| 2021-01-21 09:09:02 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE FRONT DOOR AND THE OVERHEAD |
| | GARAGE DOOR. |
| | 2) JOB VALUE ON THE BUILDING PERMIT APPLICATION APPEARS |
| | TO BE LOW FOR MATERIAL AND LABOR (NEW BEAM+FRONT |
| | DOOR+GARAGE DOOR+LABOR) - JOB VALUE NEEDS TO BE AS IF A |
| | CONTRACTOR PRICED IT. PLEASE REVISE THE BUILDING PERMIT |
| | APPLICATION SHOWING THE CORRECTED JOB VALUE. |
| | 3) PLEASE SHOW THE LOCATIONS OF THE REQUIRED SMOKE |
| | ALARMS THROUGHOUT THE EXISTING HOUSE (CAN BE A HAND |
| | DRAWN FLOOR PLAN) TO COMPLY WITH FBC R314.2.2 |
| | ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. R314.3 |
| | LOCATION.SMOKE ALARMS SHALL BE INSTALLED IN THE |
| | FOLLOWING LOCATIONS:1.IN EACH SLEEPING ROOM. 2.OUTSIDE |
| | EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY |
| | OF THE BEDROOMS. R314.6 POWER SOURCE.ONE-FAMILY AND |
| | TWO-FAMILY DWELLINGS AND TOWNHOMES UNDERGOING A REPAIR, |
| | OR A LEVEL 1 ALTERATION AS DEFINED IN THE FLORIDA |
| | BUILDING CODE, MAY USE SMOKE ALARMS POWERED BY 10-YEAR |
| | NONREMOVABLE, NONREPLACEABLE BATTERIES IN LIEU OF |
| | RETROFITTING SUCH DWELLING WITH SMOKE ALARMS POWERED BY |
| | THE DWELLING?S ELECTRICAL SYSTEM. A BATTERY-POWERED |
| | SMOKE ALARM THAT IS NEWLY INSTALLED OR REPLACES AN |
| | EXISTING BATTERY-POWERED SMOKE ALARM AS A RESULT OF A |
| | LEVEL 1 ALTERATION MUST BE POWERED BY A NONREMOVABLE, |
| | NONREPLACEABLE BATTERY THAT POWERS THE ALARM FOR AT |
| | LEAST 10 YEARS. |