Plan Review Details - Permit 21010590
Plan Review Stops For Permit 21010590
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-07-29 Cont ID  
Sent By rmcphers Date 2021-07-29 Time 09:33 Rev Time 0.00
Received By rmcphers Date 2021-07-29 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-07-09 Cont ID  
Sent By rmcphers Date 2021-07-09 Time 09:30 Rev Time 0.00
Received By rmcphers Date 2021-07-09 Time 09:30 Sent To  
Notes
2021-07-09 09:55:01SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE EXTERIOR WALL SHEATHING THICKNESS
 FBC R703.1.2
 2) PLEASE SHOW THE EXTERIOR WALL SHEATHING ATTACHMENTS
 (SIZE OF SCREWS OR NAILS) FBC R703.3.1
 3) PLEASE PROVIDE MANUFACTURE SPECS SHOWING THE USE OF
 "ZIP SYSTEM" AS FLOOR SHEATHING - FBC R503.1
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-22 Cont ID  
Sent By rmcphers Date 2021-06-22 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2021-06-22 Time 15:04 Sent To  
Notes
2021-06-22 15:31:35SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE EXTERIOR WALL SHEATHING TYPE,
 THICKNESS AND ATTACHMENT (NAILING) REQUIREMENTS. FBC
 R703.3.1
 2) PLEASE SHOW FLOOR SHEATHING TYPE, THICKNESS. FBC
 R503.1
 3) PRODUCT APPROVAL PROVIDED FOR THE ROOFING IS FOR AN
 INSULATED ROOF DECK (DRAWINGS DO NOT SHOW INSULATION ON
 TOP OF THE ROOF SHEATHING) AND IT SHOWS A WIND DESIGN
 PRESSURE OF (-60) - WIND ZONE 3 REQUIRES A WIND DESIGN
 PRESSURE OF 108.17 - PLEASE PROVIDE ADDITION ATTACHMENT
 DETAILS FROM AN ARCHITECT OR ENGINEER PER THE PRODUCT
 APPROVAL LIMITATION NOTE NUMBER 7
  
  
 DEFERRED = ROOFING SYSTEM PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-27 Cont ID  
Sent By rmcphers Date 2021-04-27 Time 09:06 Rev Time 0.00
Received By rmcphers Date 2021-04-27 Time 08:51 Sent To  
Notes
2021-04-27 09:06:24SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A FLOOR PLAN (COULD BE HAND DRAWN)
 SHOWING THE LOCATION OF THE EXISTING OR ADDED SMOKE
 DETECTORS PER FBC R314.2.2 ALTERATIONS, REPAIRS AND
 ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 2) PLEASE SHOW THE EXTERIOR WALL SHEATHING TYPE,
 THICKNESS AND ATTACHMENT REQUIREMENTS.
 3) PLEASE SHOW FLOOR SHEATHING TYPE, THICKNESS AND
 ATTACHMENT REQUIREMENTS.
 4) R30 INSULATION WILL NOT ALLOW THE REQUIRED 1 INCH
 AIR GAP BETWEEN THE INSULATION AND THE ROOF SHEATHING
 FOR VENTILATION. FBC R806.3
 5) ROOF VENTILATION - EAVE SHOULD SHOW A CONTINOUS
 SCREEN VENT TO VENT BETWEEN EACH RAFTER FBC R806.1
 6) PLEASE CIRCLE THE ROOFING SYSTEM TYPE (SUCH AS
 SYSTEM TYPE A1 OR A2 ETC) TO BE USED IN THE PRODUCT
 APPROVAL PROVIDED - IF NEEDED PLEASE PROVIDE SIGNED AND
 SEALED ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY
 REQUIRE A HIGHER WIND PRESSURE - SEE NOTES ON THE
 PRODUCT APPROVAL.
  
