Plan Review Details - Permit 21010356
Plan Review Stops For Permit 21010356
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-02-01 Cont ID  
Sent By rrossano Date 2021-02-01 Time   Rev Time 0.00
Received By rrossano Date 2021-02-01 Time 10:09 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-25 Cont ID  
Sent By bdolan Date 2021-01-25 Time 12:32 Rev Time 0.00
Received By bdolan Date 2021-01-22 Time 10:10 Sent To  
Notes
2021-01-25 12:32:05FIRE LINE LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA
 24 AND SHALL BE COORDINATED WITH THE OFFICE OF FIRE
 MARSHAL, THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE
 PLANNER, AND THE CITY'S PLANNING AND ZONING OFFICE.
  
 FIRE LINE (UNDERGROUND) MUST BE SUBMITTED UNDER A
 SEPERATE PERMIT PER NFPA 24
  
 FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED NOT MORE
 THAN 100 FT (30.5 M) FROM THE NEAREST FIRE HYDRANT
 CONNECTED TO AN APPROVED WATER SUPPLY
  
 FOR THE PROPOSED FIRE PUMP THE PRIMARY AND SECONDARY
 POWER SOURCES MUST BE SPECIFIED.
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 DURING ON SITE FIRE INSPECTIONS. FAILURE TO FOLLOW
 THESE PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-02 Cont ID  
Sent By lmarchan Date 2021-02-02 Time 09:30 Rev Time 0.00
Received By lmarchan Date 2021-01-14 Time 21:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-26 Cont ID  
Sent By medwards Date 2021-01-26 Time 10:29 Rev Time 0.00
Received By medwards Date 2021-01-26 Time 10:24 Sent To  
Notes
***NONE***