Plan Review Details - Permit 21010095
Plan Review Stops For Permit 21010095
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-03-05 Cont ID  
Sent By rmcdouga Date 2021-03-05 Time 08:11 Rev Time 0.00
Received By rmcdouga Date 2021-03-05 Time 07:51 Sent To  
Notes
2021-03-05 08:12:47SEE PERMIT #20081403 FOR GENERATOR PAD AND ANCHORING
 DETAILS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-20 Cont ID  
Sent By jleahy Date 2021-04-20 Time 16:16 Rev Time 0.00
Received By jleahy Date 2021-04-20 Time 16:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 07:06 Rev Time 0.00
Received By jleahy Date 2021-03-05 Time 07:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 14:04 Rev Time 0.00
Received By jleahy Date 2021-04-08 Time 12:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-19 Cont ID  
Sent By pvalenti Date 2021-03-19 Time 09:46 Rev Time 0.00
Received By pvalenti Date 2021-01-14 Time 12:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-03-05 Cont ID  
Sent By rmcdouga Date 2021-03-05 Time 08:12 Rev Time 0.00
Received By rmcdouga Date 2021-03-05 Time 07:51 Sent To  
Notes
2021-03-05 07:06:44ELECTRIC SIGNATURE OK JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date 2021-05-11 Cont ID  
Sent By rthermid Date 2021-05-11 Time   Rev Time 0.00
Received By rthermid Date 2021-05-11 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-03-18 Cont ID  
Sent By rthermid Date 2021-03-18 Time   Rev Time  
Received By rthermid Date 2021-03-18 Time   Sent To I
Notes
2021-03-18 11:57:34ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 3/18/2021
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PER THE CITY ZONING CODE, MECHANICAL EQUIPMENT
 CANNOT ENCROACH MORE THAN 4 FEET INTO A REQUIRED
 SETBACK. IN THIS CASE, THE GENERATOR MUST BE SETBACK A
 MINIMUM OF 11 FEET FROM THE REAR, AND 1 FOOT FROM THE
 SIDE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved