| Plan Review Stops For Permit 20121411 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-07-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-07-14 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-07-14 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-06-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-06-18 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-06-18 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2021-06-18 11:46:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | | | | 1. REVISE GOVERNING CODE, SHOULD BE FBC 7TH EDITION. | | | | | | 2. SUBMIT PRODUCT APPROVALS, REVIEWED BY DESIGNER OF | | | RECORD, FOR THE WINDOWS AND DOOR. IF YOU WANT FOR THIS | | | TO BE A DEFERRED SUBMITTAL YOU MAY REQUEST IT BUT IF | | | THIS IS REQUESTED PLEASE EXPLAIN WHY THAT IS NEEDED. | | | SCOPE OF PROJECT IS VERY SMALL. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-05-26 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-05-26 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-05-26 |
Time |
08:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-09-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-09-03 |
Time |
14:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-07-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-19 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-13 |
Time |
14:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-06-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-06-18 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-05-18 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-07-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-19 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-19 |
Time |
06:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-25 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-25 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2021-05-25 15:51:07 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-20121411 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M101: THE GENERAL HVAC NOTES ARE CONSISTENT | | | WITH INSTALLING A MECHANICAL SYSTEM ALTHOUGH THE | | | DRAWING DOES NOT SHOW A MECHANICAL VENTILATION SYSTEM. | | | IF THIS PROJECT DOES NOT INCLUDE A MECHANICAL SYSTEM | | | PLEASE REMOVE NOTES THAT DO NOT MEET THE SCOPE OF THIS | | | PROJECT. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-07-16 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-07-16 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-07-16 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2021-07-16 08:53:27 | 07/16/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-05-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-05-27 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-05-27 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2021-05-27 11:50:47 | 05/27/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ON SHEET A101 AND P101 HAS THE INCORRECT REFERENCE | | | CODE; PLEASE SHOW THE CURRENT CODE YEAR AND EDITION PER | | | THE WPB AMENDMENTS TO THE FBC SEC. 101.4 REFERENCED | | | CODES. | | | | | | 2. SIGNED AND SEALED DRAWINGS NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF AT CITY HALL THE ORIGINAL | | | SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN REVIEW | | | REQUEST FORM" EXPLAINING THE REASON FOR SUBMITTING THE | | | DOCUMENT OR DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN | | | BE OBTAINED BY EMAILING [email protected] AND ASKING FOR THE | | | FORM. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-09-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-09-07 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-09-07 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2021-09-03 14:32:53 | FILES UNDER SIGNATURES FOLDER |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-07-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-19 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-19 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2021-07-19 07:44:34 | PLEASE PROVIDE DIGITALLY SIGNED DRAWINGS. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-05-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-25 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-25 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2021-05-25 15:52:55 | PLANS WERE SUBMITTED DIGITALLY, THE DESIGNER OF THE | | | DRAWINGS MUST PROVIDE AN ORIGINAL DIGITALLY SIGNED | | | DRAWINGS. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|