Plan Review Details - Permit 21010205
Plan Review Stops For Permit 21010205
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-02-08 Cont ID  
Sent By cthroop Date 2021-02-08 Time 07:27 Rev Time 0.00
Received By cthroop Date 2021-02-08 Time 06:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-03 Cont ID  
Sent By cthroop Date 2021-02-03 Time 09:36 Rev Time 0.00
Received By cthroop Date 2021-02-03 Time 07:58 Sent To  
Notes
2021-02-03 09:40:06PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN
 SHEETS UNDER THEIR AUTHORITY.
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL
 WITH SIGNATURE OF DESIGNER AS APPLICABLE; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT OR DROP
 OFF (OR MAIL) ONE PAPER ORIGINAL WITH CONTRACTORS/O/B
 SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By cthroop Date 2021-01-26 Time 13:17 Rev Time 0.00
Received By cthroop Date 2021-01-26 Time 11:50 Sent To  
Notes
2021-01-26 13:26:36PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: INSUFFICIENT INFORMATION FOR A COMPREHENSIVE
 REVIEW.
  
 1. PROVIDE A FLOOR PLAN. IDENTIFY LOCATION AND SCOPE OF
 WORK. IF BLDG, ROOM OR FACILITIES ARE BEING
 RE-CONFIGURED, PROVIDE AN EXISTING AND PROPOSED PLAN.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2021-02-08 Cont ID  
Sent By cthroop Date 2021-02-08 Time 07:26 Rev Time 0.00
Received By cthroop Date 2021-02-08 Time 06:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2021-02-03 Cont ID  
Sent By cthroop Date 2021-02-03 Time 09:40 Rev Time 0.00
Received By cthroop Date 2021-02-03 Time 07:58 Sent To  
Notes
2021-02-03 09:48:10SMOKE ALARMS ARE NOT REQUIRED IN EXISTING AREAS PER
 R314.2.2, EXCEPTION #2. CT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By cthroop Date 2021-01-26 Time 13:26 Rev Time 0.00
Received By cthroop Date 2021-01-26 Time 11:47 Sent To  
Notes
2021-01-26 13:30:13PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: INSUFFICIENT INFORMATION FOR A COMPREHENSIVE
 REVIEW.
  
 1. PROVIDE AN ELECTRICAL PLAN. IDENTIFY LOCATION AND
 SCOPE OF WORK. IF BLDG, ROOM OR FACILITIES ARE BEING
 RE-CONFIGURED, PROVIDE AN EXISTING AND PROPOSED PLAN.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2. SMOKE ALARMS
 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A BUILDING.
 R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 3. AN ELECTRICAL SUB-PERMIT IS REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-08 Cont ID  
Sent By cthroop Date 2021-02-08 Time 07:27 Rev Time 0.00
Received By cthroop Date 2021-02-03 Time 07:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-03 Cont ID  
Sent By cthroop Date 2021-02-03 Time 09:51 Rev Time 0.00
Received By cthroop Date 2021-01-28 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-26 Cont ID  
Sent By cthroop Date 2021-01-26 Time 13:31 Rev Time 0.00
Received By cthroop Date 2021-01-20 Time 08:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-02-05 Cont ID  
Sent By ccole Date 2021-02-05 Time 17:10 Rev Time 0.00
Received By ccole Date 2021-02-05 Time 17:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-01 Cont ID  
Sent By ccole Date 2021-02-01 Time 15:32 Rev Time 0.00
Received By ccole Date 2021-02-01 Time 13:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By ccole Date 2021-01-26 Time 07:59 Rev Time 0.00
Received By ccole Date 2021-01-26 Time 07:32 Sent To  
Notes
2021-01-26 07:59:281ST REVIEW FBC-2020 RES.
 PERMIT- 2101025
 1/26/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE PLUMBING PLANS INCLUDING AN ITEMIZED SCOPE
 OF WORK FOR THE BATH REMODELING- SECTION 107.2.1 WPB.
 PLEASE INCLUDE A SHOWER PAN DETAIL IN COMPLIANCE WITH
 SECTIONS P2709.1 & P2709.2 FBC RES. AND INCLUDE THE
 DIMENSIONS OF THE SHOWER- SECTION P2708.1.
  
 2) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-02-08 Cont ID  
Sent By cthroop Date 2021-02-08 Time 07:26 Rev Time 0.00
Received By cthroop Date 2021-02-08 Time 06:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-02-03 Cont ID  
Sent By cthroop Date 2021-02-03 Time 09:40 Rev Time 0.00
Received By cthroop Date 2021-02-03 Time 07:58 Sent To  
Notes
2021-02-03 09:40:48SEE SIGNATURE REQUIREMENT UNDER BUILDING REVIEW. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By cthroop Date 2021-01-26 Time 13:30 Rev Time 0.00
Received By cthroop Date 2021-01-26 Time 11:50 Sent To  
Notes
2021-01-26 13:31:25PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN
 SHEETS UNDER THEIR AUTHORITY.
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL
 WITH SIGNATURE OF DESIGNER AS APPLICABLE; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT OR DROP
 OFF (OR MAIL) ONE PAPER ORIGINAL WITH CONTRACTORS/O/B
 SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  