Plan Review Details - Permit 20121350
Plan Review Stops For Permit 20121350
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-03-24 Cont ID  
Sent By cpuell Date 2021-03-24 Time 14:10 Rev Time 0.00
Received By cpuell Date 2021-03-24 Time 14:10 Sent To  
Notes
2021-03-24 14:11:28ADDRESS CHANGED TO 304

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By cpuell Date 2021-03-09 Time 10:51 Rev Time 0.00
Received By cpuell Date 2021-03-09 Time 10:51 Sent To  
Notes
2021-03-09 10:52:39ADDRESSING COMMENTS NOT ADDRESSED, PLEASE EMAIL
 [email protected] TO ESTABLISH A SUITE FOR THIS JOB, 304
 NOR 304A IS NOT IN ANY OF OUR SYSTEMS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-30 Cont ID  
Sent By cpuell Date 2020-12-30 Time 15:51 Rev Time 0.00
Received By cpuell Date 2020-12-30 Time 15:51 Sent To  
Notes
2020-12-30 15:52:33UNIT 304 ISN'T IN OUR DATABASES AS A LEGAL ADDRESS
 PLEASE REACH OUT TO [email protected] TO ESTABLISH AN
 ADDRESS

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-03-09 Cont ID  
Sent By shill Date 2021-03-09 Time 10:38 Rev Time 0.00
Received By shill Date 2021-03-09 Time 10:38 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-03-08 Cont ID  
Sent By rmcdouga Date 2021-03-08 Time 12:47 Rev Time 0.00
Received By rmcdouga Date 2021-03-08 Time 12:47 Sent To  
Notes
2021-03-08 12:49:04ASBESTOS LETTER NOT SUBMITTED.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-01-16 Cont ID  
Sent By jwitmer Date 2021-01-16 Time 11:34 Rev Time 0.00
Received By jwitmer Date 2021-01-16 Time 11:17 Sent To  
Notes
2021-01-16 11:19:25TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-01-16 Cont ID  
Sent By jwitmer Date 2021-01-16 Time 11:35 Rev Time 0.00
Received By jwitmer Date 2021-01-16 Time 11:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-25 Cont ID  
Sent By equinone Date 2021-01-25 Time 10:47 Rev Time 0.00
Received By equinone Date 2021-01-25 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By pleduc Date 2021-03-23 Time   Rev Time 0.00
Received By pleduc Date 2021-03-23 Time 11:13 Sent To  
Notes
2021-03-23 11:17:18THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-15 Cont ID  
Sent By pleduc Date 2021-01-15 Time   Rev Time 0.00
Received By pleduc Date 2021-01-15 Time 15:02 Sent To  
Notes
2021-01-15 15:22:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-03-26 Time   Rev Time 0.00
Received By aoliver Date 2021-03-22 Time 13:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-09 Cont ID  
Sent By cpuell Date 2021-03-09 Time 10:52 Rev Time 0.00
Received By cpuell Date 2021-02-24 Time 08:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-25 Cont ID  
Sent By equinone Date 2021-01-25 Time 10:48 Rev Time 0.00
Received By equinone Date 2021-01-13 Time 00:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-15 Cont ID  
Sent By medwards Date 2021-01-15 Time 14:40 Rev Time 0.00
Received By medwards Date 2021-01-15 Time 14:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By ccole Date 2021-03-26 Time 07:22 Rev Time 0.00
Received By ccole Date 2021-03-25 Time 16:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By ccole Date 2021-03-05 Time 13:21 Rev Time 0.00
Received By ccole Date 2021-03-05 Time 12:12 Sent To  
Notes
2021-03-05 13:22:192ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20121350
 3/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAP LETTERS. THE REQUESTED COMMENT RESPONSE NARRATIVE
 WAS NOT PROVIDED.
  
 1) FAILED. P-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL
 TO SEAL THE ANNULAR SPACE AROUND THE NEW SINK DRAIN
 PIPING PENETRATIONS- SECTION 315.1 FBC P AND SECTION
 714.4.1.2 FBC B. PLEASE CLARIFY IF THE NEW SINK DRAIN
 PENETRATIONS WILL REQUIRE THE FLOOR TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS- SECTION 107.2.1 WPB. FIRESTOPPING NOT
 PROVIDED.
  
 2) FAILED. SECTION 212.3 REQUIRES 5%, BUT NO FEWER THAN
 ONE, OF EACH TYPE IN EACH ACCESSIBLE ROOM TO BE IN
 COMPLIANCE WITH SECTION 606 FBC ACC. PLEASE PROVIDE THE
 FOLLOWING DETAILS PER THE FBC ACC. REVISED SHEET A1.03
 DOES NOT INDICATE CLEAR FLOOR SPACES FOR THE NEW
 ACCESSIBLE SINKS IN THE BREAKROOM AND OFFICE.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 NEW SINKS- SECTIONS 212.3 AND 606.
 B) KNEE AND TOE CLEARANCES FOR THE NEW SINKS- 606.2,
 305, & 306.
 C) HEIGHT OF THE SINK RIMS OR COUNTER SURFACES ABOVE
 THE FINISH FLOORS- 606.3.
  
 3) FAILED. P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE
 THAT INCLUDES THE MAKES, MODELS, DIMENSIONS AND LISTING
 NUMBERS OF THE NEW SINKS- SECTIONS 418 & 424 FBC P. THE
 SCHEDULE ON THE PLAN INDICATES A JANITOR SINK WHICH
 NEEDS TO BE IDENTIFIED ON THE PLAN. IT IS NOT CLEAR
 WHAT THE REST OF THE SINKS IN THE ROOMS ARE TO BE USED
 FOR BECAUSE THEY ARE LISTED AS "BY OWNER". PLEASE
 CLARIFY THE USE OF THE SINKS AND NOTE THAT DEFERRED
 SUBMITTALS ARE ALLOWED, BUT ALL SPECIFICATIONS MUST BE
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL IN
 CHARGE- SECTION 107.3.4.1 WPB. THREE NEW SINKS ARE
 BEING INSTALLED WHICH SHALL BE ACCESSIBLE. PLEASE
 PROVIDE THE REQUESTED SINK INFO IN THE SCHEDULE OR
 PROVIDE A NOTE TO INDICATE THE 3 SINKS WILL BE
 ACCESSIBLE TYPES.
  
 4) FAILED. P-1: CLARIFY IF THE NEW DRAIN PIPES WILL BE
 RUNNING THROUGH A PLENUM SPACE AND INDICATE THE TYPE OF
 PIPE MATERIALS TO BE INSTALLED- SECTION 303.2 FBC P AND
 107.2.1 WPB. SHEET P1 NOTES INDICATE PVC WASTE PIPING
 WHICH SHALL NOT BE INSTALLED IN PLENUM SPACES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-22 Cont ID  
Sent By ccole Date 2021-01-22 Time 16:21 Rev Time 0.00
Received By ccole Date 2021-01-22 Time 14:01 Sent To  
Notes
2021-01-22 16:22:031ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20121350
 1/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL TO SEAL
 THE ANNULAR SPACE AROUND THE NEW SINK DRAIN PIPING
 PENETRATIONS- SECTION 315.1 FBC P AND SECTION 714.4.1.2
 FBC B. PLEASE CLARIFY IF THE NEW SINK DRAIN
 PENETRATIONS WILL REQUIRE THE FLOOR TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS- SECTION 107.2.1 WPB.
  
 2) SECTION 212.3 REQUIRES 5%, BUT NO FEWER THAN ONE, OF
 EACH TYPE IN EACH ACCESSIBLE ROOM TO BE IN COMPLIANCE
 WITH SECTION 606 FBC ACC. PLEASE PROVIDE THE FOLLOWING
 DETAILS PER THE FBC ACC.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 NEW SINKS- SECTIONS 212.3 AND 606.
  
 B) KNEE AND TOE CLEARANCES FOR THE NEW SINKS- 606.2,
 305, & 306.
  
 C) HEIGHT OF THE SINK RIMS OR COUNTER SURFACES ABOVE
 THE FINISH FLOORS- 606.3.
  
 3) P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE THAT
 INCLUDES THE MAKES, MODELS, DIMENSIONS AND LISTING
 NUMBERS OF THE NEW SINKS- SECTIONS 418 & 424 FBC P. THE
 SCHEDULE ON THE PLAN INDICATES A JANITOR SINK WHICH
 NEEDS TO BE IDENTIFIED ON THE PLAN. IT IS NOT CLEAR
 WHAT THE REST OF THE SINKS IN THE ROOMS ARE TO BE USED
 FOR BECAUSE THEY ARE LISTED AS "BY OWNER". PLEASE
 CLARIFY THE USE OF THE SINKS AND NOTE THAT DEFERRED
 SUBMITTALS ARE ALLOWED, BUT ALL SPECIFICATIONS MUST BE
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL IN
 CHARGE- SECTION 107.3.4.1 WPB.
  
 4) P-1: CLARIFY IF THE NEW DRAIN PIPES WILL BE RUNNING
 THROUGH A PLENUM SPACE AND INDICATE THE TYPE OF PIPE
 MATERIALS TO BE INSTALLED- SECTION 303.2 FBC P AND
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By ccole Date 2021-03-26 Time 07:22 Rev Time 0.00
Received By ccole Date 2021-03-25 Time 16:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By ccole Date 2021-03-05 Time 13:26 Rev Time 0.00
Received By ccole Date 2021-03-05 Time 13:26 Sent To  
Notes
2021-03-05 13:32:36SIGNATURE REVIEW
 3/5/2021
  
 THE NEW PLAN SHEET A03 REQUIRES AN ELECTRONIC SEAL AND
 SIGNATURE BY THE ARCHITECT OF RECORD- FL STATUTE
 481.221 AND SECTION 61G1-16.005 FLORIDA ADMINISTRATIVE
 CODE.
  
 CHRISTOPHER L. COLE
 PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-15 Cont ID  
Sent By medwards Date 2021-01-15 Time 14:43 Rev Time 0.00
Received By medwards Date 2021-01-15 Time 14:43 Sent To  
Notes
***NONE***