Plan Review Details - Permit 21010413
Plan Review Stops For Permit 21010413
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-15 Cont ID  
Sent By jgomez Date 2021-04-15 Time 15:01 Rev Time 0.00
Received By jgomez Date 2021-04-15 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-24 Cont ID  
Sent By jgomez Date 2021-02-24 Time 17:36 Rev Time 0.00
Received By jgomez Date 2021-02-24 Time 12:59 Sent To  
Notes
2021-02-24 17:38:05RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT#21010413
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
  
 1- SHEET C1: PLANS ARE DESIGNED BASED ON THE 2017 FBC.
 AS OF DECEMBER 31 OF 2020, THE NEW CODE IN EFFECT IS
 THE 2020 FBC, 7TH EDITION. UPDATE DESIGN AND CODE
 INFORMATION AS REQUIRED.
 CHAPTER 553 FLORIDA STATUTE.
  
 2- REVISE WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON
 SHEET A1.0 TO REFLECT THE DESIGN PRESSURES OF SEC.
 R301.2.1 FBC-RESIDENTIAL, 7TH EDITION (2020).
  
 3- SHEET A1.0: ENTRY DOOR SIZE (2'-8") DOESN'T COMPLY
 WITH THE THE MIN 32" CLEAR OPENING AS REQUIRED BY SEC.
 R311.2 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 SEC. 605 FBC-EXISTING BUILDING CODE. SEC. 1012.1.1
 FBC-EXISTING BUILDING CODE.
  
 4- EAST ELEVATION SHOWN ON SHEET A2.0 DOESN'T MATCH
 FLOOR PLAN SHOWN ON SHEET A1.0. REVISE AS REQUIRED TO
 MATCH. SEE BATHROOM WINDOW. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FRAMING OF WALL AT EXISTING BARN DOORS AND NEW WINDOWS
 ABOVE AS SHOWN ON PLANS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS.
 SEC. 605 FBC-EXISTING BUILDING CODE. SEC. 1012.1.1
 FBC-EXISTING BUILDING CODE. SEC. R301.1
 FBC-RESIDENTIAL.
  
 6- WINDOWS AND DOORS HEAD/JAMB AND SILL DETAILS SHOWN
 ON SHEET A2.0 ARE FOR MASONRY CONSTRUCTION. THIS
 STRUCTURE IS WOOD FRAMING. REVISE AS REQUIRED.
 SEC. 107..1 CITY AMENDMENTS.
  
 7-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF CLAY TILE AS SPECIFIED ON PLANS.
 NOTE: CLEARLY SPECIFY ROOF TILE FASTENING. IF
 SPECIFYING ROOF TILE ADHESIVE, THEN PROVIDE PRODUCT
 APPROVAL. IF SPECIFYING SCREWS, THEN SPECIFY SCREW SIZE
 AND NUMBER OF SCREWS.
  
 B)ROOF TILE ADHESIVE IF SPECIFIED. SEE ROOF TILE NOA
 SUBMITTED FOR LISTED ADHESIVES. AND CLEARLY MARK PADDY
 SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING
 PERMITS.
  
 C)AWNING WINDOW NOA 20-0402.07 SUBMITTED. ONLY THE
 COVER PAGE WAS SUBMITTED. NEED TO SUBMIT COMPLETE
 REPORT INCLUDING THE INSTALLATION INSTRUCTIONS.
  
 D)EXTERIOR SWINGING DOORS FL20873-R4 AND FL15210-R6.
 ONLY THE COVER PAGE WAS SUBMITTED. NEED TO SUBMIT
 COMPLETE REPORT INCLUDING THE INSTALLATION
 INSTRUCTIONS.
  
 E)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 8-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-03 Cont ID  
Sent By jleahy Date 2021-05-03 Time 05:35 Rev Time 0.00
Received By jleahy Date 2021-05-03 Time 05:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-19 Cont ID  
Sent By cthroop Date 2021-02-19 Time 13:15 Rev Time 0.00
Received By cthroop Date 2021-02-19 Time 11:00 Sent To  
Notes
2021-02-19 13:55:44PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. R404.1LIGHTING EQUIPMENT (MANDATORY).
 NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY
 HIGH-EFFICACY LAMPS.
 EXCEPTION: LOW-VOLTAGE LIGHTING.
 A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1
  
 2. OUTLET WALL SPACING. PLAN SHOWS OUTLET WHERE THERE
 IS NO WALL. CHECK SPACING OF WALL OUTLETS.
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)]
  
 3. PROVIDE OUTLETS AT FRONT AND REAR OF UNIT.
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
  
 4. IDENTIFY LOCATION OF NEW PANEL A AT EXISTING 1-STORY
 RESIDENCE..
  
 5. PROVIDE LOCATION OF EXISTING 100A DISCONENCT AT
 PROPOSED CABANA.
 FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL A. NEC 225.31,
 225.32
  
 6. PROVIDE EQUIPMENT SERVICE OUTLET FOR CU-1
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 7. IDENTIFY LOCATION OF WATER HEATER AND DISCONNECT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 8. INCLUDE THE FOLLOWING STATEMENT ON ELECTRICAL PLAN.
 AFCI OUTLETS
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16
  
 9. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. .
 NEC 406.12; FBC RE E4002.14 A NOTE ON PLAN WILL SUFFICE
  
 11. SMOKE ALARMS
 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING.
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 12. PROVIDE 2 SMALL APPLIANCE CIRCUTS.
 E3901.3 SMALL APPLIANCE RECEPTACLES.
 IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR
 SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE
 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND
 E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR
 REFRIGERATION APPLIANCES. [210.52(B)(1)]
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2021-05-03 Cont ID  
Sent By jleahy Date 2021-05-03 Time 05:35 Rev Time 0.00
Received By jleahy Date 2021-05-03 Time 05:42 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-02-19 Cont ID  
Sent By cthroop Date 2021-02-19 Time 11:53 Rev Time 0.00
Received By cthroop Date 2021-02-19 Time 11:53 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-04-08 Cont ID  
Sent By aborngra Date 2021-04-08 Time 12:47 Rev Time 0.00
Received By aborngra Date 2021-04-08 Time 12:47 Sent To  
Notes
2021-04-08 12:47:21PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. ALL GLASS SHALL BE CLEAR OR CLEAR WITH LOW-E
 COATING. A NON-STREET BATHROOM MAY HAVE OBSCURED
 TEXTURED GLASS OR "RAINDROP" GLASS.
 2. ALL TILE SHALL HAVE AN EARTH TONE COLOR.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By aborngra Date 2021-03-08 Time 12:35 Rev Time 0.00
Received By aborngra Date 2021-03-08 Time 12:31 Sent To  
Notes
2021-03-08 12:35:12THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. REMOVE THE FRONT ENTRY ON THE FRONT ELEVATION OF THE
 MAIN STRUCTURE.
 2. PROVIDE PRODUCT APPROVAL FOR THE TILE ROOF.
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE:
 1. ALL GLASS SHALL BE CLEAR OR CLEAR WITH LOW-E
 COATING. A NON-STREET BATHROOM MAY HAVE OBSCURED
 TEXTURED GLASS OR "RAINDROP" GLASS.
 2. ALL TILE SHALL HAVE AN EARTH TONE COLOR.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-20 Cont ID  
Sent By medwards Date 2021-05-20 Time 08:31 Rev Time 0.00
Received By medwards Date 2021-05-14 Time 12:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-05-11 Time   Rev Time 0.00
Received By aoliver Date 2021-05-07 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-03 Cont ID  
Sent By jleahy Date 2021-05-03 Time 05:35 Rev Time 0.00
Received By jleahy Date 2021-04-05 Time 14:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-08 Cont ID  
Sent By lmarchan Date 2021-03-08 Time 14:03 Rev Time 0.00
Received By lmarchan Date 2021-01-20 Time 17:42 Sent To  
Notes
2021-02-24 17:42:46FEES PAID ON 01/20/21. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By lmarchan Date 2021-06-22 Time 11:09 Rev Time 0.00
Received By lmarchan Date 2021-05-26 Time 13:32 Sent To  
Notes
2021-06-18 15:18:43RECEIPT MU-2021-26363 - $4304.62 - PAID
2021-05-26 13:32:215/26/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By lmarchan Date 2021-03-08 Time 14:04 Rev Time 0.00
Received By lmarchan Date 2021-03-08 Time 14:04 Sent To  
Notes
2021-03-08 14:05:06PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-05-20 Cont ID  
Sent By medwards Date 2021-05-20 Time 08:31 Rev Time 0.00
Received By medwards Date 2021-05-20 Time 08:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-05-11 Cont ID  
Sent By medwards Date 2021-05-11 Time 06:36 Rev Time 0.00
Received By medwards Date 2021-05-11 Time 06:21 Sent To  
Notes
2021-05-11 06:41:371) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST
 ALSO BE DESIGNED BY AN ENGINEER OR THE MECHANICAL
 CONTRACTOR WITH THE PERMIT TO INSTALL THE EQUIPMENT FOR
 THIS PROJECT. FS 471.003
  
 2) SHEET M.1: PLEASE REMOVE ALL WORDING FROM THE
 DIAGRAM FOR THE EXHAUST TERMINATION AS THIS DESIGN DOES
 NOT MEET FBC RES 1502.3 (SCREENS AT THE TERMINATION)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 13:46 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 13:46 Sent To  
Notes
2021-04-08 13:50:26THE MECHANICAL EQUIPMENT SIZING CALCULATIONS AND THE
 MECHANICAL DESIGN MUST BE DESIGNED BY EITHER A LICENSED
 ENGINEER IN FLORIDA OR THE MECHANICAL CONTRACTOR THAT
 HAS A PERMIT TO INSTALL THIS PROJECT. SINCE THERE IS NO
 MECHANICAL CONTRACTOR OR PERMIT PLEASE HAVE A FLORIDA
 LICENSED ENGNEER TO PRESENT THE EQUIPMENT SIZING
 CALCULATIONS AND THE MECHANICAL DRAWINGS. F.S.
 471.003(H)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-19 Cont ID  
Sent By medwards Date 2021-02-19 Time 14:51 Rev Time 0.00
Received By medwards Date 2021-02-19 Time 14:51 Sent To  
Notes
2021-02-19 14:51:371ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21010413
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-05-11 Cont ID  
Sent By ccole Date 2021-05-11 Time 17:48 Rev Time 0.00
Received By ccole Date 2021-05-11 Time 13:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-04-09 Cont ID  
Sent By ccole Date 2021-04-09 Time 14:43 Rev Time 0.00
Received By ccole Date 2021-04-09 Time 10:38 Sent To  
Notes
2021-04-09 14:45:462ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT-21010413
 4/9/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW WERE NOT
 ADDRESSED. THE RESPONSE NARRATIVE INDICATES THE DETAILS
 ARE ON SHEET S-4 HOWEVER THE SHEET WAS NOT UPLOADED.
  
 3) S1.0: PROVIDE A WATER PLAN AND RISER DRAWING SHOWING
 THE POINT OF CONNECTION TO THE CITY SERVICE- SECTIONS
 107.2.1 AND 107.3.5.3 FBC RES. PLEASE NOTE THAT A
 BACKFLOW PREVENTER MAY BE REQUIRED AT THE SERVICE
 ACCORDING TO CITY OF WEST PALM CROSS UTILITIES
 DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM.
 MULTI-FAMILY DWELLING, AND WATER USERS WILL BE REQUIRED
 TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT
 OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY REQUIRED
 WILL BE DEPENDENT UPON THE DEGREE OF HAZARD POSED BY
 THE WATER USER. FOR FURTHER INFORMATION CONTACT THE WPB
 UTILITIES DEPT. AT 561-822-2210.
  
 4) S1.0: SHOW THE SOURCE OF HOT WATER FOR THE PLUMBING
 FIXTURES- SECTION P2801.1 FBC RES. CLARIFY IF A NEW
 WATER HEATER WILL BE INSTALLED- SHOW THE LOCATION OF
 THE UNIT, PROVIDE AN EQUIPMENT SCHEDULE, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- TABLE C404.2 FBC EC.
  
 5) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 &
 P2709.2 FBC RES.
  
 6) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 11:08 Rev Time 0.00
Received By ccole Date 2021-02-22 Time 09:56 Sent To  
Notes
2021-02-22 11:09:031ST REVIEW FBC-2020 RES.
 PERMIT-21010413
 2/22/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C1.0: PLEASE UPDATE THE CODE REFERENCES- THE
 FBC- 2020 7TH EDITION CODES WENT INTO EFFECT ON
 12/31/20.
  
 2) SHEET S1.0 SANITARY RISER: SHOW THE REQUIRED
 CLEANOUT AT THE JUNCTION OF THE CABANA DRAIN AND SEWER-
 SECTION P3005.2.3 FBC RES.
  
 3) S1.0: PROVIDE A WATER PLAN AND RISER DRAWING SHOWING
 THE POINT OF CONNECTION TO THE CITY SERVICE- SECTIONS
 107.2.1 AND 107.3.5.3 FBC RES. PLEASE NOTE THAT A
 BACKFLOW PREVENTER MAY BE REQUIRED AT THE SERVICE
 ACCORDING TO CITY OF WEST PALM CROSS UTILITIES
 DEPARTMENT AND THEIR CONNECTION CONTROL PROGRAM.
 MULTI-FAMILY DWELLING, AND WATER USERS WILL BE REQUIRED
 TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT THE POINT
 OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY REQUIRED
 WILL BE DEPENDENT UPON THE DEGREE OF HAZARD POSED BY
 THE WATER USER. FOR FURTHER INFORMATION CONTACT THE WPB
 UTILITIES DEPT. AT 561-822-2210.
  
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
  
 4) S1.0: SHOW THE SOURCE OF HOT WATER FOR THE PLUMBING
 FIXTURES- SECTION P2801.1 FBC RES. CLARIFY IF A NEW
 WATER HEATER WILL BE INSTALLED- SHOW THE LOCATION OF
 THE UNIT, PROVIDE AN EQUIPMENT SCHEDULE, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- TABLE C404.2 FBC EC.
 PLEASE NOTE THAT A SEPARATE PRIMARY OR SUB GAS PERMIT
 WILL BE REQUIRED FOR GAS WATER HEATERS- SECTION 105.1
 WPB. AT THE PRESENT TIME NO GAS PLANS HAVE BEEN
 SUBMITTED.
  
 5) PROVIDE A SHOWER PAN DETAIL- SECTION P2709.1 &
 P2709.2 FBC RES.
  
 6) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 7) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-04-15 Cont ID  
Sent By jgomez Date 2021-04-15 Time 15:00 Rev Time 0.00
Received By jgomez Date 2021-04-15 Time 14:56 Sent To  
Notes
2021-04-15 15:01:00CONCRETE TILE NOA 19-1021.12

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-05-14 Cont ID  
Sent By equinone Date 2021-05-14 Time 13:02 Rev Time 0.00
Received By equinone Date 2021-05-14 Time 13:02 Sent To  
Notes
2021-05-14 13:03:13PAPER MECHANICAL DRAWING M-1 SUBMITTED WITH ORIGINAL
 SEAL AND SIGNATURE. ROUTED TO STORAGE. EQ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-05-07 Cont ID  
Sent By medwards Date 2021-05-07 Time 16:35 Rev Time 0.00
Received By medwards Date 2021-05-07 Time 16:35 Sent To  
Notes
2021-05-07 16:40:09THE DIGITALLY SIGNED DRAWINGS ARE A COPY OF THE DIGITAL
 SIGNATURE. WE CANNOT ACCEPT A COPY OF A DIGITAL
 SIGNATURE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-08 Cont ID  
Sent By medwards Date 2021-04-08 Time 13:51 Rev Time 0.00
Received By medwards Date 2021-04-08 Time 13:51 Sent To  
Notes
2021-04-08 13:53:00A LICENSED IN FLORIDA ENGINEER MUST SUBMIT THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS AND THE
 MECHANICAL DRAWING. F.S. 471.003(H)
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-19 Cont ID  
Sent By medwards Date 2021-02-19 Time 14:53 Rev Time 0.00
Received By medwards Date 2021-02-19 Time 14:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-08 Cont ID  
Sent By aborngra Date 2021-04-08 Time 12:44 Rev Time 0.00
Received By aborngra Date 2021-04-08 Time 12:43 Sent To  
Notes
2021-04-08 12:44:07PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. ALL GLASS SHALL BE CLEAR OR CLEAR WITH LOW-E
 COATING. A NON-STREET BATHROOM MAY HAVE OBSCURED
 TEXTURED GLASS OR "RAINDROP" GLASS.
 2. ALL TILE SHALL HAVE AN EARTH TONE COLOR.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By aborngra Date 2021-03-08 Time 12:36 Rev Time 0.00
Received By aborngra Date 2021-03-08 Time 12:36 Sent To  
Notes
2021-03-08 12:36:22THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
 1. REMOVE THE FRONT ENTRY ON THE FRONT ELEVATION OF THE
 MAIN STRUCTURE.
 2. PROVIDE PRODUCT APPROVAL FOR THE TILE ROOF.
  
 PROPOSED CONDITIONS, SUBJECT TO CHANGE:
 1. ALL GLASS SHALL BE CLEAR OR CLEAR WITH LOW-E
 COATING. A NON-STREET BATHROOM MAY HAVE OBSCURED
 TEXTURED GLASS OR "RAINDROP" GLASS.
 2. ALL TILE SHALL HAVE AN EARTH TONE COLOR.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  