| Plan Review Stops For Permit 20121298 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2021-03-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-03-22 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-03-22 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-01-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-26 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-01-26 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2021-01-26 09:04:06 | TO THE BUILDING CONTRACTOR: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING: THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2021-01-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-01-26 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-01-26 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-07 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-07 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-01-28 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-01-28 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-01-28 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-01-06 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-01-06 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-07 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-03-23 |
Time |
09:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-03-22 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-02-24 |
Time |
07:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-01-28 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-01-28 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-12-30 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-15 |
Time |
08:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-01-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-01-19 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-01-19 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2021-01-19 13:47:15 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-20121298 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2020 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2020 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE MORE INFORMATION FOR THE STERILIZER, | | | WHAT IS THE SIZE OF THE OLD STERILIZER? PLEASE SHOW THE | | | EXISTING STERILIZER AND THE EXISTING HOOD. PLEASE SHOW | | | THE NEW STERILIZER AND THE MODIFICATION OF THE EXISTING | | | HOOD. IS THE EXHAUST SYSTEM ABLE TO HANDLE THE NEW | | | STERILIZER? FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-03-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-03-19 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-03-19 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-01-24 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2021-01-24 |
Time |
02:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2021-01-22 |
Time |
05:35 |
Sent To |
|
|
| Notes |
| 2021-01-22 10:36:50 | 1) SUBMIT ADDITIONAL INFORMATIONL FOR THE STERILIZER | | | SUCH AS MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | MANUAL. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE | | | COLD WATER SUPPLY TO THE STERILIZER IF THE SUPPLY IS | | | POTABLE WATER. CLARIFY THE ACRONYMN "NPCW." | | | FBC-PLUMBING SEC.608.3.1. | | | 3) INDICATE THE TYPE OF PIPE FOR THE DRAIN ON THE | | | STERILIZER. WHERE THE WASTE WATER TEMPERATURE WILL BE | | | GREATER THAN 140 DEGREES, THE PIPING MATERIAL SHALL BE | | | RATED FOR THE HIGHEST TEMPERATURE OF THE WASTE WATER. | | | FBC-PLUMBING SEC. 702.5. | | | 4) WHAT IS THE TEMPERATURE OF THE HOT WATER? THE | | | THICKNESS OF THE REQUIRED INSULATION SHALL COMPLY WITH | | | FBC-ENERGY TABLE C403.2.10.REFER TO SHT. P1.1 - | | | PLUMBING SPECIFICATIONS NOTE #14 (C) - | | | 5) SUBMIT THE INSTALLATION MANUAL FOR THE STERILIZER. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) SHT. P1.1 - PLUMBING NOTES - NOTE #6 REFERS TO 1/2 " | | | NPHW RINSE WATER LINE BUT THIS LINE IS NOT SHOWN ON THE | | | STERILIZER PIPING DIAGRAM. CLARIFY. | | | 7) PLUMBING SHEET NOT DIGITALLY SIGNED AND SEALED AND | | | REQUIRES 3RD PARTY CERTIFICATION PER FL. ADDMIN. CODE | | | RULE 61G15-23.004. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-04-07 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-07 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-07 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-03-15 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-15 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-15 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2021-03-15 08:47:53 | THE 2ND CYCLE ELECTRICAL DRAWINGS ARE NOT DIGITALLY | | | SIGNED AND SEALED. PLEASE SUBMIT DIGITALLY SIGNED AND | | | SEALED DRAWINGS. | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-01-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-01-19 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-01-19 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2021-01-19 13:54:36 | THE MEP SHEETS ENGINEER MUST HAVE 3RD PARTY | | | VERIFICATION. | | | | | | 61G15?23.004 F.A.C. | | | (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL | | | SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL | | | HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION | | | AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE | | | IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF | | | VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE | | | SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO | | | A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE | | | AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY | | | DATA IN THE DOCUMENT IS CHANGED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|