Plan Review Details - Permit 21010426
Plan Review Stops For Permit 21010426
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-04 Cont ID  
Sent By rmcphers Date 2021-05-04 Time 15:38 Rev Time 0.00
Received By rmcphers Date 2021-05-04 Time 15:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By rmcphers Date 2021-03-09 Time 15:07 Rev Time 0.00
Received By rmcphers Date 2021-03-09 Time 15:07 Sent To  
Notes
2021-03-09 15:08:52GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CORRECT THE SURVEY INDICATING A 5 FT. CLEARANCE FOR
 THE GENERATOR EXHAUST TO OPENINGS IN THE HOUSE. A
 MINIMUM 10 FT. CLEARANCE IS REQUIRED- SECTION R303.5.1
 FBC RES.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-29 Cont ID  
Sent By rmcphers Date 2021-01-29 Time 15:36 Rev Time 0.00
Received By rmcphers Date 2021-01-29 Time 15:33 Sent To  
Notes
2021-01-29 15:36:54GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CORRECT THE SURVEY INDICATING A 5 FT. CLEARANCE FOR
 THE GENERATOR EXHAUST TO OPENINGS IN THE HOUSE. A
 MINIMUM 10 FT. CLEARANCE IS REQUIRED- SECTION R303.5.1
 FBC RES.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-15 Cont ID  
Sent By cthroop Date 2021-01-15 Time 16:43 Rev Time 0.00
Received By cthroop Date 2021-01-15 Time 13:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-05-07 Cont ID  
Sent By ccole Date 2021-05-07 Time 16:52 Rev Time 0.00
Received By ccole Date 2021-05-07 Time 16:52 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-04-29 Cont ID  
Sent By ccole Date 2021-04-29 Time 17:38 Rev Time 0.00
Received By ccole Date 2021-04-27 Time 17:35 Sent To  
Notes
2021-04-29 17:41:533RD REVIEW FBC-2020 RES.
 PERMIT- 21010426
 4/29/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #5 LISTED BELOW
 FROM THE 1ST AND 2ND REVIEW STILL EXISTS. PENDING REPLY
 TO EMAIL TO CONTRACTOR ON 4/29/21 THE COMMENT WILL
 STAND.
  
  
 5) FAILED. I WAS UNABLE TO FIND A PERMIT OR GAS PLANS
 FOR THE INSTALLATION OF THE BBQ. PLEASE NOTE THAT ANY
 GAS PIPING OR GAS-FIRED APPLIANCES PREVIOUSLY
 UNPERMITTED OR NOT INSPECTED MUST BE REVIEWED AND
 APPROVED AS NEW INSTALLATIONS- SECTION 107.2.1 WPB. THE
 BBQ GRILL AND GAS PIPING SUPPLYING THE GRILL APPEAR TO
 HAVE BEEN INSTALLED WITHOUT A PERMIT. BECAUSE YOU ARE
 MODIFYING THE SYSTEM, IT IS REQUIRED THAT THE ENTIRE
 SYSTEM BE EVALUATED FOR COMPLIANCE.
  
 REFER TO SECTION G2412.4 (401.4) ADDITIONAL APPLIANCES.
 WHERE AN ADDITIONAL APPLIANCE IS TO BE SERVED, THE
 EXISTING PIPING SHALL BE CHECKED TO DETERMINE IF IT HAS
 ADEQUATE CAPACITY FOR ALL APPLIANCES SERVED. IF
 INADEQUATE, THE EXISTING SYSTEM SHALL BE ENLARGED AS
 REQUIRED OR SEPARATE PIPING OF ADEQUATE CAPACITY SHALL
 BE PROVIDED.
  
 THE BBQ GRILLS AND PIPING CANNOT BE LABELED AS EXISTING
 AND MUST BE REVIEWED AND INSPECTED AS NEW
 INSTALLATIONS. PLEASE SHOW THE LOCATION OF THE GRILL ON
 THE SURVEY DRAWING AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS OR PROVIDE LISTING AND LABEL
 INFORMATION. PLEASE NOTE THAT THE GRILL SHALL BE
 INSTALLED IN ACCORDANCE WITH MAN. SPECS. AND HAVE
 LOCATION LIMITATIONS- CLEARANCES TO COMBUSTIBLE,
 ENCLOSED SPACES, AND OVERHEAD ROOF CONSTRUCTION-
 SECTIONS G2408.1 & G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINE
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 13:48 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 12:19 Sent To  
Notes
2021-02-24 13:48:242ND REVIEW FBC-2020 RES.
 PERMIT- 21010426
 2/24/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS LISTED BELOW FROM
 THE 1ST REVIEW STILL EXIST. NOTES HAVE BEEN TO THE
 FAILED COMMENTS.
  
 1) FAILED. PLEASE UPDATE THE CODE REFERENCES AND PIPE
 SIZING TABLES TO THE FBC 7TH EDITION 2020 RESIDENTIAL
 AND FBC- 7TH EDITION 2020 FUEL GAS. THE RISER DRAWING
 IS INDICATING THE 2029 CODE- PLEASE CORRECT TO INDICATE
 2020.
  
 3) FAILED. CORRECT THE SURVEY INDICATING A 5 FT.
 CLEARANCE FOR THE GENERATOR EXHAUST TO OPENINGS IN THE
 HOUSE. A MINIMUM 10 FT. CLEARANCE IS REQUIRED- SECTION
 R303.5.1 FBC RES. MINIMUM 10 FT. CLEARANCE IS REQUIRED-
 SECTION R303.5.1 FBC RES.
  
 5) FAILED. I WAS UNABLE TO FIND A PERMIT OR GAS PLANS
 FOR THE INSTALLATION OF THE BBQ. PLEASE NOTE THAT ANY
 GAS PIPING OR GAS-FIRED APPLIANCES PREVIOUSLY
 UNPERMITTED OR NOT INSPECTED MUST BE REVIEWED AND
 APPROVED AS NEW INSTALLATIONS- SECTION 107.2.1 WPB. THE
 BBQ GRILLS AND GAS PIPING SUPPLYING THEM APPEAR TO HAVE
 BEEN INSTALLED WITHOUT A PERMIT. BECAUSE YOU ARE
 MODIFYING THE SYSTEM, IT IS REQUIRED THAT THE ENTIRE
 SYSTEM BE EVALUATED FOR COMPLIANCE.
  
 REFER TO SECTION G2412.4 (401.4) ADDITIONAL APPLIANCES.
 WHERE AN ADDITIONAL APPLIANCE IS TO BE SERVED, THE
 EXISTING PIPING SHALL BE CHECKED TO DETERMINE IF IT HAS
 ADEQUATE CAPACITY FOR ALL APPLIANCES SERVED. IF
 INADEQUATE, THE EXISTING SYSTEM SHALL BE ENLARGED AS
 REQUIRED OR SEPARATE PIPING OF ADEQUATE CAPACITY SHALL
 BE PROVIDED.
  
 THE BBQ GRILLS AND PIPING CANNOT BE LABELED AS EXISTING
 AND MUST BE REVIEWED AND INSPECTED AS NEW
 INSTALLATIONS. PLEASE SHOW THE LOCATIONS OF ALL 3 BBQ
 GRILLS ON THE SURVEY DRAWING AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS OR PROVIDE LISTING AND LABEL
 INFORMATION. PLEASE NOTE THAT THE GRILLS SHALL BE
 INSTALLED IN ACCORDANCE WITH MAN. SPECS. AND HAVE
 LOCATION LIMITATIONS- CLEARANCES TO COMBUSTIBLE,
 ENCLOSED SPACES, AND OVERHEAD ROOF CONSTRUCTION-
 SECTIONS G2408.1 & G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINE
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By ccole Date 2021-01-26 Time 10:40 Rev Time 0.00
Received By ccole Date 2021-01-26 Time 10:40 Sent To  
Notes
2021-01-26 10:40:171ST REVIEW FBC-2020 RES.
 PERMIT- 21010426
 1/26/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UPDATE THE CODE REFERENCES AND PIPE SIZING
 TABLES TO THE FBC 7TH EDITION 2020 RESIDENTIAL AND FBC-
 7TH EDITION 2020 FUEL GAS.
  
 2) GAS RISER: THE GENERATOR SPECS INDICATE A FULL LOAD
 OF 306,000 BTUH- PLEASE CORRECT.
  
 3) CORRECT THE SURVEY INDICATING A 5 FT. CLEARANCE FOR
 THE GENERATOR EXHAUST TO OPENINGS IN THE HOUSE. A
 MINIMUM 10 FT. CLEARANCE IS REQUIRED- SECTION R303.5.1
 FBC RES.
  
 4) SUBMIT MANUFACTURER'S SPECIFICTIONS FOR THE
 REGULATORS MARKED UP TO SHOW THE SELECTED MODEL, AND
 THE INPUT AND OUTPUT PRESSURES- SECTION G2421 FBC RES.
  
 5) I WAS UINABLE TO FIND A PERMIT OR GAS PLANS FOR THE
 INSTALLATION OF THE BBQ. PLEAASE NOTE THAT ANY GAS
 PIPING OR GAS-FIRED APPLIANCES PREVIOUSLY UNPERMITTED
 OR NOT INSPECTED MUST BE REVIWED AND APPROVED AS NEW
 INSTALLATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-24 Cont ID  
Sent By ccole Date 2021-05-24 Time 15:02 Rev Time 0.00
Received By ccole Date 2021-04-20 Time 16:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-09 Cont ID  
Sent By pvalenti Date 2021-04-09 Time 09:43 Rev Time 0.00
Received By pvalenti Date 2021-02-17 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-05 Cont ID  
Sent By cpuell Date 2021-02-05 Time 11:53 Rev Time 0.00
Received By cpuell Date 2021-01-14 Time 20:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-04-27 Cont ID  
Sent By ccole Date 2021-04-27 Time 17:35 Rev Time 0.00
Received By ccole Date 2021-04-27 Time 17:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 13:48 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-01-26 Cont ID  
Sent By ccole Date 2021-01-26 Time 10:41 Rev Time 0.00
Received By ccole Date 2021-01-26 Time 10:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-04 Cont ID  
Sent By rmcphers Date 2021-05-04 Time 15:40 Rev Time 0.00
Received By rmcphers Date 2021-05-04 Time 15:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By rmcphers Date 2021-03-09 Time 15:09 Rev Time 0.00
Received By rmcphers Date 2021-03-09 Time 15:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-29 Cont ID  
Sent By rmcphers Date 2021-01-29 Time 15:37 Rev Time 0.00
Received By rmcphers Date 2021-01-29 Time 15:37 Sent To  
Notes
2021-01-29 15:37:38SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 4 Status P Date 2021-06-14 Cont ID  
Sent By ajones Date 2021-06-14 Time 14:48 Rev Time 0.00
Received By ajones Date 2021-06-14 Time 14:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2021-05-21 Cont ID  
Sent By kalexand Date 2021-05-21 Time 11:17 Rev Time 0.00
Received By kalexand Date 2021-05-21 Time 11:16 Sent To I
Notes
2021-05-21 11:17:44FIRST SET OF ZONING COMMENTS HAVE NOT BEEN ADDRESSED.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-04-08 Cont ID  
Sent By kalexand Date 2021-04-08 Time 11:05 Rev Time 0.00
Received By kalexand Date 2021-04-08 Time 11:05 Sent To I
Notes
2021-04-08 11:06:02SEE PREVIOUS ZONING COMMENTS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-04 Cont ID  
Sent By kalexand Date 2021-02-04 Time 14:56 Rev Time 0.00
Received By kalexand Date 2021-02-04 Time 14:56 Sent To I
Notes
2021-02-04 19:01:38ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK. THE MINIMUM
 SETBACK REQUIRED FOR THIS LOT PER IBIS REGULATIONS IS
 8FT; THEREFORE THE MINIMUM GENERATOR SETBACK SHOULD BE
 4FT FROM THE PROPOERTY LINE.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved