| Plan Review Stops For Permit 21010413 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-04-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-04-15 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-04-15 |
Time |
10:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-02-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-02-24 |
Time |
17:36 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-02-24 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2021-02-24 17:38:05 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT#21010413 | | | | | | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE. | | | | | | | | | 1- SHEET C1: PLANS ARE DESIGNED BASED ON THE 2017 FBC. | | | AS OF DECEMBER 31 OF 2020, THE NEW CODE IN EFFECT IS | | | THE 2020 FBC, 7TH EDITION. UPDATE DESIGN AND CODE | | | INFORMATION AS REQUIRED. | | | CHAPTER 553 FLORIDA STATUTE. | | | | | | 2- REVISE WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON | | | SHEET A1.0 TO REFLECT THE DESIGN PRESSURES OF SEC. | | | R301.2.1 FBC-RESIDENTIAL, 7TH EDITION (2020). | | | | | | 3- SHEET A1.0: ENTRY DOOR SIZE (2'-8") DOESN'T COMPLY | | | WITH THE THE MIN 32" CLEAR OPENING AS REQUIRED BY SEC. | | | R311.2 FBC-RESIDENTIAL. REVISE AS REQUIRED. | | | SEC. 605 FBC-EXISTING BUILDING CODE. SEC. 1012.1.1 | | | FBC-EXISTING BUILDING CODE. | | | | | | 4- EAST ELEVATION SHOWN ON SHEET A2.0 DOESN'T MATCH | | | FLOOR PLAN SHOWN ON SHEET A1.0. REVISE AS REQUIRED TO | | | MATCH. SEE BATHROOM WINDOW. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | FRAMING OF WALL AT EXISTING BARN DOORS AND NEW WINDOWS | | | ABOVE AS SHOWN ON PLANS. SPECIFY ALL FRAMING MEMBERS | | | AND CONNECTORS. | | | SEC. 605 FBC-EXISTING BUILDING CODE. SEC. 1012.1.1 | | | FBC-EXISTING BUILDING CODE. SEC. R301.1 | | | FBC-RESIDENTIAL. | | | | | | 6- WINDOWS AND DOORS HEAD/JAMB AND SILL DETAILS SHOWN | | | ON SHEET A2.0 ARE FOR MASONRY CONSTRUCTION. THIS | | | STRUCTURE IS WOOD FRAMING. REVISE AS REQUIRED. | | | SEC. 107..1 CITY AMENDMENTS. | | | | | | 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A)ROOF CLAY TILE AS SPECIFIED ON PLANS. | | | NOTE: CLEARLY SPECIFY ROOF TILE FASTENING. IF | | | SPECIFYING ROOF TILE ADHESIVE, THEN PROVIDE PRODUCT | | | APPROVAL. IF SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE | | | AND NUMBER OF SCREWS. | | | | | | B)ROOF TILE ADHESIVE IF SPECIFIED. SEE ROOF TILE NOA | | | SUBMITTED FOR LISTED ADHESIVES. AND CLEARLY MARK PADDY | | | SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING | | | PERMITS. | | | | | | C)AWNING WINDOW NOA 20-0402.07 SUBMITTED. ONLY THE | | | COVER PAGE WAS SUBMITTED. NEED TO SUBMIT COMPLETE | | | REPORT INCLUDING THE INSTALLATION INSTRUCTIONS. | | | | | | D)EXTERIOR SWINGING DOORS FL20873-R4 AND FL15210-R6. | | | ONLY THE COVER PAGE WAS SUBMITTED. NEED TO SUBMIT | | | COMPLETE REPORT INCLUDING THE INSTALLATION | | | INSTRUCTIONS. | | | | | | E)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED: | | | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY | | | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. | | | | | | 8-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-05-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-03 |
Time |
05:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-05-03 |
Time |
05:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-02-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-02-19 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-02-19 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2021-02-19 13:55:44 | PLAN REVIEW / ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. R404.1LIGHTING EQUIPMENT (MANDATORY). | | | NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY | | | LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY | | | HIGH-EFFICACY LAMPS. | | | EXCEPTION: LOW-VOLTAGE LIGHTING. | | | A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1 | | | | | | 2. OUTLET WALL SPACING. PLAN SHOWS OUTLET WHERE THERE | | | IS NO WALL. CHECK SPACING OF WALL OUTLETS. | | | E3901.2.1 SPACING. | | | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT | | | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL | | | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE | | | OUTLET. [210.52(A)(1)] | | | | | | 3. PROVIDE OUTLETS AT FRONT AND REAR OF UNIT. | | | E3901.7 OUTDOOR OUTLETS. | | | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY | | | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 | | | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE | | | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH | | | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. | | | | | | 4. IDENTIFY LOCATION OF NEW PANEL A AT EXISTING 1-STORY | | | RESIDENCE.. | | | | | | 5. PROVIDE LOCATION OF EXISTING 100A DISCONENCT AT | | | PROPOSED CABANA. | | | FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | | MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31, | | | 225.32 | | | | | | 6. PROVIDE EQUIPMENT SERVICE OUTLET FOR CU-1 | | | E3901.12 HVAC OUTLET. | | | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED | | | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE | | | LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING | | | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE | | | LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) | | | OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION | | | EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED | | | TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING | | | MEANS. (210.63) | | | | | | 7. IDENTIFY LOCATION OF WATER HEATER AND DISCONNECT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 8. INCLUDE THE FOLLOWING STATEMENT ON ELECTRICAL PLAN. | | | AFCI OUTLETS | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC | | | 210.12; FBC RE E3902.16 | | | | | | 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 | | | | | | 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. . | | | NEC 406.12; FBC RE E4002.14 A NOTE ON PLAN WILL SUFFICE | | | | | | 11. SMOKE ALARMS | | | 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING. | | | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | 12. PROVIDE 2 SMALL APPLIANCE CIRCUTS. | | | E3901.3 SMALL APPLIANCE RECEPTACLES. | | | IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR | | | SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE | | | 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY | | | SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR | | | RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND | | | E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR | | | REFRIGERATION APPLIANCES. [210.52(B)(1)] | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
2 |
Status |
P |
Date |
2021-05-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-03 |
Time |
05:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-05-03 |
Time |
05:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2021-02-19 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-02-19 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-02-19 |
Time |
11:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-04-08 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2021-04-08 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2021-04-08 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2021-04-08 12:47:21 | PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | | CONDITION(S): | | | 1. ALL GLASS SHALL BE CLEAR OR CLEAR WITH LOW-E | | | COATING. A NON-STREET BATHROOM MAY HAVE OBSCURED | | | TEXTURED GLASS OR "RAINDROP" GLASS. | | | 2. ALL TILE SHALL HAVE AN EARTH TONE COLOR. | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2021-03-08 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2021-03-08 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2021-03-08 12:35:12 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | 1. REMOVE THE FRONT ENTRY ON THE FRONT ELEVATION OF THE | | | MAIN STRUCTURE. | | | 2. PROVIDE PRODUCT APPROVAL FOR THE TILE ROOF. | | | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | | 1. ALL GLASS SHALL BE CLEAR OR CLEAR WITH LOW-E | | | COATING. A NON-STREET BATHROOM MAY HAVE OBSCURED | | | TEXTURED GLASS OR "RAINDROP" GLASS. | | | 2. ALL TILE SHALL HAVE AN EARTH TONE COLOR. | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-20 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-14 |
Time |
12:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-05-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2021-05-07 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-05-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-03 |
Time |
05:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-04-05 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-03-08 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-03-08 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-01-20 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2021-02-24 17:42:46 | FEES PAID ON 01/20/21. JG. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2021-06-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-06-22 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-05-26 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2021-06-18 15:18:43 | RECEIPT MU-2021-26363 - $4304.62 - PAID | | 2021-05-26 13:32:21 | 5/26/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-03-08 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-03-08 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2021-03-08 14:05:06 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-20 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-20 |
Time |
08:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-11 |
Time |
06:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-11 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2021-05-11 06:41:37 | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST | | | ALSO BE DESIGNED BY AN ENGINEER OR THE MECHANICAL | | | CONTRACTOR WITH THE PERMIT TO INSTALL THE EQUIPMENT FOR | | | THIS PROJECT. FS 471.003 | | | | | | 2) SHEET M.1: PLEASE REMOVE ALL WORDING FROM THE | | | DIAGRAM FOR THE EXHAUST TERMINATION AS THIS DESIGN DOES | | | NOT MEET FBC RES 1502.3 (SCREENS AT THE TERMINATION) | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-04-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-08 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-08 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2021-04-08 13:50:26 | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND THE | | | MECHANICAL DESIGN MUST BE DESIGNED BY EITHER A LICENSED | | | ENGINEER IN FLORIDA OR THE MECHANICAL CONTRACTOR THAT | | | HAS A PERMIT TO INSTALL THIS PROJECT. SINCE THERE IS NO | | | MECHANICAL CONTRACTOR OR PERMIT PLEASE HAVE A FLORIDA | | | LICENSED ENGNEER TO PRESENT THE EQUIPMENT SIZING | | | CALCULATIONS AND THE MECHANICAL DRAWINGS. F.S. | | | 471.003(H) | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-02-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-19 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-19 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2021-02-19 14:51:37 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21010413 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC | | | 101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC R403.7 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2021-05-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-05-11 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-05-11 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2021-04-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-04-09 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-04-09 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2021-04-09 14:45:46 | 2ND REVIEW FBC-2020 RES. PLUMBING | | | PERMIT-21010413 | | | 4/9/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | COMMENTS FROM THE 1ST REVIEW LISTED BELOW WERE NOT | | | ADDRESSED. THE RESPONSE NARRATIVE INDICATES THE DETAILS | | | ARE ON SHEET S-4 HOWEVER THE SHEET WAS NOT UPLOADED. | | | | | | 3) S1.0: PROVIDE A WATER PLAN AND RISER DRAWING SHOWING | | | THE POINT OF CONNECTION TO THE CITY SERVICE- SECTIONS | | | 107.2.1 AND 107.3.5.3 FBC RES. PLEASE NOTE THAT A | | | BACKFLOW PREVENTER MAY BE REQUIRED AT THE SERVICE | | | ACCORDING TO CITY OF WEST PALM CROSS UTILITIES | | | DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM. | | | MULTI-FAMILY DWELLING, AND WATER USERS WILL BE REQUIRED | | | TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT | | | OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY REQUIRED | | | WILL BE DEPENDENT UPON THE DEGREE OF HAZARD POSED BY | | | THE WATER USER. FOR FURTHER INFORMATION CONTACT THE WPB | | | UTILITIES DEPT. AT 561-822-2210. | | | | | | 4) S1.0: SHOW THE SOURCE OF HOT WATER FOR THE PLUMBING | | | FIXTURES- SECTION P2801.1 FBC RES. CLARIFY IF A NEW | | | WATER HEATER WILL BE INSTALLED- SHOW THE LOCATION OF | | | THE UNIT, PROVIDE AN EQUIPMENT SCHEDULE, AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS- TABLE C404.2 FBC EC. | | | | | | 5) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 & | | | P2709.2 FBC RES. | | | | | | 6) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-02-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-02-22 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-02-22 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2021-02-22 11:09:03 | 1ST REVIEW FBC-2020 RES. | | | PERMIT-21010413 | | | 2/22/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET C1.0: PLEASE UPDATE THE CODE REFERENCES- THE | | | FBC- 2020 7TH EDITION CODES WENT INTO EFFECT ON | | | 12/31/20. | | | | | | 2) SHEET S1.0 SANITARY RISER: SHOW THE REQUIRED | | | CLEANOUT AT THE JUNCTION OF THE CABANA DRAIN AND SEWER- | | | SECTION P3005.2.3 FBC RES. | | | | | | 3) S1.0: PROVIDE A WATER PLAN AND RISER DRAWING SHOWING | | | THE POINT OF CONNECTION TO THE CITY SERVICE- SECTIONS | | | 107.2.1 AND 107.3.5.3 FBC RES. PLEASE NOTE THAT A | | | BACKFLOW PREVENTER MAY BE REQUIRED AT THE SERVICE | | | ACCORDING TO CITY OF WEST PALM CROSS UTILITIES | | | DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM. | | | MULTI-FAMILY DWELLING, AND WATER USERS WILL BE REQUIRED | | | TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT | | | OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY REQUIRED | | | WILL BE DEPENDENT UPON THE DEGREE OF HAZARD POSED BY | | | THE WATER USER. FOR FURTHER INFORMATION CONTACT THE WPB | | | UTILITIES DEPT. AT 561-822-2210. | | | | | | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR | | | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE | | | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB | | | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL | | | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT | | | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. | | | | | | 4) S1.0: SHOW THE SOURCE OF HOT WATER FOR THE PLUMBING | | | FIXTURES- SECTION P2801.1 FBC RES. CLARIFY IF A NEW | | | WATER HEATER WILL BE INSTALLED- SHOW THE LOCATION OF | | | THE UNIT, PROVIDE AN EQUIPMENT SCHEDULE, AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS- TABLE C404.2 FBC EC. | | | PLEASE NOTE THAT A SEPARATE PRIMARY OR SUB GAS PERMIT | | | WILL BE REQUIRED FOR GAS WATER HEATERS- SECTION 105.1 | | | WPB. AT THE PRESENT TIME NO GAS PLANS HAVE BEEN | | | SUBMITTED. | | | | | | 5) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 & | | | P2709.2 FBC RES. | | | | | | 6) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB. | | | | | | 7) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION | | | 105.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2021-04-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-04-15 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-04-15 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2021-04-15 15:01:00 | CONCRETE TILE NOA 19-1021.12 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-05-14 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-05-14 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-05-14 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2021-05-14 13:03:13 | PAPER MECHANICAL DRAWING M-1 SUBMITTED WITH ORIGINAL | | | SEAL AND SIGNATURE. ROUTED TO STORAGE. EQ |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-05-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-07 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-07 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2021-05-07 16:40:09 | THE DIGITALLY SIGNED DRAWINGS ARE A COPY OF THE DIGITAL | | | SIGNATURE. WE CANNOT ACCEPT A COPY OF A DIGITAL | | | SIGNATURE. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-04-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-04-08 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-04-08 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2021-04-08 13:53:00 | A LICENSED IN FLORIDA ENGINEER MUST SUBMIT THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS AND THE | | | MECHANICAL DRAWING. F.S. 471.003(H) | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-02-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-19 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-19 |
Time |
14:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-04-08 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2021-04-08 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2021-04-08 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2021-04-08 12:44:07 | PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | | CONDITION(S): | | | 1. ALL GLASS SHALL BE CLEAR OR CLEAR WITH LOW-E | | | COATING. A NON-STREET BATHROOM MAY HAVE OBSCURED | | | TEXTURED GLASS OR "RAINDROP" GLASS. | | | 2. ALL TILE SHALL HAVE AN EARTH TONE COLOR. | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2021-03-08 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2021-03-08 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2021-03-08 12:36:22 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | 1. REMOVE THE FRONT ENTRY ON THE FRONT ELEVATION OF THE | | | MAIN STRUCTURE. | | | 2. PROVIDE PRODUCT APPROVAL FOR THE TILE ROOF. | | | | | | PROPOSED CONDITIONS, SUBJECT TO CHANGE: | | | 1. ALL GLASS SHALL BE CLEAR OR CLEAR WITH LOW-E | | | COATING. A NON-STREET BATHROOM MAY HAVE OBSCURED | | | TEXTURED GLASS OR "RAINDROP" GLASS. | | | 2. ALL TILE SHALL HAVE AN EARTH TONE COLOR. | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|