  
 DEFERRED = ROOFING SYSTEM PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-11 Cont ID  
Sent By rmcphers Date 2021-02-11 Time 10:03 Rev Time 0.00
Received By rmcphers Date 2021-02-10 Time 15:27 Sent To  
Notes
2021-02-11 09:58:40SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING S-2 THE EXTERIOR WALL DETAILS SHOWN APPEARS
 TO BE AN INTERIOR WALL - PLEASE REVISE SHOWING THE
 EXTERIOR WALL FRAMING AND CLADDING DETAILS.
 2) PLEASE SHOW THE EXTERIOR WALL STRAPPING - BOTTOM
 WALL PLATE TO WALL STUD - TOP WALL PLATE TO BEAM. FBC
 R301.2.1 WIND DESIGN CRITERIA. A CONTINUOUS LOAD PATH
 SHALL BE PROVIDED TO TRANSMIT THE APPLICABLE UPLIFT
 FORCES FROM THE ROOF ASSEMBLY TO THE FOUNDATION.
 3) PLEASE SHOW THE ROOF SHEATHING DETAILS TYPE AND
 FASTENING FBC R803.2.3.1SHEATHING FASTENINGS.
 WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO
 ROOF FRAMING IN ACCORDANCE WITH TABLE R803.2.3.1. WHERE
 THE SHEATHING THICKNESS IS 15/32 INCHES AND LESS,
 SHEATHING SHALL BE FASTENED WITH ASTM F1667 RSRS-01
 (23/8" ? 0.113") NAILS. WHERE THE SHEATHING THICKNESS
 IS GREATER THAN 15/32 INCHES, SHEATHING SHALL BE
 FASTENED WITH ASTM F1667 RSRS-03 (21/2" ? 0.131") NAILS
 OR ASTM F1667 RSRS-04 (3" ? 0.120") NAILS. RSRS-01,
 RSRS-03 AND RSRS-04 ARE RING SHANK NAILS MEETING THE
 SPECIFICATIONS IN ASTM F1667.
 4) PLEASE SHOW THE SOFFIT VENT - FBC R806.1VENTILATION
 REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM.
 FBC R806.3 VENT AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING,
 BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW
 OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.
 5) PLEASE SHOW THE EXTERIOR WALL, FLOOR AND CEILING
 INSULATION TYPE AND "R" VALUE TO COMPLY WITH FBC ENERGY
 CONSERVATION R401
 6) PLEASE SHOW WHAT THE ROOF SLOPE IS.
 7) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF
 THE EXISTING OR ADDED SMOKE DETECTORS PER FBC R314.2.2
 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 8) PRODUCT APPROVAL FOR THE GLASS BLOCK REQUIRES
 SHUTTERS - PLEASE PROVIDE A COMPLETE MIAMI DADE OR
 FLORIDA STATE SHUTTER PRODUCT APPROVAL.
 9) THE CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE
 REVISE THE CODE USED FOR DESIGN TO SHOW THE CODE IN
 EFFECT (2020 FBC AND ASCE 7-16)
 10) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE
 FLAT/LOW SLOPE DECK ROOFING = PLEASE CIRCLE THE ROOFING
 SYSTEM TO BE USED IN THE PRODUCT APPROVAL - IF NEEDED
 PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL ATTACHMENT
 DETAILS FROM AN ARCHITECT OR ENGINEER FOR THE ROOF
 ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE
 - SEE NOTES ON THE PRODUCT APPROVAL.
 11) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - (JOB VALUE IS MATERIAL AND LABOR AS
 IF PRICED BY A CONTRACTOR) FBC 109.3 - ICC VALUATION
 TABLE = 127 SQ. FEET X 122 PER SQ. FOOT = 15,494.00 -
 PLEASE REVISE THE BUILDING PERMIT APPLICATION TO SHOW
 THE CORRECT JOB VALUE.
  
 DEFERRED = ROOFING SYSTEM PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-01 Cont ID  
Sent By equinone Date 2021-02-01 Time 11:24 Rev Time 0.00
Received By equinone Date 2021-02-01 Time 11:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-29 Cont ID  
Sent By rmcphers Date 2021-07-29 Time 09:33 Rev Time 0.00
Received By rmcphers Date 2021-07-19 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-09 Cont ID  
Sent By rmcphers Date 2021-07-09 Time 09:55 Rev Time 0.00
Received By rmcphers Date 2021-06-30 Time 17:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-22 Cont ID  
Sent By rmcphers Date 2021-06-22 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2021-06-08 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-27 Cont ID  
Sent By rmcphers Date 2021-04-27 Time 09:07 Rev Time 0.00
Received By rmcphers Date 2021-04-12 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-11 Cont ID  
Sent By rmcphers Date 2021-02-11 Time 10:14 Rev Time 0.00
Received By rmcphers Date 2021-01-19 Time 11:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-08-09 Cont ID  
Sent By lmarchan Date 2021-08-09 Time 09:08 Rev Time 0.00
Received By lmarchan Date 2021-08-02 Time 07:40 Sent To  
Notes
2021-08-09 09:08:57RECEIPT MU-2021-38426 - $0.00 NO FEES DUE
2021-08-02 07:40:198/02/21 EMAILED IMPACT FOR REVIEW AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-07-09 Cont ID  
Sent By rmcphers Date 2021-07-09 Time 09:28 Rev Time 0.00
Received By rmcphers Date 2021-07-09 Time 09:28 Sent To  
Notes
2021-07-09 09:29:36PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-27 Cont ID  
Sent By medwards Date 2021-01-27 Time 08:06 Rev Time 0.00
Received By medwards Date 2021-01-27 Time 07:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-01-22 Cont ID  
Sent By lcrespo Date 2021-01-22 Time 05:09 Rev Time 0.00
Received By lcrespo Date 2021-01-22 Time 05:36 Sent To  
Notes
2021-01-22 05:10:2101/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2021-07-09 Cont ID  
Sent By rmcphers Date 2021-07-09 Time 09:55 Rev Time 0.00
Received By rmcphers Date 2021-07-09 Time 09:55 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2021-06-22 Cont ID  
Sent By rmcphers Date 2021-06-22 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2021-06-22 Time 15:32 Sent To  
Notes
2021-06-22 15:32:37SEE BUILDING PLAN REVIEW
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-04-27 Cont ID  
Sent By rmcphers Date 2021-04-27 Time 09:06 Rev Time 0.00
Received By rmcphers Date 2021-04-27 Time 09:06 Sent To  
Notes
2021-04-27 09:07:45SEE BUILDING PLAN REVIEW
 A BUILDING PERMIT APPLICATION IS REQUIRED (MARKED
 ROOF).

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-02-11 Cont ID  
Sent By rmcphers Date 2021-02-11 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2021-02-11 Time 10:13 Sent To  
Notes
2021-02-11 10:14:44SEE BUILDING PLAN REVIEW
 A BUILDING PERMIT APPLICATION IS REQUIRED (MARKED
 ROOF).

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-07-29 Cont ID  
Sent By rmcphers Date 2021-07-29 Time 09:33 Rev Time 0.00
Received By rmcphers Date 2021-07-29 Time 09:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-07-09 Cont ID  
Sent By rmcphers Date 2021-07-09 Time 09:30 Rev Time 0.00
Received By rmcphers Date 2021-07-09 Time 09:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-09 Cont ID  
Sent By equinone Date 2021-06-09 Time 08:57 Rev Time 0.00
Received By equinone Date 2021-06-09 Time 08:57 Sent To  
Notes
2021-06-09 08:58:01PAPER DRAWING SUBMITTED WITH ORIGINAL SEAL AND
 SIGNATURE. ROUTED TO STORAGE. EQ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 16:58 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 16:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-19 Cont ID  
Sent By medwards Date 2021-01-19 Time 14:12 Rev Time 0.00
Received By medwards Date 2021-01-19 Time 14:07 Sent To  
Notes
2021-01-19 14:14:46ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE. ME

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-21 Cont ID  
Sent By awooten Date 2021-01-21 Time   Rev Time  
Received By awooten Date 2021-01-21 Time   Sent To  
Notes
***NONE***