| 2021-02-02 13:33:50 | 02/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE CLARIFY IF THE TANK-LESS YOU ARE REPLACING |
| | HAD AN OLD TANK-LESS AT THAT SAME LOCATION. INDICATE ON |
| | DRAWING PLAN IF THE TANK-LESS WATER HEATER IS REPLACING |
| | AN EXISTING TANK-LESS WATER HEATER OR IS IT REPLACING A |
| | STORAGE TANK-TYPE WATER HEATER OR IS IT BEING ADDED TO |
| | THE EXISTING HOT WATER SYSTEM? INDICATE ON THE |
| | APPLICATION IN THE DESCRIPTION OF WORK PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 3. THERE MAY BE GAS PIPING OUTSIDE BUT WE WILL REQUIRE |
| | MORE INFORMATION SO PLEASE SUBMIT A COMPLETE GAS RISER |
| | SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED |
| | LENGTH TO THE FURTHEST GAS OUTLET, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE OF GAS, AND |
| | THE TOTAL BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS |
| | ALSO APPLY TO A NEW GAS SYSTEM PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | 4. PLEASE THE MANUAL FOR INSTALLATION CLEARANCES FROM |
| | THE RINNAI. IF THE MANUAL REQUIRES A CLEARANCE OF |
| | EITHER 4 FEET OR 12 INCHES FROM ANY OPERABLE WINDOWS OR |
| | DOORS. SHOW THE LOCATION OF ALL OPERABLE WINDOWS AND |
| | DOORS ON THE PLAN AND THE DISTANCE OF THE TANK-LESS |
| | WATER HEATER FROM EACH. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 6. THIS TANK-LESS UNIT MAY CALL FOR A 10.5? WATER |
| | COLUMN AND THE SERVICE METER DISCHARGES IS A 12? WATER |
| | COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1. PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1? OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| | G2421.2 OR 2017 FBC FG SEC 410.2. |
| | |
| | 7. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS |
| | ISOMERIC PER THE 2020 FBC RES. SEC. G2401.1.3. |
| | |
| | 8. PLEASE SHOW AND LABEL DRIP LEG ON TANK-LESS WATER |
| | HEATER INSTALLED PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | 9. WATER PIPES OUTSIDE AND NOT IN CONDITION SPACE NEED |
| | TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC |
| | SEC. RE 403.5.3 |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |