Plan Review Details - Permit 21010716
Plan Review Stops For Permit 21010716
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-02-08 Cont ID  
Sent By lcrespo Date 2021-02-08 Time 11:10 Rev Time 0.00
Received By lcrespo Date 2021-02-08 Time 11:10 Sent To  
Notes
2021-02-08 11:11:2902/08/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-02 Cont ID  
Sent By lcrespo Date 2021-02-02 Time 13:34 Rev Time 0.00
Received By lcrespo Date 2021-02-02 Time 13:32 Sent To  
Notes
2021-02-02 13:33:5002/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE CLARIFY IF THE TANK-LESS YOU ARE REPLACING
 HAD AN OLD TANK-LESS AT THAT SAME LOCATION. INDICATE ON
 DRAWING PLAN IF THE TANK-LESS WATER HEATER IS REPLACING
 AN EXISTING TANK-LESS WATER HEATER OR IS IT REPLACING A
 STORAGE TANK-TYPE WATER HEATER OR IS IT BEING ADDED TO
 THE EXISTING HOT WATER SYSTEM? INDICATE ON THE
 APPLICATION IN THE DESCRIPTION OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 3. THERE MAY BE GAS PIPING OUTSIDE BUT WE WILL REQUIRE
 MORE INFORMATION SO PLEASE SUBMIT A COMPLETE GAS RISER
 SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED
 LENGTH TO THE FURTHEST GAS OUTLET, THE BTU LOAD OF EACH
 APPLIANCE, THE PSI OF THE SYSTEM, THE TYPE OF GAS, AND
 THE TOTAL BTU LOAD ON THE SYSTEM. THESE REQUIREMENTS
 ALSO APPLY TO A NEW GAS SYSTEM PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 4. PLEASE THE MANUAL FOR INSTALLATION CLEARANCES FROM
 THE RINNAI. IF THE MANUAL REQUIRES A CLEARANCE OF
 EITHER 4 FEET OR 12 INCHES FROM ANY OPERABLE WINDOWS OR
 DOORS. SHOW THE LOCATION OF ALL OPERABLE WINDOWS AND
 DOORS ON THE PLAN AND THE DISTANCE OF THE TANK-LESS
 WATER HEATER FROM EACH. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. THIS TANK-LESS UNIT MAY CALL FOR A 10.5? WATER
 COLUMN AND THE SERVICE METER DISCHARGES IS A 12? WATER
 COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1. PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1? OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2 OR 2017 FBC FG SEC 410.2.
  
 7. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC RES. SEC. G2401.1.3.
  
 8. PLEASE SHOW AND LABEL DRIP LEG ON TANK-LESS WATER
 HEATER INSTALLED PER THE 2020 FBC RES. SEC. G2419.2.
  
 9. WATER PIPES OUTSIDE AND NOT IN CONDITION SPACE NEED
 TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC
 SEC. RE 403.5.3
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-08 Cont ID  
Sent By lcrespo Date 2021-02-08 Time 11:11 Rev Time 0.00
Received By lcrespo Date 2021-02-05 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-02 Cont ID  
Sent By lcrespo Date 2021-02-02 Time 13:34 Rev Time 0.00
Received By lcrespo Date 2021-01-29 Time 11:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-08 Cont ID  
Sent By lcrespo Date 2021-02-08 Time 11:05 Rev Time 0.00
Received By lcrespo Date 2021-02-08 Time 11:05 Sent To  
Notes
2021-02-08 11:05:3502/08/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-02 Cont ID  
Sent By lcrespo Date 2021-02-02 Time 13:34 Rev Time 0.00
Received By lcrespo Date 2021-02-02 Time 13:34 Sent To  
Notes
2021-02-02 13:35:07PLEASE REFER TO GAS COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-02-02 Cont ID  
Sent By lcrespo Date 2021-02-02 Time 13:35 Rev Time 0.00
Received By lcrespo Date 2021-02-02 Time 13:35 Sent To  
Notes
2021-02-02 13:38:19NO DRAWING WHERE SUBMITTED AT THIS TIME PLEASE REFER TO
 GAS COMMENT #5 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.