANT WOULD BE AN A-2 BUT
 WITH THE EXCEPTION FOR OCCUPANTS IT COULD BE CLASSIFIED
 AS A BUSINESS. FBC 303.1.1
  
 2) SHEET A1-V3 SHOWS THAT THIS BUILDING IS TYPE V
 UNPROTECTED. PLEASE SHOW THE CONSTRUCTION OF THE WALLS
 WHERE THE HOODS WILL BE MOUNTED. PLEASE ALSO SHOW THE
 CLEARANCES TO COMBUSTIBLES. FBC 107.2.1
  
 3) PLEASE SHOW THAT THE GREASE DUCTS WILL MEET THE
 CLEARANCE TO COMBUSTIBLES. FBC M 506.3.6
  
 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE I.E. DINING ROOM, KITCHEN AND OFFICE BASED ON
 FBC M 403.3.1.1 AND TABLE 403.3.1.1 OR ASHRAE 62.1-
 2016
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 14:48 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 14:48 Sent To  
Notes
2021-04-08 14:48:341ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21010779
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MUA UNIT MUST MEET FBC M 508.1.1 MAKEUP AIR
 TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
 2) THE APPLICATION INDICATES THIS IS FOR THE
 INSTALLATION OF THE KITCHEN HOODS AND GREASE DUCT AND
 MAKE UP AIR FOR THE HOODS. PLEASE REMOVE ALL UNRELATED
 DRAWINGS FROM THIS HOOD APPLICATION. THE HOOD, GREASE
 DUCT AND MAKE UP AIR IS A STAND ALONE PERMIT THAT
 SHOULD BE SEPARATELY FROM THE MAIN PERMIT. FBC 107.2.1
  
 3) SHEET H-1 INDICATES THE TYPE II HOOD IS TO BE
 DISABLED ALTHOUGH IT APPEARS THERE WILL BE SOME TYPE OF
 COOKING UNDER THIS HOOD. PLEASE EXPLAIN WHY THERE IS NO
 NEED FOR A HOOD. FBC 507.1
  
 THE AIR BALANCE REPOT MUST MEET: FBC M 508.1.2AIR
 BALANCE.
 DESIGN PLANS FOR A FACILITY WITH A COMMERCIAL KITCHEN
 VENTILATION SYSTEM SHALL INCLUDE A SCHEDULE OR DIAGRAM
 INDICATING THE DESIGN OUTDOOR AIR BALANCE. THE DESIGN
 OUTDOOR AIR BALANCE SHALL INDICATE ALL EXHAUST AND
 REPLACEMENT AIR FOR THE FACILITY, PLUS THE NET
 EXFILTRATION IF APPLICABLE. THE TOTAL REPLACEMENT AIR
 AIRFLOW RATE SHALL EQUAL THE TOTAL EXHAUST AIRFLOW RATE
 PLUS THE NET EXFILTRATION. (THE BATH ROOM EXHAUST MUST
 BE INCLUDED IN THE AIR BALANCE REPORT).
  
 4) WHAT IS THE TYPE OF CONSTRUCTION FOR THIS BUILDING?
  
 PLEASE SHOW THE GREASE DUCT WILL HAVE THE REQUIRED
 CLEARANCE TO COMBUSTIBLES: FBC M 510.9.2CLEARANCE TO
 COMBUSTIBLES.
 DUCTS SHALL HAVE A CLEARANCE TO COMBUSTIBLES IN
 ACCORDANCE WITH TABLE 510.9.2. EXHAUST GASES HAVING
 TEMPERATURES IN EXCESS OF 600?F (316?C) SHALL BE
 EXHAUSTED TO A CHIMNEY IN ACCORDANCE WITH SECTION
 511.2.
  
 5) PLEASE SHOW THE DISTANCE FROM UNITS TO ROOF EDGE.
 FBC M 304.11
  
 6) PLEASE SHOW ACCESS TO THE UNITS ON THE ROOF. FBC M
 306.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-01 Cont ID  
Sent By medwards Date 2021-02-01 Time 15:59 Rev Time 0.00
Received By medwards Date 2021-02-01 Time 14:41 Sent To  
Notes
2021-02-01 16:00:061ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21010779
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A COMPLETE CODE COMPLIANT SET OF
 DRAWINGS SHOWING THE LAYOUT OF THE RESTAURANT WITH THE
 KITCHEN AND HOODS SHOWN. THIS SHOULD ALSO INCLUDE A
 DRAWING OF THE DUCT SYSTEM FOR BOTH GREASE DUCT
 SYSTEMS. PROVIDE A DETAIL LIST OF ALL COOKING
 APPLIANCES UNDER THE HOODS. THESE DRAWINGS SHOULD ALSO
 SHOW THE TYPE OF CONSTRUCTION OF THE WALLS AND CEILINGS
 AROUND THE HOODS AND SHOW THE REQUIRED CLEARANCES TO
 COMBUSTIBLES. PLEASE ALSO PROVIDE A ROOF DRAWING
 SHOWING THE HOOD EXHAUST AND MAKE UP AIR SYSTEM. THIS
 SHOULD ALSO INCLUDE THE REQUIRED DISTANCES FROM EXHAUST
 AIR AND PLUMBING VENTS AND THE INTAKE OPENINGS. PLEASE
 SHOW GUARDS IF REQUIRED. FBC 107.2.1
  
 2) PLEASE PROVIDE AN AIR BALANCE REPORT FOR THIS
 RESTAURANT. FBC M 508.1.2
  
 3) SHEET 004 MUA-1: WITHOUT EXCEPTION, THE TEMPERATURE
 DIFFERENTIAL BETWEEN MAKE UP AIR AND THE AIR IN THE
 CONDITIONED SPACE SHALL NOT EXCEED 10DEG.F. FBC M
 508.1.1
  
 4) DESIGNER OF THESE DRAWINGS MUST PRINT AND SIGN THEIR
 NAME ON EACH SHEET.
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-08-10 Cont ID  
Sent By medwards Date 2021-08-10 Time 08:08 Rev Time 0.00
Received By medwards Date 2021-08-10 Time 08:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-07-16 Cont ID  
Sent By medwards Date 2021-07-16 Time 15:12 Rev Time 0.00
Received By medwards Date 2021-07-16 Time 15:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-22 Cont ID  
Sent By medwards Date 2021-06-22 Time 09:14 Rev Time 0.00
Received By medwards Date 2021-06-22 Time 09:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 14:51 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 14:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-02-01 Cont ID  
Sent By medwards Date 2021-02-01 Time 16:00 Rev Time 0.00
Received By medwards Date 2021-02-01 Time 16:00 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved