| 2021-01-26 16:18:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET FA 2 - THERE APPEARS TO BE 30CD IN THE |
| | RESTROOM STALLS, WHERE ON 15CD MAY BE REQUIRED. |
| | |
| | PLEASE REVIEW AND CORRECT IF APPLICABLE. |
| | |
| | |
| | 2) SHEET FA 2 - THERE APPEARS TO BE 75CD IN THE SINGLE |
| | RESTROOMS 1140 & 1141, WHERE ON 15CD MAY BE REQUIRED. |
| | |
| | PLEASE REVIEW AND CORRECT IF APPLICABLE. |
| | |
| | |
| | |
| | 3) SHEET FA 2 - THERE APPEARS TO BE 75CD IN THE SINGLE |
| | RESTROOMS 1204, WHERE ON 15CD MAY BE REQUIRED. |
| | |
| | PLEASE REVIEW AND CORRECT IF APPLICABLE. |
| | |
| | |
| | |
| | |
| | 4) SHEET FA 3 - IN THE ROOM LOCATED IN THE LOWER LEFT |
| | CORNER, THERE ARE NO INDICATIONS OF NOTIFICIATION AND |
| | SA DEVICES. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 5) SHEET FA 9 - AMPLIFIER LOADS IN THE CALCS SHOULD BE |
| | LABELED IN WATTS NOT AMPS |
| | |
| | PLEASE REVIEW AND CORRECT IF APPLICABLE. |
| | |
| | |
| | 6) ALL FLOOR PLAN SHEETS - WHERE ROOMS ARE CONNECTED |
| | WITH A DOOR BEWTWEEN THEM THE SA SHALL BE |
| | INTERCONNECTED. |
| | |
| | THERE ARE NO INDICATIONS THAT THE SA IN THE ADJACENT |
| | SUITES ARE INTERCONNECTED. |
| | |
| | PER NFPA 101, CH 9 |
| | |
| | 9.6.2.10.3* THE INTERCONNECTION OF SMOKE ALARMS SHALL |
| | APPLY ONLY |
| | TO NEW CONSTRUCTION AS PROVIDED IN 9.6.2.10.8. |
| | |
| | 9.6.2.10.8* IN NEW CONSTRUCTION, WHERE TWO OR MORE |
| | SMOKE ALARMS |
| | ARE REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR |
| | SIMILAR AREA, |
| | THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE |
| | ALARM SHALL |
| | CAUSE THE ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING |
| | UNIT, SUITE |
| | OF ROOMS, OR SIMILAR AREA TO SOUND, UNLESS OTHERWISE |
| | PERMITTED BY |
| | ONE OF THE FOLLOWING: |
| | |
| | (1) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY WHERE |
| | PERMITTED BY ANOTHER SECTION OF THIS CODE. |
| | (2) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY TO |
| | CONFIGURATIONS THAT PROVIDE EQUIVALENT DISTRIBUTION OF |
| | THE |
| | ALARM SIGNAL. |
| | 9.6.2.10.9 THE ALARMS DESCRIBED IN 9.6.2.10.8 SHALL |
| | SOUND ONLY |
| | WITHIN AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR |
| | SIMILAR AREA |
| | AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM, |
| | UNLESS |
| | OTHERWISE PERMITTED BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | PLEASE REVIEW AND CORRECT AND PROVIDE A NOTE OF |
| | ACKNOWLEDGEMENT IN THOSE ROOMS. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |