Plan Review Details - Permit 21010382
Plan Review Stops For Permit 21010382
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-02-10 Cont ID  
Sent By rmcdouga Date 2021-02-10 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2021-02-10 Time 08:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-20 Cont ID  
Sent By rmcdouga Date 2021-01-20 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2021-01-20 Time 08:52 Sent To  
Notes
2021-01-20 09:29:28PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SELECTED FASTENING OPTION #3 ON PAGE 51 OF NOA
 NO. 18-0919.12 HAS A MAXIMUM DESIGN PRESSURE OF -52.5
 PSF AND REQUIRES ENHANCED FASTENING TO MEET THE
 REQUIRED DESIGN PRESSURES FOR THE PROJECT ROOF. GENERAL
 LIMITATION #7 ALLOWS ENHANCED FASTENING CALCULATIONS IN
 ACCORDANCE WITH RAS 117. IT ALSO REQUIRES THE
 CALCULATIONS TO BE SIGNED BY AN ARCHITECT, ENGINEER OR
 REGISTERED ROOF CONSULTANT. SUBMIT SIGNED AND SEALED
 CALCULATION. FBC 107.2.1
  
 2) BECAUSE THE PERMIT FOR THIS PROJECT WAS APPLIED FOR
 AFTER DECEMBER 31, 2020, IT IS REQUIRED TO COMPLY WITH
 THE 2020 FBC AND ASCE 7-16. PLEASE MAKE SURE THAT THE
 RE-SUBMITTAL DOCUMENTS REFERENCE AND COMPLY WITH THE
 CURRENT CODE (2020 FBC). FBC 107.2.1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-24 Cont ID  
Sent By jleahy Date 2021-02-24 Time 07:50 Rev Time 0.00
Received By jleahy Date 2021-02-23 Time 05:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-10 Cont ID  
Sent By rmcdouga Date 2021-02-10 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2021-02-04 Time 17:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-20 Cont ID  
Sent By rmcdouga Date 2021-01-20 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2021-01-13 Time 12:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-24 Cont ID  
Sent By jleahy Date 2021-02-24 Time 07:49 Rev Time 0.00
Received By jleahy Date 2021-02-24 Time 07:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-10 Cont ID  
Sent By rmcdouga Date 2021-02-10 Time 08:32 Rev Time 0.00
Received By rmcdouga Date 2021-02-10 Time 08:05 Sent To  
Notes
2021-02-10 08:34:00ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-20 Cont ID  
Sent By rmcdouga Date 2021-01-20 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2021-01-20 Time 09:30 Sent To  
Notes
2021-01-20 09:31:29DESIGN PROFESSIONAL'S SIGNATURE WILL BE REQUIRED ON RAS
 117 CALCUATIONS.