Plan Review Details - Permit 21010654
Plan Review Stops For Permit 21010654
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-02-22 Cont ID  
Sent By rmcphers Date 2022-02-22 Time 12:58 Rev Time 0.00
Received By rmcphers Date 2022-02-22 Time 12:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-01-21 Cont ID  
Sent By rmcphers Date 2022-01-21 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2022-01-21 Time 12:53 Sent To  
Notes
2022-01-21 12:57:09SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) YOU HAVE PROVIDED EXTERIOR DOOR INSTALLATION
 INSTRUCTIONS - I CANNOT FIND THE FRONT PAGES ON THE
 FLORIDA PRODUCT APPROVAL WEB SITE - PLEASE PROVIDE
 COMPLETE MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL
 FOR THE EXTERIOR DOOR.
  
 2) YOU PROVIDED A PRODUCT APPROVAL FOR ROOF SHINGLES -
 THE ADDITION THAT YOU ARE BUILDING HAS A LOW SLOPE ROOF
 - SHINGLES CANNOT BE APPROVED FOR A LOW SLOPE ROOF.
 PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A
 HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT
 APPROVAL.
  
 3) DRAWINGS A-3 AND M-1 STILL SHOW A BATHROOM ADDITION.
 PLEASE CORRECT.
  
 4) ROOFING SYSTEM AND WINDOW AND DOOR PRODUCT APPROVALS
 MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE
 DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 15:09 Rev Time 0.00
Received By rmcphers Date 2021-06-04 Time 14:53 Sent To  
Notes
2021-06-04 15:07:56SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT) FROM A
 SOIL ENGINEER FBC R401.4
 2) YOU HAVE PROVIDED EXTERIOR DOOR INSTALLATION
 INSTRUCTIONS - I CANNOT FIND THE FRONT PAGES ON THE
 FLORIDA PRODUCT APPROVAL WEB SITE - PLEASE PROVIDE
 COMPLETE MIAMI DADE OR FLORIDA STATE PRODUCT APPROVAL
 FOR THE EXTERIOR DOOR.
 3) YOU PROVIDED A PRODUCT APPROVAL FOR ROOF SHINGLES -
 THE ADDITION THAT YOU ARE BUILDING HAS A LOW SLOPE ROOF
 - SHINGLES CANNOT BE APPROVED FOR A LOW SLOPE ROOF.
 PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A
 HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT
 APPROVAL.
 4) ROOFING SYSTEM AND WINDOW AND DOOR PRODUCT APPROVALS
 MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE
 DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-02 Cont ID  
Sent By rmcphers Date 2021-04-02 Time 12:55 Rev Time 0.00
Received By rmcphers Date 2021-04-02 Time 12:32 Sent To  
Notes
2021-04-02 12:50:48SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PROVIDE A SIGNED AND SEALED SOIL REPORT OR PROVIDE A
 STATEMENT ON THE DRAWINGS THAT THE EXISTING SOIL
 BEARING CAPACITY MEETS THE REQUIRED DESIGN SOIL BEARING
 CAPACITY. FBC R401.4
 2) DOOR AND WINDOW PRODUCT APPROVALS PROVIDED REQUIRE
 SHUTTERS - PLEASE PROVIDE THE COMPLETE MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVAL FOR THE SHUTTERS
 (REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD).
 3) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE FRONT
 PAGES FOR THE EXTERIOR DOOR PRODUCT APPROVAL PROVIDED
 (THE INSTALLATION INSTRUCTIONS HAVE BEEN PROVIDED).
 4) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE FLAT DECK ROOFING =
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND
 SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY
 REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE
 PRODUCT APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By rmcphers Date 2021-02-12 Time 09:36 Rev Time 0.00
Received By rmcphers Date 2021-02-11 Time 15:43 Sent To  
Notes
2021-02-12 09:36:53SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE
 THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN EFFECT
 (2020 FBC AND ASCE 7-16)
 2) DRAWINGS SHOULD SHOW THE FOUNDATION SOIL BEARING
 PRESSURE. FBC R401.2
 3) PROVIDE A SIGNED AND SEALED SOIL REPORT OR PROVIDE A
 STATEMENT ON THE DRAWINGS THAT THE EXISTING SOIL
 BEARING CAPACITY MEETS THE REQUIRED DESIGN SOIL BEARING
 CAPACITY. FBC R401.4
 4) PLEASE SHOW THE PROPOSED ROOF SLOPE FBC
 R905.9.1SLOPE.
 BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF NOT LESS
 THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) FOR DRAINAGE.
 5) PLEASE CLARIFY THE JOIST WIDTH - DRAWING A2 SHOWS 2
 X 10 JOIST - DRAWING A3 SHOWS 2 X 12 JOIST.
 6) IF USING 2X10 JOIST - R30 BAT INSULATION DOES NOT
 ALLOW FOR THE REQUIRED 1 INCH AIR GAP FBC R806.3VENT
 AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING,
 BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW
 OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.
 7) THE SOFFIT VENTILATION SHOULD BE A CONTINUOUS SCREEN
 VENT TO ALLOW EACH ENCLOSED RAFTER SPACE TO VENT FBC
 R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE
 8) PLEASE PROVIDE A COMPLETE FLOOR PLAN OF THE EXISTING
 HOUSE TO SHOW THE LOCATION OF THE EXISTING OR ADDED
 SMOKE DETECTORS PER FBC R314.2.2ALTERATIONS, REPAIRS
 AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 9) DOOR AND WINDOW PRODUCT APPROVALS PROVIDED REQUIRE
 SHUTTERS - PLEASE PROVIDE THE COMPLETE MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVAL FOR THE SHUTTERS
 (REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD).
 10) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE
 FRONT PAGES FOR THE EXTERIOR DOOR PRODUCT APPROVAL
 PROVIDED (THE INSTALLATION INSTRUCTIONS HAVE BEEN
 PROVIDED).
 11) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE FLAT DECK ROOFING =
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND
 SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY
 REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE
 PRODUCT APPROVAL.
 12) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - (JOB VALUE IS MATERIAL AND LABOR AS
 IF A CONTRACTOR PRICED THE JOB) - ICC VALUE SCHEDULE =
 326 SQ. FEET X $122 PER SQ. FOOT = $39,772.00 - PLEASE
 REVISE THE BUILDING PERMIT APPLICATION TO SHOW THE
 ACTUAL JOB VALUE. FBC WPB AMENDMENTS ? FOR PERMITTING
 PURPOSES THE VALUE OF ALL LABOR AND MATERIALS REQUIRED
 TO COMPLETE THE PROJECT ARE REQUIRED TO BE INCLUDED IN
 THE COST. FBC 109.3 BUILDING PERMIT VALUATION. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL ? SWIFT, MEANS, ETC.) AS PUBLISHED
 BY INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2022-03-02 Cont ID  
Sent By mpeterso Date 2022-03-02 Time 09:59 Rev Time 0.00
Received By mpeterso Date 2022-03-02 Time 09:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-01-28 Cont ID  
Sent By fgiaquin Date 2022-01-28 Time 23:02 Rev Time 0.00
Received By fgiaquin Date 2022-01-28 Time 22:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-05-24 Cont ID  
Sent By equinone Date 2021-05-24 Time 12:46 Rev Time 0.00
Received By equinone Date 2021-05-24 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-30 Cont ID  
Sent By equinone Date 2021-03-30 Time 14:28 Rev Time 0.00
Received By equinone Date 2021-03-30 Time 14:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-04 Cont ID  
Sent By equinone Date 2021-02-04 Time 10:08 Rev Time 0.00
Received By equinone Date 2021-02-04 Time 09:42 Sent To  
Notes
2021-02-04 10:08:38CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) RISER DIAGRAM: PLEASE IDENTIFY PANELS (NEW CIRCUITS
 ARE SHOWN AS COMING FROM PANEL B BUT NOT CLEAR WHICH
 ONE IS PANEL B AND WHAT THE OTHER PANEL IS CALLED)
 2) IS 100 AMPS SUBPANEL EXISTING? IF NEW OR MODIFIED
 PLEASE PROVIDE PANEL SCHEDULE
 3) AFCI NOTE: PLEASE MODIFY NOTE TO INCLUDE RECEPTACLES
 IN SITTING AREA.
  
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. NEC 210.12; FBC RE E3902.16
  
 4) PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 5) PLEASE MODIFY NOTE THAT SAYS "ALL ELECTRICAL WORK AS
 PER N.E.C........" TO INCLUDE THE CURRENT CODE EDITION
 NEC 2017, FBC RE 2020.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-03-02 Cont ID  
Sent By mpeterso Date 2022-03-02 Time 09:59 Rev Time 0.00
Received By mpeterso Date 2022-02-16 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-04 Cont ID  
Sent By vbroglia Date 2022-02-04 Time 15:23 Rev Time 0.00
Received By vbroglia Date 2022-01-19 Time 12:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 15:14 Rev Time 0.00
Received By rmcphers Date 2021-05-17 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-14 Cont ID  
Sent By cthroop Date 2021-04-14 Time 09:26 Rev Time 0.00
Received By cthroop Date 2021-03-24 Time 11:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-12 Cont ID  
Sent By rmcphers Date 2021-02-12 Time 09:45 Rev Time 0.00
Received By rmcphers Date 2021-01-20 Time 13:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-04-12 Cont ID  
Sent By lmarchan Date 2022-04-12 Time 13:33 Rev Time 0.00
Received By lmarchan Date 2022-04-08 Time 10:10 Sent To  
Notes
2022-04-12 13:33:11RECEIPT MU-2022-015974 - NO FEES DUE. LEM
2022-04-08 10:10:564/8/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By rmcphers Date 2021-02-12 Time 09:37 Rev Time 0.00
Received By rmcphers Date 2021-02-12 Time 09:37 Sent To  
Notes
2021-02-12 09:37:47PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2022-02-23 Cont ID  
Sent By medwards Date 2022-02-23 Time 08:58 Rev Time 0.00
Received By medwards Date 2022-02-23 Time 08:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-01-20 Cont ID  
Sent By medwards Date 2022-01-20 Time 06:55 Rev Time 0.00
Received By medwards Date 2022-01-20 Time 06:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-05-28 Cont ID  
Sent By medwards Date 2021-05-28 Time 08:22 Rev Time 0.00
Received By medwards Date 2021-05-28 Time 08:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-03-31 Cont ID  
Sent By medwards Date 2021-03-31 Time 17:42 Rev Time 0.00
Received By medwards Date 2021-03-31 Time 17:42 Sent To  
Notes
2021-03-31 17:42:412ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21010654
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS. THERE IS NO
 MECHANICAL SUB PERMIT FOR THIS JOB. PLEASE HAVE A
 LICENSED ENGINEER PROVIDE A SIGNED AND SEALED
 MECHANICAL EQUIPMENT SIZING CALCULATION AND A SIGNED
 AND SEALED MECHANICAL DRAWING.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-27 Cont ID  
Sent By hmoser Date 2021-01-27 Time 15:12 Rev Time 0.00
Received By hmoser Date 2021-01-27 Time 14:59 Sent To  
Notes
2021-01-27 15:11:43PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS FOR ADDITION
 PER SECTION M1401.3 EQUIPMENT SIZING.
 2020 RESIDENTIAL CODE.
 2) REFER TO SECTION R303.3 BATHROOM EXHAUST
 2020 RESIDENTIAL CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2022-10-20 Cont ID  
Sent By rwbrown Date 2022-10-20 Time 15:43 Rev Time 0.00
Received By rwbrown Date 2022-10-20 Time 15:43 Sent To  
Notes
2022-10-20 15:43:55PLUMBING REMOVED FROM SCOPE

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-29 Cont ID  
Sent By lcrespo Date 2021-03-29 Time 10:47 Rev Time 0.00
Received By lcrespo Date 2021-03-29 Time 10:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-01-22 Cont ID  
Sent By lcrespo Date 2021-01-22 Time 05:40 Rev Time 0.00
Received By lcrespo Date 2021-01-22 Time 05:10 Sent To  
Notes
2021-01-22 05:41:2701/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2022-03-04 Cont ID  
Sent By rmcphers Date 2022-03-04 Time 14:33 Rev Time 0.00
Received By rmcphers Date 2022-03-04 Time 14:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2022-02-22 Cont ID  
Sent By rmcphers Date 2022-02-22 Time 12:58 Rev Time 0.00
Received By rmcphers Date 2022-02-22 Time 12:58 Sent To  
Notes
2022-02-22 13:26:22ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED -
  
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL WHICH MEETS THE REQUIRED
 PRESSURES SHOWN ON DRAWING A2. PLEASE HAVE THE BUILDING
 ADDITION DESIGNER OF RECORD (ARCHITECT) REVIEW AND
 APPROVE THE ROOFING PRODUCT APPROVAL FBC WPB 107.3.4
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2022-01-21 Cont ID  
Sent By rmcphers Date 2022-01-21 Time 12:57 Rev Time 0.00
Received By rmcphers Date 2022-01-21 Time 12:57 Sent To  
Notes
2022-01-21 12:57:50SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2021-06-04 Cont ID  
Sent By rmcphers Date 2021-06-04 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2021-06-04 Time 15:10 Sent To  
Notes
2021-06-04 15:11:14SEE BUILDING PLAN REVIEW
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-04-02 Cont ID  
Sent By lcrespo Date 2021-04-02 Time 12:56 Rev Time 0.00
Received By rmcphers Date 2021-04-02 Time 12:56 Sent To  
Notes
2021-04-02 12:56:32SEE BUILDING PLAN REVIEW
 A BUILDING PERMIT APPLICATION (MARKED ROOFING) WILL BE
 REQUIRED
 ROOFING SYSTEM MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By rmcphers Date 2021-02-12 Time 09:41 Rev Time 0.00
Received By rmcphers Date 2021-02-12 Time 09:37 Sent To  
Notes
2021-02-12 09:44:11SEE BUILDING PLAN REVIEW
 A BUILDING PERMIT APPLICATION (MARKED ROOFING) WILL BE
 REQUIRED
 ROOFING SYSTEM MAY BE DEFERRED SUBMITTALS BY LISTING
 ITEMS TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS -
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-02-17 Cont ID  
Sent By jgomez Date 2022-02-17 Time 18:18 Rev Time 0.00
Received By jgomez Date 2022-02-17 Time 18:09 Sent To  
Notes
2022-02-17 18:19:56HARD COPY DRAWINGS CV.1, A..1, A.2 AND E1 & H1 HAVE
 ARCHITECT'S ORIGINAL SEAL/SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-01-20 Cont ID  
Sent By mpeterso Date 2022-01-20 Time 16:27 Rev Time 0.00
Received By mpeterso Date 2022-01-20 Time 16:27 Sent To  
Notes
2022-01-20 16:32:19SIGNATURE REVIEW FAILED
 IT APPEARS PAPER PLANS LABELED "E1&H1,A.2,A.1 AND CV.1'
 HAVE A COPY OF AN ARCHITECTS SEAL AND SIGNATURE.
  
 PLEASE FOLLOW THE DIRECTIONS OUTLINED BELOW TO CORRECT
 THIS ISSUE.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected] WITH ANY QUESTIONS
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-18 Cont ID  
Sent By medwards Date 2021-05-18 Time 17:22 Rev Time 0.00
Received By medwards Date 2021-05-18 Time 17:18 Sent To  
Notes
2021-05-18 17:22:50ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By medwards Date 2021-03-25 Time 05:49 Rev Time 0.00
Received By medwards Date 2021-03-25 Time 05:46 Sent To  
Notes
2021-03-25 05:50:04ORIGINAL SIGNED AND SEALED PAPER DOCUMENT ROUTED TO
 STORAGE. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-20 Cont ID  
Sent By medwards Date 2021-01-20 Time 14:18 Rev Time 0.00
Received By medwards Date 2021-01-20 Time 14:12 Sent To  
Notes
2021-01-20 14:17:50ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 4 Status P Date 2022-02-23 Cont ID  
Sent By asangele Date 2022-02-23 Time   Rev Time 0.00
Received By asangele Date 2022-02-23 Time 15:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-02-04 Cont ID  
Sent By vbroglia Date 2022-02-04 Time 15:20 Rev Time 0.00
Received By vbroglia Date 2022-02-04 Time 15:20 Sent To  
Notes
2022-02-04 15:23:492/4/22 FAILED- PLEASE PROVIDE SIDE SETBACKS FROM THE
 HOUSE TO THE SIDE PROPERTY LINE
  
 VALENTINA BROGLIA
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-13 Cont ID  
Sent By kalexand Date 2021-04-13 Time 13:07 Rev Time 0.00
Received By kalexand Date 2021-04-13 Time 13:07 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-02-08 Cont ID  
Sent By kalexand Date 2021-02-08 Time 16:48 Rev Time 0.00
Received By kalexand Date 2021-02-08 Time 16:48 Sent To I
Notes
***NONE***