| 2021-01-13 10:22:59 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 20121335 |
| | 1/13/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | NFPA 58-14 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED SURVEY INDICATES THE 250-GALLON LP |
| | TANK AS EXISTING HOWEVER THE TANK PERMIT- 10090018 HAS |
| | EXPIRED AND FINAL INSPECTION OF THE TANK WAS NEVER |
| | PERFORMED. PLEASE NOTE THAT THE SCOPE OF WORK FOR |
| | PERMIT 10090018 WAS TO MANIFOLD TOGETHER A NEW |
| | 250-GALLON LP TANK TO AN EXISTING LP TANK. BECAUSE YOUR |
| | PERMIT WILL INVOLVE CONNECTING THE NEW GAS LINE FROM |
| | THE TANKS TO THE GENERATOR, THE NEW TANK MUST ALSO |
| | RECEIVE FINAL APPROVAL EITHER UNDER THIS NEW GAS |
| | PERMIT, OR UNDER THE PREVIOUS PERMIT THAT WAS OBTAINED |
| | BY TANKS AND MOORE GAS SERVICE. PLEASE SEND AN EMAIL TO |
| | [email protected] FOR FURTHER ASSISTANCE. |
| | |
| | 2) THE GAS RISER DRAWING HAS AN INCOMPLETE UG LP TANK |
| | HOLD DOWN DETAIL HOWEVER THE RISER INDICATES THE TANK |
| | AS EXISTING. AGAIN, IT IS NOT CLEAR WHICH CONTRACTOR |
| | WILL BE ACCEPTING RESPONSIBILITY FOR THE NEW TANK |
| | INSTALLATION, HOWEVER PLEASE NOTE THAT COMPLETE DETAILS |
| | FOR INSTALLATION OF THE TANK ARE REQUIRED FOR THE FINAL |
| | INSPECTION. PLEASE REVISE THE RISER AND PROVIDE |
| | ADDITIONAL DETAILS PER ITEMS A- F BELOW: |
| | |
| | A) SHOW THE SEPARATION DISTANCE BETWEEN THE TWO |
| | UNDERGROUND TANKS. A 3FT. SEPARATION IS REQUIRED PER |
| | TABLE 6.3.1.1 NFPA 58. |
| | |
| | B) REVISE THE RISER DRAWING TO SHOW THE TANKS |
| | MANIFOLDED TOGETHER, AND PROVIDE A DETAIL SHOWING HOW |
| | THE PIPING INTERCONNECTION WILL BE MADE- SECTION |
| | 6.9.3.9 NFPA 58. PLEASE NOTE THAT PE PIPE CANNOT BE |
| | USED FOR PERMANENT INTERCONNECTION OF THE TANKS- |
| | SECTION 6.9.3.9B NFPA 58. |
| | |
| | C) SHOW HOW THE REGULATOR WILL BE CONNECTED TO THE |
| | MANIFOLD- SECTION 6.8.1.1 NFPA 58. |
| | |
| | D) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | 250-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| | BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| | IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| | REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| | SECTION 5.2.1.1 NFPA 58. |
| | |
| | E) PROVIDE LP TANK INSTALLATION DETAILS SHOWING HOW THE |
| | TANK WILL BE ANCHORED TO PREVENT FLOTATION, COLLAPSE, |
| | OR LATERAL MOVEMENT- SECTION 6.6.1.6. PLEASE INCLUDE A |
| | FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE BURIAL |
| | DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES, SIZES, |
| | AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND THE TYPE |
| | OF PROTECTIVE SLEEVES FOR THE CABLES OR STRAPS. |
| | |
| | F) SHOW HOW THE TANK WILL BE PROTECTED AGAINST |
| | CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| | SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| | IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & |
| | 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND |
| | HOW IT WILL BE TESTED- SECTION 6.17.1. |
| | |
| | 3) PLEASE MARK UP THE SURVEY DRAWING TO SHOW BOTH OF |
| | THE TANKS AND THE AND REQUIRED 10 FT. UG TANK CLEARANCE |
| | DISTANCES TO THE HOUSE AND ADJACENT PROPERTY LINES- |
| | TABLE 6.3.1.1 NFPA 58. PLEASE NOTE THAT IF THE TANKS |
| | ARE LESS TANK 10 FT. FROM THE DRIVEWAY, THE SHELLS FOR |
| | THE TANKS SHALL BE 18 IN. BELOW GRADE OR VEHICULAR |
| | BARRIER PROTECTION WILL BE REQUIRED- SECTIONS 6.6.6.1 |
| | (A). |
| | |
| | 4) THE ADDRESS OF THE PROJECT, SIGNATURE AND PRINTED |
| | NAME OF THE CONTRACTOR ARE CUT OFF SLIGHTLY ON THE |
| | RISER DRAWING AND CANNOT BE VIEWED PROPERLY. PLEASE |
| | PROVIDE ALL THE INFORMATION CLEARLY ON THE REVISED |
| | DRAWING- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |