Plan Review Details - Permit 21010583
Plan Review Stops For Permit 21010583
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-10-14 Cont ID  
Sent By jleahy Date 2021-10-14 Time 07:29 Rev Time 0.00
Received By jleahy Date 2021-10-14 Time 07:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2021-08-27 Cont ID  
Sent By jleahy Date 2021-08-27 Time 15:14 Rev Time 0.00
Received By jleahy Date 2021-08-27 Time 15:14 Sent To  
Notes
2021-08-27 15:15:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 WITH THE PANEL BEING IN THE POLE HOW DOES IT COMPLY
 WITH 110.26 FOR WORKING CLEARANCES?

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-05-24 Cont ID  
Sent By equinone Date 2021-05-24 Time 12:55 Rev Time 0.00
Received By equinone Date 2021-05-24 Time 12:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By equinone Date 2021-03-23 Time 15:13 Rev Time 0.00
Received By equinone Date 2021-03-23 Time 11:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-16 Cont ID  
Sent By equinone Date 2021-02-16 Time 17:10 Rev Time 0.00
Received By equinone Date 2021-02-16 Time 17:10 Sent To  
Notes
2021-02-16 17:10:49CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEET PAGE 03- CIRCUIT DETAIL: IT SEEMS THERE ARE
 SOME INCONSISTENCIES BETWEEN RISER DIAGRAM AND PANEL
 SCHEDULES THAT NEED CLARIFICATION OR CORRECTIONS
  
 ? RISER DIAGRAM SHOWS ONE RAYCAP PANEL, BUT POWER PANEL
 BREAKER SCHEDULE SHOWS TWO 30 AMPS RAYCAP FEEDERS.
 PLEASE CLARIFY AND CORRECT IF NEEDED.
 ? RAYCAP BREAKER PANEL SCHEDULE SHOWS ONE 60 AMPS MAIN
 BREAKER BUT POWER PANEL BREAKER SCHEDULE SHOWS 30 AMPS
 BREAKERS FOR RAYCAP FEEDERS. PLEASE CLARIFY AND CORRECT
 IF NEEDED.
 ? RISER DIAGRAM, NOTE 2, SHOWS 1#3-10 SEOW CONDUCTOR
 FOR RAYCAP PANEL. DOES THIS MEAN 2#3 + 1#10 G OR DOES
 IT MEAN 2#10 + 1#10 G CONDUCTORS? PLEASE CLARIFY AND
 CORRECT IF NEEDED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-09-17 Cont ID  
Sent By gpatrie Date 2021-09-17 Time 09:57 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-09-17 09:57:08LAT/LONG ADJUSTED.
 THIS LOCATION IS NOT IN THE CITY RIGHT-OF-WAY, PALM
 BEACH COUNY PERMIT REQUIRED.
  
 CONTACT: [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-06-17 Cont ID  
Sent By gpatrie Date 2021-06-17 Time 10:10 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-06-17 10:10:521. THE LAT / LONG PROVIDED ON SH 1 PLACES THE POLE ON
 PRIVATE PROPERTY.
  
 CONTACT: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-10-14 Cont ID  
Sent By jleahy Date 2021-10-14 Time 07:29 Rev Time 0.00
Received By jleahy Date 2021-09-28 Time 12:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-09-20 Time   Rev Time 0.00
Received By aoliver Date 2021-08-12 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-14 Cont ID  
Sent By medwards Date 2021-07-14 Time 07:43 Rev Time 0.00
Received By medwards Date 2021-05-19 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-13 Cont ID  
Sent By lmarchan Date 2021-04-13 Time 08:24 Rev Time 0.00
Received By lmarchan Date 2021-03-17 Time 12:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-03 Cont ID  
Sent By lmarchan Date 2021-03-03 Time 17:10 Rev Time 0.00
Received By lmarchan Date 2021-01-29 Time 16:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-09-20 Cont ID  
Sent By ccole Date 2021-09-20 Time 11:40 Rev Time 0.00
Received By ccole Date 2021-09-20 Time 11:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-24 Cont ID  
Sent By equinone Date 2021-05-24 Time 12:59 Rev Time 0.00
Received By equinone Date 2021-05-24 Time 12:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By equinone Date 2021-03-23 Time 15:14 Rev Time 0.00
Received By equinone Date 2021-03-23 Time 15:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-16 Cont ID  
Sent By equinone Date 2021-02-16 Time 17:12 Rev Time 0.00
Received By equinone Date 2021-02-16 Time 17:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2021-08-16 Cont ID  
Sent By eschneid Date 2021-08-16 Time 09:06 Rev Time 0.25
Received By eschneid Date 2021-08-16 Time 08:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2021-07-13 Cont ID  
Sent By eschneid Date 2021-07-13 Time 13:26 Rev Time 0.25
Received By eschneid Date 2021-07-13 Time 13:23 Sent To  
Notes
2021-07-13 13:26:47FAILED
  
 1) THE REVISED STRUCTURAL ANALYSIS PLAN SHOWS A
 PROPOSED WIRELESS FACILITY (POLE) THAT STILL DOES NOT
 MEET THE CITY OF WEST PALM BEACH CONCEALMENT (STEALTH)
 STYLE REQUIREMENT LISTED IN SECTIONS 78-411(E),
 78-411(F) AND 78-411(G) OF THE CITY CODE. PROVIDE A
 POLE THAT MEETS THE CITY CODE REQUIREMENTS. NOTE: AT&T
 HAS SHOWN POLES ON OTHER APPLICATIONS THAT MEET THE
 CITY CODE REQUIREMENTS, SUCH AS THE ONE ON APPROVED FOR
 PALM BEACH LAKES AS CRAN_RTFL_PBC223_592.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-04-12 Cont ID  
Sent By eschneid Date 2021-04-12 Time 13:50 Rev Time 0.25
Received By eschneid Date 2021-04-12 Time 13:50 Sent To  
Notes
2021-04-12 13:50:48FAILED
  
 1) THE PROPOSED WIRELESS COMMUNICATION FACILITY POLE
 LOCATION HAS CHANGED FROM THE ORIGINAL SUBMITTAL ON
 JANUARY 19, 2021, WITH THE POLE NOW LOCATED WITHIN PALM
 BEACH COUNTY RIGHT-OF-WAY.
 PROVIDE A COPY OF THE PALM BEACH COUNTY APPROVAL FOR
 THE WORK WITHIN THEIR RIGHT-OF-WAY.
  
 2) PROVIDE AN UPDATED SURVEY SHOWING THE NEW LOCATION
 OF THE POLE, WITH THE RIGHT-OF-WAY, SIDEWALK AND
 PROPERTY LINE SHOWN, SO THAT STAFF CAN VERIFY THAT IT
 IS WITHIN THE RIGHT-OF-WAY.
  
 3) PROVIDE AN UPDATED SITE PLAN BASED ON THE NEW POLE
 LOCATION.
  
 4) THE REVISED STRUCTURAL ANALYSIS PLAN SHOWS A
 PROPOSED WIRELESS FACILITY (POLE) THAT STILL DOES NOT
 MEET THE CITY OF WEST PALM BEACH CONCEALMENT (STEALTH)
 STYLE REQUIREMENT LISTED IN SECTIONS 78-411(E),
 78-411(F) AND 78-411(G) OF THE CITY CODE. PROVIDE A
 POLE THAT MEETS THE CITY CODE REQUIREMENTS. NOTE: AT&T
 HAS SHOWN POLES ON OTHER APPLICATIONS THAT MEET THE
 CITY CODE REQUIREMENTS, SUCH AS THE ONE ON APPROVED FOR
 PALM BEACH LAKES AS CRAN_RTFL_PBC223_592.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-03 Cont ID  
Sent By eschneid Date 2021-03-03 Time 13:15 Rev Time 0.25
Received By eschneid Date 2021-03-03 Time 13:15 Sent To  
Notes
2021-03-03 13:15:35FAILED
  
 1) PROVIDE A COPY OF THE FDOT APPROVAL FOR THE WORK
 WITHIN THEIR RIGHT-OF-WAY.
  
 2) THE STRUCTURAL ANALYSIS PLAN SHOWS A PROPOSED
 WIRELESS FACILITY (POLE) THAT DOES NOT MEET THE CITY OF
 WEST PALM BEACH CONCEALMENT (STEALTH) STYLE REQUIREMENT
 LISTED IN SECTIONS 78-411(E), 78-411(F) AND 78-411(G)
 OF THE CITY CODE. PROVIDE A POLE THAT MEETS THE CITY
 CODE REQUIREMENTS. NOTE: AT&T HAS SHOWN POLES ON OTHER
 APPLICATIONS THAT MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  