Plan Review Details - Permit 21010631
Plan Review Stops For Permit 21010631
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-29 Cont ID  
Sent By jwitmer Date 2021-01-29 Time 15:56 Rev Time 0.00
Received By jwitmer Date 2021-01-29 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By jwitmer Date 2021-01-28 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2021-01-28 Time 11:15 Sent To  
Notes
2021-01-28 11:47:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21010631
 ADD: 600 S. DIXIE HWY. SUITE # 637
 CONT: ROYAL PALM FLOORING
 TEL: 561-790-7148
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 28/ 2021
 ACTION: DENIED
  
 1) THE SUBMITTED FLOOR PLAN DOES NOT STATE WHO THE
 AUTHOR IS FOR THE PLAN. PLEASE PRINT YOUR NAME, SIGN
 YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
  
 CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION BY
 CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 2) THE SUBMITTED IIC & STC REPORT STATES ON THE COVER
 SHEET THAT IT IS FOR LUXURY VINYL PLANK OVER LV200
 UNDERLAYMENT. THE PROBLEM IS IT ALSO INCLUDES A DROPPED
 CEILING. THIS REPORT IS NOT ACCEPTABLE BECAUSE OF THE
 DROPPED CEILING. THE PRODO DOES NOT HAVE DROPPED
 CEILINGS THROUGH OUT THE UNITS.
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-01-29 Time 15:57 Rev Time 0.00
Received By ccarvaja Date 2021-01-29 Time 12:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-01-28 Time 11:48 Rev Time 0.00
Received By ccarvaja Date 2021-01-21 Time 18:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-29 Cont ID  
Sent By jwitmer Date 2021-01-29 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2021-01-29 Time 15:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By jwitmer Date 2021-01-28 Time 11:48 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-01-28 11:48:26SEE BUILDING REVIEW CONTRACTOR SIGNATURE, CONTRACTORS
 PRINTED NAME AND LICENSE NUMBER.