| 2021-02-11 09:58:40 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) DRAWING S-2 THE EXTERIOR WALL DETAILS SHOWN APPEARS |
| | TO BE AN INTERIOR WALL - PLEASE REVISE SHOWING THE |
| | EXTERIOR WALL FRAMING AND CLADDING DETAILS. |
| | 2) PLEASE SHOW THE EXTERIOR WALL STRAPPING - BOTTOM |
| | WALL PLATE TO WALL STUD - TOP WALL PLATE TO BEAM. FBC |
| | R301.2.1 WIND DESIGN CRITERIA. A CONTINUOUS LOAD PATH |
| | SHALL BE PROVIDED TO TRANSMIT THE APPLICABLE UPLIFT |
| | FORCES FROM THE ROOF ASSEMBLY TO THE FOUNDATION. |
| | 3) PLEASE SHOW THE ROOF SHEATHING DETAILS TYPE AND |
| | FASTENING FBC R803.2.3.1SHEATHING FASTENINGS. |
| | WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO |
| | ROOF FRAMING IN ACCORDANCE WITH TABLE R803.2.3.1. WHERE |
| | THE SHEATHING THICKNESS IS 15/32 INCHES AND LESS, |
| | SHEATHING SHALL BE FASTENED WITH ASTM F1667 RSRS-01 |
| | (23/8" ? 0.113") NAILS. WHERE THE SHEATHING THICKNESS |
| | IS GREATER THAN 15/32 INCHES, SHEATHING SHALL BE |
| | FASTENED WITH ASTM F1667 RSRS-03 (21/2" ? 0.131") NAILS |
| | OR ASTM F1667 RSRS-04 (3" ? 0.120") NAILS. RSRS-01, |
| | RSRS-03 AND RSRS-04 ARE RING SHANK NAILS MEETING THE |
| | SPECIFICATIONS IN ASTM F1667. |
| | 4) PLEASE SHOW THE SOFFIT VENT - FBC R806.1VENTILATION |
| | REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL |
| | HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM |
| | AND 1/4 INCH (6.4 MM) MAXIMUM. |
| | FBC R806.3 VENT AND INSULATION CLEARANCE. |
| | WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING, |
| | BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW |
| | OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE |
| | PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING |
| | AND AT THE LOCATION OF THE VENT. |
| | 5) PLEASE SHOW THE EXTERIOR WALL, FLOOR AND CEILING |
| | INSULATION TYPE AND "R" VALUE TO COMPLY WITH FBC ENERGY |
| | CONSERVATION R401 |
| | 6) PLEASE SHOW WHAT THE ROOF SLOPE IS. |
| | 7) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF |
| | THE EXISTING OR ADDED SMOKE DETECTORS PER FBC R314.2.2 |
| | ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | 8) PRODUCT APPROVAL FOR THE GLASS BLOCK REQUIRES |
| | SHUTTERS - PLEASE PROVIDE A COMPLETE MIAMI DADE OR |
| | FLORIDA STATE SHUTTER PRODUCT APPROVAL. |
| | 9) THE CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE |
| | REVISE THE CODE USED FOR DESIGN TO SHOW THE CODE IN |
| | EFFECT (2020 FBC AND ASCE 7-16) |
| | 10) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL FOR THE |
| | FLAT/LOW SLOPE DECK ROOFING = PLEASE CIRCLE THE ROOFING |
| | SYSTEM TO BE USED IN THE PRODUCT APPROVAL - IF NEEDED |
| | PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL ATTACHMENT |
| | DETAILS FROM AN ARCHITECT OR ENGINEER FOR THE ROOF |
| | ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND PRESSURE |
| | - SEE NOTES ON THE PRODUCT APPROVAL. |
| | 11) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION |
| | APPEARS TO BE LOW - (JOB VALUE IS MATERIAL AND LABOR AS |
| | IF PRICED BY A CONTRACTOR) FBC 109.3 - ICC VALUATION |
| | TABLE = 127 SQ. FEET X 122 PER SQ. FOOT = 15,494.00 - |
| | PLEASE REVISE THE BUILDING PERMIT APPLICATION TO SHOW |
| | THE CORRECT JOB VALUE. |
| | |
| | DEFERRED = ROOFING SYSTEM PRODUCT APPROVALS MAY BE |
| | DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON |
| | THE CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |