| Plan Review Stops For Permit 20121295 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-01-05 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-01-05 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
N |
Date |
2023-01-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-01-10 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-01-10 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2023-01-10 11:09:48 | PROPOSED POLE IS IN THE RIGHT OF WAY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
N |
Date |
2022-06-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-06-27 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-06-27 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2022-06-27 08:42:09 | POLE IS IN THE RIGHT OF WAY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-20 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-20 |
Time |
09:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-04 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-04 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2021-05-04 12:37:24 | ANTENNA | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE THE STRUCTURAL DETAILS AND | | | CALCULATIONS FROM A DESIGN PROFESSIONAL FOR THE POLE | | | AND MOUNTED ANTENNA SHOWING FOUNDATION AND ATTACHMENTS | | | TO COMPLY WITH THE WIND LOADS PER FBC 1609 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-01-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-28 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-28 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2021-01-28 14:55:20 | ANTENNA POLE | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE POLE DETAILS TO COMPLY WITH THE WIND | | | LOADS PER FBC 1609 OR STATE ON THE PLANS THAT POLE IS | | | TO BE UNDER A SEPARATE PERMIT. | | | 2) CODE IN EFFECT HAS CHANGED ON 1/1/21 - PLEASE REVISE | | | THE DRAWINGS TO REFLECT THE DESIGN TO BE BASED ON THE | | | 2020 FBC | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2023-01-12 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-12 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-12 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2022-07-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-07-01 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-07-01 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2021-12-21 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-21 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-21 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-04-27 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-04-27 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-04-27 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-01-25 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-01-25 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-01-25 |
Time |
09:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-01-04 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-04 09:41:35 | REVIEWED AS PART OF WCF ROW PERMIT |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2021-07-01 |
|
|
Cont ID |
|
| Sent By |
gpatrie |
Date |
2021-07-01 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
gpatrie |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-07-01 09:57:06 | PULLBOX LAT/LONG REQUIRED. | | | REF #19021027 | | | | | | CONTACT: [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-14 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-01-06 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-08-29 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-06-16 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-01-05 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-09 |
Time |
07:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-07-02 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-07-02 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-04-20 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-01-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-28 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-12 |
Time |
08:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2023-01-12 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-01-12 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-01-12 |
Time |
16:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-07-01 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-07-01 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-07-01 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-20 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-20 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2021-12-20 09:17:41 | SIGNATURE REVIEW | | | | | | DRAWINGS BELOW AS LABELED IN PROJECTDOX DO NOT SHOW AS | | | DIGITALLY SIGNED IN ADOBE READER - | | | | | | 006 E5 - UTILITY ROUTING-GROUNDING PLAN.PDF | | | 013 B1 SURVEY.PDF | | | RAYCAP_POLE DESIGN_24-FOOT POLE-09-28-2021.PDF | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | | DIVISION AT THE CITY HALL. | | | | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-05-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-04 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-04 |
Time |
12:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-01-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-28 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-28 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2021-01-28 14:57:30 | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2023-03-14 |
Time |
14:48 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2023-02-01 |
Time |
13:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-08-29 |
Time |
10:37 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2022-08-29 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2022-08-29 10:42:37 | FAILED | | | | | | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT | | | PERMIT - CITY RIGHTS-OF-WAY (19021027) MUST BE APPROVED | | | PRIOR TO THIS PERMIT BEING APPROVED. NOTE: THIS PERMIT | | | MEETS ZONING REQUIREMENTS. | | | | | | 2) THE POLE HEIGHT AND STEALTH DESIGN MEET CITY | | | STANDARDS. THE POLE COLOR AT THIS LOCATION SHALL BE | | | RAL/RAYCAP 7022 UMBRA GREY. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-01-04 |
Time |
17:06 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2022-01-04 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2022-01-04 17:11:48 | FAILED | | | | | | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT | | | PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO | | | THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH | | | THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED | | | WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS | | | BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS | | | WELL AS WITH THIS PERMIT. | | | | | | 2) THE POLE HEIGHT AND STEALTH DESIGN MEET CITY | | | STANDARDS. THE POLE COLOR IS TO MATCH THE EXISTING | | | DECORATIVE CITY LIGHT POLES (SPECKLED BLACK) LOCATED | | | ALONG FERN STREET. | | | | | | 3) REPEAT COMMENT: THE PLANTERS THAT ARE SHOWN ON THE | | | SURVEY AND ENGINEERING PLANS ARE SURROUNDED BY A | | | STRUCTURAL SOIL SYSTEM THAT IS NOT PERMITTED TO BE | | | DISTURBED BY THE INSTALLATION OF THE PROPOSED POLE, | | | GROUND RODS, FIBER/POWER PULL BOX AND UNDERGROUND | | | ELECTRIC, SO THE CURRENT LOCATION IS NOT APPROVED. THE | | | FULL AREA COVERED BY THE STRUCTURAL SOIL UNDER THE | | | SIDEWALK IS A MINIMUM OF 19 FEET EAST TO WEST AND THE | | | FULL DEPTH OF THE SIDEWALK FROM THE CURB TO THE EDGE OF | | | THE RIGHT-OF-WAY LINE. NO EXCAVATION OR INSTALLATION | | | MAY OCCUR CLOSER THAN SEVEN (7) FEET FROM A PARALLEL | | | LINE WITH THE OUTER EDGES OF THE PLANTER WALLS, FROM | | | THE CURB FACE TO THE RIGHT-OF-WAY LINE. | | | | | | 3) THE STAFF HAS MARKED THE SURVEY WITH TWO GREEN | | | LINES, THAT ARE APPROXIMATELY 10 FEET APART WHERE YOU | | | MAY INSTALL THE POLE, PULL BOX, GROUND RODS, ETC.. THIS | | | FINAL LAYOUT IN THIS AREA MUST BE PROVIDED ON A BLOW UP | | | INSET WITH DIMENSIONS. | | | | | | 4) THE POLE NEEDS TO BE PUSHED AS CLOSE TO THE CURB AS | | | POSSIBLE GIVEN THE OVERHEAD WIRE IN ORDER TO MAINTAIN | | | AS MUCH OF A STREET FURNITURE RHYTHM AS POSSIBLE AND TO | | | MAINTAIN A UNIFORM SIDEWALK WIDTH BEHIND THE PLANTERS. | | | | | | 5) THANK YOU FOR PROVIDING THE UTILITY POWER PLAN. THE | | | POWER PATH IS SHOWN DISTURBING THE STRUCTURAL SOIL | | | SYSTEM, WHICH IS NOT PERMITTED. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-05-26 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2021-05-26 |
Time |
16:31 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2021-05-26 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2021-05-26 16:33:17 | FAILED | | | | | | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT | | | PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO | | | THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH | | | THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED | | | WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS | | | BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS | | | WELL AS WITH THIS PERMIT. | | | | | | 2) SHEET T1 LISTS THE SCOPE OF WORK INCLUDES THE | | | INSTALLATION OF AN ENCLOSURE CABINET. NONE OF THE PLANS | | | SHOW AN ENCLOSURE CABINET. PLEASE CLARIFY WHAT THIS | | | MEANS. THE CITY DOES NOT PERMIT FREESTANDING OR POLE | | | MOUNTED CABINETS. | | | | | | 3) THE POLE HEIGHT AND STEALTH DESIGN MEET CITY | | | STANDARDS. THE POLE COLOR IS TO MATCH THE EXISTING | | | DECORATIVE CITY LIGHT POLES (SPECKLED BLACK) LOCATED | | | ALONG FERN STREET. | | | | | | 3) THE PLANTERS THAT ARE SHOWN ON THE SURVEY AND | | | ENGINEERING PLANS ARE SURROUNDED BY A STRUCTURAL SOIL | | | SYSTEM THAT IS NOT PERMITTED TO BE DISTURBED BY THE | | | INSTALLATION OF THE PROPOSED POLE, GROUND RODS, | | | FIBER/POWER PULL BOX AND UNDERGROUND ELECTRIC, SO THE | | | CURRENT LOCATION IS NOT APPROVED. THE FULL AREA COVERED | | | BY THE STRUCTURAL SOIL UNDER THE SIDEWALK IS A MINIMUM | | | OF 19 FEET EAST TO WEST AND THE FULL DEPTH OF THE | | | SIDEWALK FROM THE CURB TO THE EDGE OF THE RIGHT-OF-WAY | | | LINE. NO EXCAVATION OR INSTALLATION MAY OCCUR CLOSER | | | THAN SEVEN (7) FEET FROM A PARALLEL LINE WITH THE OUTER | | | EDGES OF THE PLANTER WALLS, FROM THE CURB FACE TO THE | | | RIGHT-OF-WAY LINE. | | | | | | 5) THERE ARE APPROXIMATELY 10 FEET BETWEEN THE PARALLEL | | | LINES MENTIONED IN THE PREVIOUS COMMENT, WHICH PROVIDES | | | ADEQUATE ROOM TO INSTALL THE POLE AND THE PULL BOX; | | | HOWEVER, STAFF DOES NOT KNOW WHAT THE GROUND ROD | | | REQUIREMENTS ARE AND IF THERE IS AN ABILITY TO FIT THEM | | | INTO THE AREA AS WELL (IT APPEARS CLOSE WITH THE | | | CONFIGURATION AS SHOWN). THIS FINAL LAYOUT IN THIS AREA | | | MUST BE PROVIDED ON A BLOW UP INSET WITH DIMENSIONS. | | | | | | 6) STAFF CAN PROVIDE THE ENGINEERING DRAWINGS SHOWING A | | | DETAIL FOR THE BIOSWALE PIT WITH THE SURROUNDING | | | STRUCTURAL SOIL IF YOU NEED IT. | | | | | | 7) THE STEALTH POLE SHOWN ON SHEET C3, ELEVATION AND | | | EQUIPMENT PLAN, HAS A 14-INCH DIAMETER. SCALING THE | | | POLE ON THE SURVEY AND SITE PLAN SHOW A SEVEN (7) INCH | | | DIAMETER POLE. THE SURVEY AND SITE PLAN NEED TO SHOW | | | THE CORRECT POLE SIZE AND DIMENSIONS FROM THE VARIOUS | | | FEATURES SHOWN. | | | | | | 8) THE POLE NEEDS TO BE PUSHED AS CLOSE TO THE CURB AS | | | POSSIBLE GIVEN THE OVERHEAD WIRE IN ORDER TO MAINTAIN | | | AS MUCH OF A STREET FURNITURE RHYTHM AS POSSIBLE AND TO | | | MAINTAIN A UNIFORM SIDEWALK WIDTH BEHIND THE PLANTERS. | | | | | | 9) THE UTILITY POWER PLAN WAS NOT INCLUDED THAT SHOWS | | | HOW THE UNDERGROUND POWER IS BEING PROVIDED TO THE | | | POLE. THE UNDERGROUND POWER PATH, INCLUDING ANY BORE | | | PITS AND HANDHOLES ARE REQUIRED TO BE SHOWN ON THE | | | WIRELESS COMMUNICATION FACILITY ROW PERMIT APPLICATION. | | | REMEMBER, THE POWER PATH MAY NOT DISTURB THE STRUCTURAL | | | SOIL SYSTEM. | | | | | | 10) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED | | | SURVEYOR, SHOWING THE RIGHT-OF-WAY LINE AND THE EDGE OF | | | THE SIDEWALK, WITH DIMENSIONS FOR THE UNDERGROUND POWER | | | ROUTE SO THAT STAFF CAN VERIFY THAT IT IS WITHIN A | | | RIGHT-OR-WAY AND DOES NOT CONFLICT WITH ANY UNDERGROUND | | | FACILITIES, INCLUDING LANDSCAPE ROOT AREAS. | | | | | | 11) THE ENGINEERING PLAN (UTILITY POWER PLAN) NEEDS TO | | | SHOW THE RIGHT-OF-WAY LINE (BASED ON THE SURVEY) AND | | | CLEARLY DEMONSTRATE THAT THE HANDHOLES, BORE PITS AND | | | UNDERGROUND POWER BORE ARE COMPLETELY LOCATED WITHIN | | | THE RIGHT-OF-WAY AS WELL AS AVOIDING THE STRUCTURAL | | | SOIL SYSTEM. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-01-14 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2021-01-14 |
Time |
16:01 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2021-01-14 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2021-01-14 16:03:02 | FAILED | | | | | | PROVIDE VERIFICATION THAT THE SITE HAS BEEN ISSUED A | | | COMMUNICATION FACILITY PLACEMENT PERMIT ? CITY | | | RIGHTS-OF-WAY AND A RIGHT-OF-WAY USE PERMIT FOR THE | | | PLACEMENT OF THE POLE WITHIN THE FERN STREET | | | RIGHT-OF-WAY. THE PLANS INCLUDED WITH THIS ELECTRICAL | | | PERMIT MUST MATCH THE PLANS APPROVED WITH THE | | | AFOREMENTIONED PERMITS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | | | | |
|
|