| 2021-02-08 09:02:06 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21010330 |
| | 2/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE NOTE THE FOLLOWING ITEMS ABOUT THE |
| | APPLICATION: |
| | |
| | A) THE APPLICATION HAS A CHECK MARK IN THE SUB-PERMIT |
| | BOX. THIS IS A PRIMARY GAS PERMIT AND NOT A SUB-PERMIT |
| | OF THE MASTER PERMIT- 20070012. |
| | |
| | B) A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR |
| | INSTALLATION OF THE NEW GENERATOR- SECTION 105.1 & |
| | 107.2.1 WPB. |
| | |
| | C) THE $500.00 VALUE ON THE APPLICATION DOES NOT APPEAR |
| | TO INCLUDE THE COSTS OF THE NEW APPLIANCES- RANGE, |
| | DRYER AND BBQ GRILL. PERMIT VALUE IS BASED ON THE COSTS |
| | ASSOCIATED WITH LABOR, MATERIALS, APPLIANCES, |
| | EQUIPMENT, FIXTURES, SITE WORK AND DESIGN FEES- SECTION |
| | 107.2.1 WPB. PLEASE PROVIDE A COPY OF THE SIGNED |
| | CONTRACT AND/OR COPIES OF ESTIMATES AND INVOICES. |
| | |
| | 2) FOR THE PURPOSE OF GAS PIPING REVIEW, PLEASE SUBMIT |
| | MANUFACTURER'S SPECIFICATION SHEETS FOR THE RANGE, |
| | DRYER, BBQ, AND THE GENERATOR THAT SPECIFICALLY SHOW |
| | THE BTUH LOADS AND INPUT PRESSURES. COMPLETE SPECS AND |
| | INSTALLATION MANUALS ARE REQUIRED TO BE ONSITE AT TIME |
| | OF INSPECTION- SECTION 107.2.1 WPB. |
| | |
| | 3) SHEET G-1: PLEASE UPDATE THE FBC- 2017 CODE |
| | REFERENCES. THE FBC- 2020 7TH EDITION CODES WENT INTO |
| | EFFECT 12/31/2020. |
| | |
| | 4) G-1: SHOW THE CLEARANCE DISTANCE FROM THE BBQ GRILL |
| | TO OPERABLE OPENINGS AND AIR INTAKES IN THE BUILDING- |
| | SECTIONS M1801.1, G2427.3.2, G2427.8 & G2447.1 FBC RES. |
| | |
| | 5) G-1 GAS RISER: SHOW REGULATORS AT THE GENERATOR, |
| | DRYER, AND RANGE WHICH WILL ALL BE OPERATING AT |
| | PRESSURES LOWER THAN 11 IN. WC.- SECTION 2421 FBC RES. |
| | SHOW A FLEX CONNECTOR AT THE GENERATOR AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS. |
| | |
| | 6) G-1: PLEASE NOTE THAT THE GENERATOR EXHAUST OUTLET |
| | SHALL BE LOCATED A MINIMUM OF 10 FT. FROM MECHANICAL |
| | AIR INTAKES AND OPERABLE OPENINGS IN THE BUILDING- |
| | SECTION R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |