| Plan Review Stops For Permit 21010734 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2021-02-21 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-02-03 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-02-21 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2021-02-21 08:21:34 | OWNERS APPROVED OF NEW ADDRESS, 4400 GREENWOOD AVE | | 2021-02-03 12:31:04 | CURRENTLY VACANT LAND WITH NO ADDRESS. PROPOSING AN | | | ADDRESS OF 4400 GREENWOOD AVE. PLEASE HAVE OWNER EMAIL | | | [email protected] TO APPROVE THE ADDRESS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2021-12-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-29 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-29 |
Time |
07:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-20 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-20 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2021-12-20 08:50:43 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | | | 1) PRODUCT APPROVAL PROVIDED FOR THE ROOF 17-0620.16 IS | | | FOR " CEMENTITIOUS WOOD FIBER " DECK - YOU WILL NEED TO | | | PROVIDE A PRODUCT APPROVAL FOR A " PLYWOOD" ROOF DECK | | | AS SHOWN ON THE BUILDING DRAWINGS. | | | | | | 2) ROOFING SYSTEM - PRODUCT APPROVALS MAY BE DEFERRED | | | SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE | | | CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. | | | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS | | | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE | | | NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT | | | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION | | | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-01 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-01 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2021-11-01 13:41:25 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | | | 1) PRODUCT APPROVAL INSTALLATION INSTRUCTIONS PROVIDED | | | FOR THE DOOR (17184.11) IS EXPIRED - PLEASE PROVIDE THE | | | UPDATED INSTALLATION INSTRUCTIONS (17184.11 R8) - | | | PLEASE PROVIDE THE PRODUCT APPROVAL FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS. | | | | | | 2) ROOF PRODUCT APPROVAL FL35402 = ROOFING SYSTEM TO BE | | | USED ON THE PROVIDED PRODUCT APPROVAL REQUIRES | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONE 3 WHICH | | | REQUIRES A HIGHER PRESSURE (-79.06 PER DRAWING A2.2) | | | THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-67.5) | | | - SEE NOTE NUMBER 9 ON THE PRODUCT APPROVAL. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2021-09-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-21 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-21 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2021-09-21 11:41:04 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | | | 1) DRAWING A0.2 - DESIGN CRITERIA - SHOWS THE CODE AS | | | THE INTERNATIONAL CODE SHOULD BE FBC. | | | | | | 2) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG | | | WINDOWS (20-0813.08) IS NOT THE PRODUCT APPROVAL NUMBER | | | LISTED ON THE DRAWINGS (17-1212.21) - PLEASE PROVIDE | | | THE PRODUCT APPROVALS THAT ARE LISTED ON THE DRAWINGS. | | | DRAWINGS WILL NEED TO BE REVISED IF CHANGING PRODUCT | | | APPROVALS BECAUSE THE PRODUCT APPROVAL NUMBERS ARE | | | LISTED ON THE DRAWINGS. | | | | | | 3) PRODUCT APPROVAL PROVIDED FOR THE DOOR (17347.11) IS | | | NOT THE PRODUCT APPROVAL NUMBER LISTED ON THE DRAWINGS | | | (17184.11) - PLEASE PROVIDE THE PRODUCT APPROVALS THAT | | | ARE LISTED ON THE DRAWINGS. DRAWINGS WILL NEED TO BE | | | REVISED IF CHANGING PRODUCT APPROVALS BECAUSE THE | | | PRODUCT APPROVAL NUMBERS ARE LISTED ON THE DRAWINGS. | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-22 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-22 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2021-07-22 11:15:24 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWING A0.2 SHOWS THE CODE AS (THE INTERNATIONAL | | | AND WIND DESIGN PER ASCE 7-05) DRAWING A2.1 FOUNDATION | | | DETAILS SHOWS ASCE 7-10 - PLEASE CHECK ALL DRAWINGS - | | | CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE THE | | | DRAWINGS SHOWING THE DESIGN PER THE CODE IN EFFECT | | | (2020 FBC AND ASCE 7-16) | | | 2) DO NOT SEE THE CONTAINER SPECS - NEED A CONTAINER | | | DESIGNATION NUMBER/SERIAL NUMBER SOMETHING STATING THE | | | CORRECT CONTAINER IS BEING USED AS A COMPONENT TO YOUR | | | DESIGN - THE CONTAINER IS THE STRUCTURAL BUILDING SO | | | PLEASE SHOW THE CONTAINER SPECIFICATIONS ON THE | | | DRAWINGS. | | | 3) PLEASE SHOW HOW AND WHAT STRUCTURAL ELEMENT THAT THE | | | ALL THREAD IS ATTACHED TO - PLEASE PROVIDE DETAILS FOR | | | THE AIR HANDLER SUPPORT SHOWN IN THE HALLWAY CEILING. | | | 4) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG | | | WINDOWS (20-0813.08) IS NOT THE PRODUCT APPROVAL NUMBER | | | LISTED ON THE DRAWINGS (17-1212.21) - PLEASE PROVIDE | | | THE PRODUCT APPROVALS THAT ARE LISTED ON THE DRAWINGS. | | | DRAWINGS WILL NEED TO BE REVISED IF CHANGING PRODUCT | | | APPROVALS BECAUSE THE PRODUCT APPROVAL NUMBERS ARE | | | LISTED ON THE DRAWINGS. | | | 5) PRODUCT APPROVAL PROVIDED FOR THE DOOR (17347.11) IS | | | NOT THE PRODUCT APPROVAL NUMBER LISTED ON THE DRAWINGS | | | (17184.11) - PLEASE PROVIDE THE PRODUCT APPROVALS THAT | | | ARE LISTED ON THE DRAWINGS. DRAWINGS WILL NEED TO BE | | | REVISED IF CHANGING PRODUCT APPROVALS BECAUSE THE | | | PRODUCT APPROVAL NUMBERS ARE LISTED ON THE DRAWINGS. | | | 6) PRODUCT APPROVAL FOR THE LOW SLOPE ROOFING | | | (180919.07) IS NOT THE PRODUCT APPROVAL LISTED ON THE | | | DRAWINGS (35402) - PLEASE PROVIDE THE PRODUCT APPROVALS | | | THAT ARE LISTED ON THE DRAWINGS. DRAWINGS WILL NEED TO | | | BE REVISED IF CHANGING PRODUCT APPROVALS BECAUSE THE | | | PRODUCT APPROVAL NUMBERS ARE LISTED ON THE DRAWINGS. | | | 7) SITE PLAN PROVIDED DOES NOT SHOW THE BUILDING | | | DISTANCE FROM THE PROPERTY LINES, DOES NOT SHOW THE | | | FLOOD ZONE, DOES NOT SHOW GRADE ELEVATIONS - PLEASE | | | PROVIDE A SURVEY/SITE PLAN SHOWING THE FOLLOWING | | | INFORMATION 107.2.5 SITE PLAN. THE CONSTRUCTION | | | DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT | | | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE | | | THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS | | | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN | | | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE | | | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE | | | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED | | | WATER RETAINING SWALES) | | | 8) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION | | | APPEARS TO BE LOW - PLEASE PROVIDE A COST BREAKDOWN - | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL ? SWIFT, MEANS, ETC.) AS PUBLISHED | | | BY INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-02-24 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-02-23 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2021-02-24 08:38:34 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE | | | THE DRAWINGS SHOWING THE DESIGN PER THE CODE IN EFFECT | | | (2020 FBC AND ASCE 7-16) | | | 2) THE CONTAINER IS THE STRUCTURAL BUILDING SO PLEASE | | | SHOW THE CONTAINER SPECIFICATIONS ON THE DRAWINGS. | | | 3) PLEASE PROVIDE DETAILS FOR THE AIR HANDLER SUPPORT | | | SHOWN IN THE HALLWAY CEILING. | | | 4) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG | | | WINDOWS (20-0813.08) IS NOT THE PRODUCT APPROVAL NUMBER | | | LISTED ON THE DRAWINGS (17-1212.21) - PLEASE PROVIDE | | | THE PRODUCT APPROVALS THAT ARE LISTED ON THE DRAWINGS. | | | DRAWINGS WILL NEED TO BE REVISED IF CHANGING PRODUCT | | | APPROVALS BECAUSE THE PRODUCT APPROVAL NUMBERS ARE | | | LISTED ON THE DRAWINGS. | | | 5) PRODUCT APPROVAL PROVIDED FOR THE DOOR (17347.11) IS | | | NOT THE PRODUCT APPROVAL NUMBER LISTED ON THE DRAWINGS | | | (17347.17) - PLEASE PROVIDE THE PRODUCT APPROVALS THAT | | | ARE LISTED ON THE DRAWINGS. DRAWINGS WILL NEED TO BE | | | REVISED IF CHANGING PRODUCT APPROVALS BECAUSE THE | | | PRODUCT APPROVAL NUMBERS ARE LISTED ON THE DRAWINGS. | | | 6) PRODUCT APPROVAL FOR THE LOW SLOPE ROOFING = PLEASE | | | CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT | | | APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED | | | ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR | | | ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A | | | HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT | | | APPROVAL. (FBC TABLE R301.2(2) SHOWS ZONE 3 PRESSURE AT | | | (-89.4) ) | | | 7) PLEASE PROVIDE A SURVEY/SITE PLAN SHOWING THE | | | FOLLOWING INFORMATION 107.2.5 SITE PLAN. THE | | | CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION | | | FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING | | | TO SCALE THE SIZE AND LOCATION OF NEW CONSTRUCTION AND | | | EXISTING STRUCTURES ON THE SITE, DISTANCES FROM LOT | | | LINES, THE ESTABLISHED STREET GRADES AND THE PROPOSED | | | FINISHED GRADES, DEPICTING THE PROPOSED LOT DRAINAGE | | | AND, AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND | | | DESIGN FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN | | | ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A BOUNDARY | | | LINE SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY | | | PROPOSED WATER RETAINING SWALES) | | | 8) DRAWINGS NEED TO BE SIGNED BY THE ARCHITECT. | | | 9) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION | | | APPEARS TO BE LOW - PLEASE PROVIDE A JOB VALUE | | | BREAKDOWN. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2021-10-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-10-06 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-10-06 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-22 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-22 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2021-07-22 14:20:49 | SEE COMMENT FROM LAST REVIEW JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-02-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-02-10 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-02-10 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2021-02-10 15:33:08 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SMOKE ALARM MISSING ON THE OUTSIDE OF THE BEDROOMS. | | | | | | 2) SHOW LOCATION OF PANEL, AND ADD NOTE FOR SUBFEED TO | | | PANEL MUST BE UNDERGROUND OR A MAIN WILL BE REQIRED | | | OUTSIDE BY THE METER. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2022-01-03 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2021-12-09 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-01 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-10-22 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-10-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-10-06 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-09-09 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-07-22 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-07-12 |
Time |
12:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-02-24 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-28 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-02-28 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-02-28 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-01-06 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2022-02-25 09:02:03 | RECEIPT MU-2022-1383 - $9968.61 PAID | | 2022-01-06 15:51:10 | 01/06/22 EMAILED IMPACT FOR REVIEW AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-02-24 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-02-24 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2021-02-24 08:46:57 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2021-12-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-10 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-10 |
Time |
10:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-10-25 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-10-25 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2021-10-25 15:47:07 | I SEE THE RESCHECK, THIS IS FOR THE ENERGY AND | | | INSULATION VALUES. PLEASE PROVIDE ME WITH THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS, IN OTHER | | | WORDS PLEASE SHOW ME HOW IT WAS DETERMINED THAT THIS | | | PROJECT NEEDED A 1.5 TON MECHANICAL SYSTEM. PLEASE | | | REACH OUT TO K O ENERGY DESIGNS AND ASK FOR THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC EC | | | R403.7.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-09-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-09-20 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-09-20 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2021-09-20 11:34:43 | PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC R403.7 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-07-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-21 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-21 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2021-07-21 09:15:53 | 1) MECHANICAL DESIGN MUST BE DRAWN BY EITHER A LICENSED | | | ENGINEER, THE ARCHITECT OR THE MECHANICAL CONTRACTOR | | | THAT HOLDS THE PERMIT TO INSTALL THE MECHANICAL SYSTEM | | | FOR THIS PROJECT. | | | 2) I STILL DO NOT SEE THE ENERGY CALCULATIONS. | | | 3) I STILL DO NOT SEE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. THESE ALSO MUST BE DESIGNED BY A LICENSED | | | ENGINEER, THE ARCHITECT OR THE MECHANICAL CONTRACTOR | | | THAT HOLDS THE PERMIT TO INSTALL THE MECHANICAL SYSTEM | | | FOR THIS PROJECT. FS 471.003(H) | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-02-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-05 |
Time |
06:19 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-05 |
Time |
05:51 |
Sent To |
|
|
| Notes |
| 2021-02-05 06:19:16 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21010734 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2020 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2020 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC | | | 101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC R403.7.1 | | | | | | 3) PLEASE SUBMIT A CODE COMPLIANT MECHANICAL DRAWING. | | | FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2021-09-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-09-24 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-09-24 |
Time |
14:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-07-22 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-07-22 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-02-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-02-10 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-02-10 |
Time |
07:06 |
Sent To |
|
|
| Notes |
| 2021-02-10 08:30:02 | 1ST REVIEW FBC-2020 RES. | | | PERMIT- 21010734 | | | 2/10/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET S-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE | | | WATER HEATER INDICATING MAKE, MODEL, GALLON SIZE, AND | | | EFFICIENCY RATING- TABLE C404.2 FBC EC. SUBMIT AN | | | ENERGY COMPLIANCE REPORT FOR THE NEW RESIDENCE AND | | | INCLUDE THE WATER HEATER DATA IN THE REPORT- SECTION | | | R101.5 FBC EC. PLEASE NOTE COMPLETE MANUFACTURER'S | | | SPECIFICATIONS FOR THE WATER HEATER CAN BE SUBMITTED | | | FOR REVIEW OR SHALL BE ONSITE WITH THE INSTALLATION | | | MANUAL AT TIME OF INSPECTION- SECTION 107.2.1 WPB. | | | | | | 2) S1 SANITARY RISER: A) SHOW ALL FIXTURE DRAIN SIZES- | | | TABLE P3201.7 FBC RES. B) SHOW THE WASHING MACHINE | | | STANDPIPE SIZE AND THE CONNECTING VERTICAL STACK SIZE- | | | TABLE P3201.7 FBC RES, AND SECTION 406.2 FBC P. | | | | | | 3) A-1, S-1: SHOW THE LOCATIONS OF THE WATER SUPPLY | | | SHUTOFF VALVES TO THE NEW WASHING MACHINE TO VERIFY | | | ACCESS WILL BE PROVIDED IN ACCORDANCE WITH SECTION | | | P2903.9.3 FBC RES. | | | | | | 4) S1: SHOW THE LOCATIONS OF THE POTABLE WATER SUPPLY | | | LINE ENTRANCE AND MAIN SHUTOFF VALVE- SECTIONS P2901.1, | | | P2903.1, & P2903.9.1 FBC RES. | | | | | | 5) PLEASE NOTE THAT SEPARATE PERMITS AND PLANS ARE | | | REQUIRED FOR THE POTABLE WATER BACKFLOW PREVENTER, GAS | | | PIPING, AND IRRIGATION SYSTEMS- SECTION 105.1 & SECTION | | | 107.2.1 WPB. | | | | | | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR | | | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE | | | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB | | | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL | | | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT | | | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. | | | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS | | | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-07-22 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-07-22 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2021-07-22 14:54:46 | A SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE | | | IRRIGATION SYSTEM. COMPLETE PLANS AND SPECIFICATIONS | | | SHALL BE SUBMITTED. | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
6 |
Status |
N |
Date |
2021-12-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-29 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-29 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2021-12-29 07:32:06 | ROOFING TO BE DEFERRED |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
F |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-20 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-20 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2021-12-20 08:51:26 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-01 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-01 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2021-11-01 13:52:10 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2021-09-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-21 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-21 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-22 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-22 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2021-07-22 11:16:39 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-02-24 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-02-24 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2021-02-24 08:47:59 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-20 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-20 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-01 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-01 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-09-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-09-21 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-21 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2021-09-21 11:33:37 | SIGNATURE REVIEW | | | | | | DOCUMENT LABELED " RAS117 GREENWOOD2 DOC.PDF " IN THE | | | SUPPORTING DOC'S FOLDER IN PROJECTDOX - NEEDS TO BE | | | SIGNED AND SEALED BY THE DESIGNER FBC WPB 107.1 | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | | DIVISION AT THE CITY HALL. | | | | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-22 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-22 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-02-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-05 |
Time |
06:21 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-05 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2021-02-05 06:22:58 | PLEASE SUBMIT ORIGINAL DIGITALLY SIGNED AND SEALED | | | DRAWINGS OR YOU MAY BRING ORIGINAL SIGNED AND SEALED | | | PAPER DRAWINGS TO OUR OFFICE. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2022-01-03 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2022-01-03 |
Time |
12:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2021-10-29 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-10-29 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-10-29 12:38:32 | ********************ZONING | | | REVIEW*************************** | | | | | | NEW RESIDENTIAL DEVELOPMENT TRIGGERS THE LANDSCAPE | | | CODE. | | | | | | PROVIDE A SEPARATE LANDSCAPE AND IRRIGATION PLAN | | | SHOWING THE FOLLOWING: | | | | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2021-09-16 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-09-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2021-09-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-09-16 16:02:41 | ********************ZONING | | | REVIEW*************************** | | | | | | NEW RESIDENTIAL DEVELOPMENT TRIGGERS THE LANDSCAPE | | | CODE. | | | | | | PROVIDE A SEPARATE LANDSCAPE AND IRRIGATION PLAN | | | SHOWING THE FOLLOWING: | | | | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-07-22 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-07-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2021-07-22 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-07-22 09:52:39 | ***************ZONING REVIEW FAILED************ | | | | | | | | | PROVIDE A SITE PLAN FOR THE PROPOSED HOME INDICATING | | | ALL SETBACKS. | | | | | | NEW RESIDENTIAL DEVELOPMENT TRIGGERS THE LANDSCAPE | | | CODE. | | | | | | PROVIDE A SEPARATE LANDSCAPE AND IRRIGATION PLAN | | | SHOWING THE FOLLOWING: | | | | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRE A | | | SEPARATE PERMIT. | | | | | | ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW. | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-02-11 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-02-11 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2021-02-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-02-11 15:21:03 | ***************ZONING REVIEW FAILED************ | | | | | | | | | PROVIDE A SURVEY FOR THE PROPERTY. | | | | | | PROVIDE A SITE PLAN FOR THE PROPOSED HOME INDICATING | | | ALL SETBACKS FOR THE SINGLE FAMILY DISTRICT (SF-7). | | | | | | NEW RESIDENTIAL DEVELOPMENT TRIGGERS THE LANDSCAPE | | | CODE. | | | | | | PROVIDE A SEPARATE LANDSCAPE AND IRRIGATION PLAN | | | SHOWING THE FOLLOWING: | | | | | | RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM | | | BEACH | | | SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS | | | | | | O GROSS LOT SQUARE FOOTAGE MINUS | | | O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS | | | O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA) | | | O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE | | | OR PORTION THEREOF | | | | | | THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRE A | | | SEPARATE PERMIT. | | | | | | ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW. | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] | | | | | | |
|
|