| 2021-02-04 23:51:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. METERCAN SHOWN IS A 400AMP/320AMP CONTINUOUS METER |
| | CAN. PLEASE LABEL AS 400AMP METER CAN. |
| | |
| | 2. CANNOT DE-RATE SERVICE ENTRANCE CONDUCTORS WHEN MORE |
| | THAN ONE PANEL SERVES THE LOAD OF A DWELLING. 3/0 CU |
| | REQUIRED FOR 200AMP, 2/0 CU SHOWN. NEC 310.15B7 |
| | |
| | 3. PROVIDE SPECS FOR TESLA CHARGER. FBC 107.2.1 |
| | |
| | 4. NO WIRE SIZES SHOWN FOR TESLA CHARGER. FBC 107.2.1 |
| | |
| | 5. PROVIDE CLARIFICATION THAT SERVICE MAINS ARE |
| | GROUPED. NEC 230.72A |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |