Plan Review Details - Permit 21010688
Plan Review Stops For Permit 21010688
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-19 Cont ID  
Sent By equinone Date 2021-02-19 Time 12:10 Rev Time 0.00
Received By equinone Date 2021-02-19 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-05 Cont ID  
Sent By equinone Date 2021-02-05 Time 15:45 Rev Time 0.00
Received By equinone Date 2021-02-04 Time 16:06 Sent To  
Notes
2021-02-05 15:46:15CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET GC-002, GENERAL ELECTRICAL NOTES (NOTE 1):
 PLEASE MODIFY TO REFLECT EXISTING CURRENT CODES IN
 EFFECT FBC 2020 7TH EDITION, NEC 2017).
 2) PLEASE PROVIDE UPDATED AVAILABLE SHORT CIRCUIT
 CURRENT (AIC) AT SERVICE LOCATION (FPL LETTER)
 3) SHEET E-001 AND E-004: RISER DIAGRAM ON E-001
 SPECIFIES SIX SETS OF 4#500 KCMIL + 1#1/0 G FROM ATS TO
 MSB WHILE E-004 (MSB SCHEDULE) SHOWS 6 SETS OF 4#600
 MCM + 1#1/0 GND. PLEASE CORRECT DISCREPANCIES. FBC 107
 4) SHEET E-004 (MSB CKT 32,34,36 FOR LIFT STATION).
 BREAKER IS 60 AMPS AND CONDUCTOR IS #8 WITH AMPACITY OF
 50 AMPS. PLEASE INCREASE CONDUCTOR SIZE.
 5) SEE SIGNATURE COMMENTS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-19 Cont ID  
Sent By equinone Date 2021-02-19 Time 12:10 Rev Time 0.00
Received By equinone Date 2021-02-15 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-05 Cont ID  
Sent By equinone Date 2021-02-05 Time 15:45 Rev Time 0.00
Received By equinone Date 2021-01-20 Time 10:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-19 Cont ID  
Sent By equinone Date 2021-02-19 Time 12:10 Rev Time 0.00
Received By equinone Date 2021-02-19 Time 12:10 Sent To  
Notes
2021-02-19 12:12:15ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 RESPONSE DOCUMENTS MENTIONS THAT NEW DRAWIGNS WILL HAVE
 THE SEAL AND ELECTRONIC SIGNATURE, HOWEVER THEY ARE
 STILL MISSING THE ELECTRONIC SEAL AND SIGNATURE.
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A DIGITALLY
 SIGNED PLAN IS NOT CONSIDERED AN ORIGINAL, PDF MUST
 HAVE THE INTEGRATED DIGITAL SIGNATURE.
  
 EITHER SUBMIT A DIGITALLY OR ELECTRONICALLY SIGNED
 PLAN, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL SIGNED
 AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-05 Cont ID  
Sent By equinone Date 2021-02-05 Time 15:45 Rev Time 0.00
Received By equinone Date 2021-02-05 Time 15:45 Sent To  
Notes
2021-02-05 15:48:46ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A DIGITALLY
 SIGNED PLAN IS NOT CONSIDERED AN ORIGINAL, PDF MUST
 HAVE THE INTEGRATED DIGITAL SIGNATURE.
  
 EITHER SUBMIT A DIGITALLY OR ELECTRONICALLY SIGNED
 PLAN, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL SIGNED
 AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE.
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved