Plan Review Details - Permit 21010451
Plan Review Stops For Permit 21010451
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-19 Cont ID  
Sent By rmcdouga Date 2021-03-19 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2021-03-19 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By rmcdouga Date 2021-02-18 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2021-02-18 Time 09:35 Sent To  
Notes
2021-02-18 09:44:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWING REFERENCES THE FBC SIXTH
 EDITION (2017). THE FBC SEVENTH EDITION (2020) WENT
 INTO EFFECT ON DECEMBER 31, 2020. ALL NEW PERMITS
 APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED TO
 COMPLY WITH AND REFERENCE THE 2020 FBC SEVENTH EDITION.
 FS CHAPTER 553
  
 2) FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
 SPECIFY THIS ON THE SURVEY THAT SHOWS THE GENERATOR
 LOCATION.
  
 3) SEE SIGNATURE REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-06-16 Cont ID  
Sent By jleahy Date 2021-06-16 Time 18:59 Rev Time 0.00
Received By jleahy Date 2021-06-16 Time 18:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-05-24 Cont ID  
Sent By jleahy Date 2021-05-24 Time 16:38 Rev Time 0.00
Received By jleahy Date 2021-05-24 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-03-26 Cont ID  
Sent By jleahy Date 2021-03-26 Time 16:35 Rev Time 0.00
Received By jleahy Date 2021-03-26 Time 16:35 Sent To  
Notes
2021-03-26 16:45:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER SHOWS A 150A TRANSFER SWITCH WITH A 200A
 BREAKER????
  
 2) 200A SERVICE REQUIRES 3/0 CU OR EQUIVALENT AL ENTIRE
 LOAD NOT BEING FED BY ONE MAIN. 310.15(B)(7)(1)
  
 FOR A SERVICE RATED 100 THROUGH 400 AMPERES, THE
 SERVICE CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED
 WITH A ONE-FAMILY DWELLING, OR THE SERVICE CONDUCTORS
 SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH AN INDIVIDUAL
 DWELLING UNIT IN A TWO-FAMILY OR MULTIFAMILY DWELLING,
 SHALL BE PERMITTED TO HAVE AN AMPACITY NOT LESS THAN 83
 PERCENT OF THE SERVICE RATING. THIS DOES NOT APPLY TO
 YOUR INSTALLATION
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By jleahy Date 2021-02-10 Time 15:17 Rev Time 0.00
Received By jleahy Date 2021-02-10 Time 15:08 Sent To  
Notes
2021-02-10 15:21:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL PLAN HAS TWO DIFFERENT SIZES FOR THE
 GENERATOR 16KW AND 22KW? WHICH ONE.
  
 TRANSFER SWITCH SPECS WHICH ONE? PLEASE HIGHLIGHT WHICH
 ONE BEING USED.
  
 GENERATOR SPECS WHICH ONE? PLEASE HIGHLIGHT WHICH ONE
 IS BEING USED.
  
 VALUE OF JOB (5200) TO LOW FOR EVEN A 16KW GENERATOR.
 SUBMIT A SIGNED CONTRACT WITH THE OWNER FOR THE JOB.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-16 Cont ID  
Sent By jleahy Date 2021-06-16 Time 19:00 Rev Time 0.00
Received By jleahy Date 2021-06-09 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-24 Cont ID  
Sent By jleahy Date 2021-05-24 Time 16:45 Rev Time 0.00
Received By jleahy Date 2021-05-14 Time 14:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-15 Cont ID  
Sent By lmarchan Date 2021-04-15 Time 08:46 Rev Time 0.00
Received By lmarchan Date 2021-03-18 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-18 Cont ID  
Sent By rmcdouga Date 2021-02-18 Time 09:49 Rev Time 0.00
Received By rmcdouga Date 2021-01-27 Time 10:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-06-16 Cont ID  
Sent By jleahy Date 2021-06-16 Time 19:00 Rev Time 0.00
Received By jleahy Date 2021-06-16 Time 18:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-24 Cont ID  
Sent By jleahy Date 2021-05-24 Time 16:38 Rev Time 0.00
Received By jleahy Date 2021-05-24 Time 16:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-19 Cont ID  
Sent By rmcdouga Date 2021-03-19 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2021-03-19 Time 10:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-18 Cont ID  
Sent By rmcdouga Date 2021-02-18 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2021-02-18 Time 09:44 Sent To  
Notes
2021-02-18 09:47:57THE GENERATOR PAD DRAWINGS FOR THE 2020 FBC WILL BE
 RQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE ON
 THEM. COPIES OF DIGITALLY SIGNED DOCUMENTS ARE NOT
 ACCEPTABLE. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE ON
 THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS.
 NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 471 & 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-14 Cont ID  
Sent By kalexand Date 2021-04-14 Time 08:38 Rev Time 0.00
Received By kalexand Date 2021-04-14 Time 08:38 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-02-17 Cont ID  
Sent By kalexand Date 2021-02-17 Time 09:01 Rev Time 0.00
Received By kalexand Date 2021-02-17 Time 09:00 Sent To  
Notes
***NONE***