Plan Review Details - Permit 20121298
Plan Review Stops For Permit 20121298
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-03-22 Cont ID  
Sent By pvalenti Date 2021-03-22 Time 09:09 Rev Time 0.00
Received By pvalenti Date 2021-03-22 Time 09:08 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By jwitmer Date 2021-01-26 Time 09:04 Rev Time 0.00
Received By jwitmer Date 2021-01-26 Time 08:28 Sent To  
Notes
2021-01-26 09:04:06TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-01-26 Cont ID  
Sent By jwitmer Date 2021-01-26 Time 09:36 Rev Time 0.00
Received By jwitmer Date 2021-01-26 Time 08:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-07 Cont ID  
Sent By equinone Date 2021-04-07 Time 10:41 Rev Time 0.00
Received By equinone Date 2021-04-07 Time 10:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-28 Cont ID  
Sent By equinone Date 2021-01-28 Time 15:45 Rev Time 0.00
Received By equinone Date 2021-01-28 Time 09:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-06 Cont ID  
Sent By pleduc Date 2021-01-06 Time   Rev Time 0.00
Received By pleduc Date 2021-01-06 Time 09:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-07 Cont ID  
Sent By equinone Date 2021-04-07 Time 10:46 Rev Time 0.00
Received By equinone Date 2021-03-23 Time 09:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-22 Cont ID  
Sent By pvalenti Date 2021-03-22 Time 09:09 Rev Time 0.00
Received By pvalenti Date 2021-02-24 Time 07:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-28 Cont ID  
Sent By equinone Date 2021-01-28 Time 15:46 Rev Time 0.00
Received By equinone Date 2020-12-30 Time 14:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-15 Cont ID  
Sent By medwards Date 2021-03-15 Time 08:40 Rev Time 0.00
Received By medwards Date 2021-03-15 Time 08:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-19 Cont ID  
Sent By medwards Date 2021-01-19 Time 13:47 Rev Time 0.00
Received By medwards Date 2021-01-19 Time 13:47 Sent To  
Notes
2021-01-19 13:47:151ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20121298
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MORE INFORMATION FOR THE STERILIZER,
 WHAT IS THE SIZE OF THE OLD STERILIZER? PLEASE SHOW THE
 EXISTING STERILIZER AND THE EXISTING HOOD. PLEASE SHOW
 THE NEW STERILIZER AND THE MODIFICATION OF THE EXISTING
 HOOD. IS THE EXHAUST SYSTEM ABLE TO HANDLE THE NEW
 STERILIZER? FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-19 Cont ID  
Sent By tklarge Date 2021-03-19 Time 14:03 Rev Time 0.00
Received By tklarge Date 2021-03-19 Time 13:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-24 Cont ID  
Sent By tklarge Date 2021-01-24 Time 02:48 Rev Time 0.00
Received By tklarge Date 2021-01-22 Time 05:35 Sent To  
Notes
2021-01-22 10:36:501) SUBMIT ADDITIONAL INFORMATIONL FOR THE STERILIZER
 SUCH AS MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUAL. WPB AMEND. TO FBC SEC. 107.2.1.
 2) A BACKFLOW PREVENTION DEVICE WILL BE REQUIRED ON THE
 COLD WATER SUPPLY TO THE STERILIZER IF THE SUPPLY IS
 POTABLE WATER. CLARIFY THE ACRONYMN "NPCW."
 FBC-PLUMBING SEC.608.3.1.
 3) INDICATE THE TYPE OF PIPE FOR THE DRAIN ON THE
 STERILIZER. WHERE THE WASTE WATER TEMPERATURE WILL BE
 GREATER THAN 140 DEGREES, THE PIPING MATERIAL SHALL BE
 RATED FOR THE HIGHEST TEMPERATURE OF THE WASTE WATER.
 FBC-PLUMBING SEC. 702.5.
 4) WHAT IS THE TEMPERATURE OF THE HOT WATER? THE
 THICKNESS OF THE REQUIRED INSULATION SHALL COMPLY WITH
 FBC-ENERGY TABLE C403.2.10.REFER TO SHT. P1.1 -
 PLUMBING SPECIFICATIONS NOTE #14 (C) -
 5) SUBMIT THE INSTALLATION MANUAL FOR THE STERILIZER.
 WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT. P1.1 - PLUMBING NOTES - NOTE #6 REFERS TO 1/2 "
 NPHW RINSE WATER LINE BUT THIS LINE IS NOT SHOWN ON THE
 STERILIZER PIPING DIAGRAM. CLARIFY.
 7) PLUMBING SHEET NOT DIGITALLY SIGNED AND SEALED AND
 REQUIRES 3RD PARTY CERTIFICATION PER FL. ADDMIN. CODE
 RULE 61G15-23.004.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-07 Cont ID  
Sent By equinone Date 2021-04-07 Time 10:46 Rev Time 0.00
Received By equinone Date 2021-04-07 Time 10:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-15 Cont ID  
Sent By medwards Date 2021-03-15 Time 08:46 Rev Time 0.00
Received By medwards Date 2021-03-15 Time 08:46 Sent To  
Notes
2021-03-15 08:47:53THE 2ND CYCLE ELECTRICAL DRAWINGS ARE NOT DIGITALLY
 SIGNED AND SEALED. PLEASE SUBMIT DIGITALLY SIGNED AND
 SEALED DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-19 Cont ID  
Sent By medwards Date 2021-01-19 Time 13:53 Rev Time 0.00
Received By medwards Date 2021-01-19 Time 13:53 Sent To  
Notes
2021-01-19 13:54:36THE MEP SHEETS ENGINEER MUST HAVE 3RD PARTY
 VERIFICATION.
  
 61G15?23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  