Plan Review Details - Permit 20121295
Plan Review Stops For Permit 20121295
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-01-05 Cont ID  
Sent By cpuell Date 2022-01-05 Time 12:19 Rev Time 0.00
Received By cpuell Date 2022-01-05 Time 12:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2023-01-10 Cont ID  
Sent By rmcphers Date 2023-01-10 Time 11:09 Rev Time 0.00
Received By rmcphers Date 2023-01-10 Time 11:09 Sent To  
Notes
2023-01-10 11:09:48PROPOSED POLE IS IN THE RIGHT OF WAY

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2022-06-27 Cont ID  
Sent By rmcphers Date 2022-06-27 Time 08:41 Rev Time 0.00
Received By rmcphers Date 2022-06-27 Time 08:41 Sent To  
Notes
2022-06-27 08:42:09POLE IS IN THE RIGHT OF WAY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-12-20 Cont ID  
Sent By rmcphers Date 2021-12-20 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2021-12-20 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-04 Cont ID  
Sent By rmcphers Date 2021-05-04 Time 12:36 Rev Time 0.00
Received By rmcphers Date 2021-05-04 Time 12:36 Sent To  
Notes
2021-05-04 12:37:24ANTENNA
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE THE STRUCTURAL DETAILS AND
 CALCULATIONS FROM A DESIGN PROFESSIONAL FOR THE POLE
 AND MOUNTED ANTENNA SHOWING FOUNDATION AND ATTACHMENTS
 TO COMPLY WITH THE WIND LOADS PER FBC 1609

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By rmcphers Date 2021-01-28 Time 14:55 Rev Time 0.00
Received By rmcphers Date 2021-01-28 Time 14:53 Sent To  
Notes
2021-01-28 14:55:20ANTENNA POLE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE POLE DETAILS TO COMPLY WITH THE WIND
 LOADS PER FBC 1609 OR STATE ON THE PLANS THAT POLE IS
 TO BE UNDER A SEPARATE PERMIT.
 2) CODE IN EFFECT HAS CHANGED ON 1/1/21 - PLEASE REVISE
 THE DRAWINGS TO REFLECT THE DESIGN TO BE BASED ON THE
 2020 FBC
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2023-01-12 Cont ID  
Sent By mpeterso Date 2023-01-12 Time 16:35 Rev Time 0.00
Received By mpeterso Date 2023-01-12 Time 16:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-07-01 Cont ID  
Sent By mpeterso Date 2022-07-01 Time 10:14 Rev Time 0.00
Received By mpeterso Date 2022-07-01 Time 10:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-12-21 Cont ID  
Sent By mpeterso Date 2021-12-21 Time 13:12 Rev Time 0.00
Received By mpeterso Date 2021-12-21 Time 13:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-27 Cont ID  
Sent By equinone Date 2021-04-27 Time 11:03 Rev Time 0.00
Received By equinone Date 2021-04-27 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-25 Cont ID  
Sent By equinone Date 2021-01-25 Time 09:37 Rev Time 0.00
Received By equinone Date 2021-01-25 Time 09:33 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2022-01-04 Cont ID  
Sent By eschneid Date 2022-01-04 Time 09:41 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2022-01-04 09:41:35REVIEWED AS PART OF WCF ROW PERMIT

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-07-01 Cont ID  
Sent By gpatrie Date 2021-07-01 Time 09:57 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-07-01 09:57:06PULLBOX LAT/LONG REQUIRED.
 REF #19021027
  
 CONTACT: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-03-14 Cont ID  
Sent By lmarchan Date 2023-03-14 Time 15:57 Rev Time 0.00
Received By lmarchan Date 2023-01-06 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-29 Cont ID  
Sent By lmarchan Date 2022-08-29 Time 10:55 Rev Time 0.00
Received By lmarchan Date 2022-06-16 Time 13:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-05 Cont ID  
Sent By cpuell Date 2022-01-05 Time 12:20 Rev Time 0.00
Received By cpuell Date 2021-12-09 Time 07:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-02 Cont ID  
Sent By lmarchan Date 2021-07-02 Time 11:01 Rev Time 0.00
Received By lcrespo Date 2021-04-20 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-28 Cont ID  
Sent By rmcphers Date 2021-01-28 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2021-01-12 Time 08:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-01-12 Cont ID  
Sent By mpeterso Date 2023-01-12 Time 16:36 Rev Time 0.00
Received By mpeterso Date 2023-01-12 Time 16:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-01 Cont ID  
Sent By mpeterso Date 2022-07-01 Time 10:14 Rev Time 0.00
Received By mpeterso Date 2022-07-01 Time 10:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-12-20 Cont ID  
Sent By rmcphers Date 2021-12-20 Time 09:11 Rev Time 0.00
Received By rmcphers Date 2021-12-20 Time 09:11 Sent To  
Notes
2021-12-20 09:17:41SIGNATURE REVIEW
  
 DRAWINGS BELOW AS LABELED IN PROJECTDOX DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 006 E5 - UTILITY ROUTING-GROUNDING PLAN.PDF
 013 B1 SURVEY.PDF
 RAYCAP_POLE DESIGN_24-FOOT POLE-09-28-2021.PDF
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-04 Cont ID  
Sent By rmcphers Date 2021-05-04 Time 12:40 Rev Time 0.00
Received By rmcphers Date 2021-05-04 Time 12:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By rmcphers Date 2021-01-28 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2021-01-28 Time 14:57 Sent To  
Notes
2021-01-28 14:57:30SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 5 Status P Date 2023-03-14 Cont ID  
Sent By eschneid Date 2023-03-14 Time 14:48 Rev Time 0.25
Received By eschneid Date 2023-02-01 Time 13:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2022-08-29 Cont ID  
Sent By eschneid Date 2022-08-29 Time 10:37 Rev Time 0.25
Received By eschneid Date 2022-08-29 Time 10:37 Sent To  
Notes
2022-08-29 10:42:37FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY (19021027) MUST BE APPROVED
 PRIOR TO THIS PERMIT BEING APPROVED. NOTE: THIS PERMIT
 MEETS ZONING REQUIREMENTS.
  
 2) THE POLE HEIGHT AND STEALTH DESIGN MEET CITY
 STANDARDS. THE POLE COLOR AT THIS LOCATION SHALL BE
 RAL/RAYCAP 7022 UMBRA GREY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-01-04 Cont ID  
Sent By eschneid Date 2022-01-04 Time 17:06 Rev Time 0.25
Received By eschneid Date 2022-01-04 Time 15:57 Sent To  
Notes
2022-01-04 17:11:48FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH
 THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED
 WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS
 BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS
 WELL AS WITH THIS PERMIT.
  
 2) THE POLE HEIGHT AND STEALTH DESIGN MEET CITY
 STANDARDS. THE POLE COLOR IS TO MATCH THE EXISTING
 DECORATIVE CITY LIGHT POLES (SPECKLED BLACK) LOCATED
 ALONG FERN STREET.
  
 3) REPEAT COMMENT: THE PLANTERS THAT ARE SHOWN ON THE
 SURVEY AND ENGINEERING PLANS ARE SURROUNDED BY A
 STRUCTURAL SOIL SYSTEM THAT IS NOT PERMITTED TO BE
 DISTURBED BY THE INSTALLATION OF THE PROPOSED POLE,
 GROUND RODS, FIBER/POWER PULL BOX AND UNDERGROUND
 ELECTRIC, SO THE CURRENT LOCATION IS NOT APPROVED. THE
 FULL AREA COVERED BY THE STRUCTURAL SOIL UNDER THE
 SIDEWALK IS A MINIMUM OF 19 FEET EAST TO WEST AND THE
 FULL DEPTH OF THE SIDEWALK FROM THE CURB TO THE EDGE OF
 THE RIGHT-OF-WAY LINE. NO EXCAVATION OR INSTALLATION
 MAY OCCUR CLOSER THAN SEVEN (7) FEET FROM A PARALLEL
 LINE WITH THE OUTER EDGES OF THE PLANTER WALLS, FROM
 THE CURB FACE TO THE RIGHT-OF-WAY LINE.
  
 3) THE STAFF HAS MARKED THE SURVEY WITH TWO GREEN
 LINES, THAT ARE APPROXIMATELY 10 FEET APART WHERE YOU
 MAY INSTALL THE POLE, PULL BOX, GROUND RODS, ETC.. THIS
 FINAL LAYOUT IN THIS AREA MUST BE PROVIDED ON A BLOW UP
 INSET WITH DIMENSIONS.
  
 4) THE POLE NEEDS TO BE PUSHED AS CLOSE TO THE CURB AS
 POSSIBLE GIVEN THE OVERHEAD WIRE IN ORDER TO MAINTAIN
 AS MUCH OF A STREET FURNITURE RHYTHM AS POSSIBLE AND TO
 MAINTAIN A UNIFORM SIDEWALK WIDTH BEHIND THE PLANTERS.
  
 5) THANK YOU FOR PROVIDING THE UTILITY POWER PLAN. THE
 POWER PATH IS SHOWN DISTURBING THE STRUCTURAL SOIL
 SYSTEM, WHICH IS NOT PERMITTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-05-26 Cont ID  
Sent By eschneid Date 2021-05-26 Time 16:31 Rev Time 0.25
Received By eschneid Date 2021-05-26 Time 15:26 Sent To  
Notes
2021-05-26 16:33:17FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH
 THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED
 WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS
 BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS
 WELL AS WITH THIS PERMIT.
  
 2) SHEET T1 LISTS THE SCOPE OF WORK INCLUDES THE
 INSTALLATION OF AN ENCLOSURE CABINET. NONE OF THE PLANS
 SHOW AN ENCLOSURE CABINET. PLEASE CLARIFY WHAT THIS
 MEANS. THE CITY DOES NOT PERMIT FREESTANDING OR POLE
 MOUNTED CABINETS.
  
 3) THE POLE HEIGHT AND STEALTH DESIGN MEET CITY
 STANDARDS. THE POLE COLOR IS TO MATCH THE EXISTING
 DECORATIVE CITY LIGHT POLES (SPECKLED BLACK) LOCATED
 ALONG FERN STREET.
  
 3) THE PLANTERS THAT ARE SHOWN ON THE SURVEY AND
 ENGINEERING PLANS ARE SURROUNDED BY A STRUCTURAL SOIL
 SYSTEM THAT IS NOT PERMITTED TO BE DISTURBED BY THE
 INSTALLATION OF THE PROPOSED POLE, GROUND RODS,
 FIBER/POWER PULL BOX AND UNDERGROUND ELECTRIC, SO THE
 CURRENT LOCATION IS NOT APPROVED. THE FULL AREA COVERED
 BY THE STRUCTURAL SOIL UNDER THE SIDEWALK IS A MINIMUM
 OF 19 FEET EAST TO WEST AND THE FULL DEPTH OF THE
 SIDEWALK FROM THE CURB TO THE EDGE OF THE RIGHT-OF-WAY
 LINE. NO EXCAVATION OR INSTALLATION MAY OCCUR CLOSER
 THAN SEVEN (7) FEET FROM A PARALLEL LINE WITH THE OUTER
 EDGES OF THE PLANTER WALLS, FROM THE CURB FACE TO THE
 RIGHT-OF-WAY LINE.
  
 5) THERE ARE APPROXIMATELY 10 FEET BETWEEN THE PARALLEL
 LINES MENTIONED IN THE PREVIOUS COMMENT, WHICH PROVIDES
 ADEQUATE ROOM TO INSTALL THE POLE AND THE PULL BOX;
 HOWEVER, STAFF DOES NOT KNOW WHAT THE GROUND ROD
 REQUIREMENTS ARE AND IF THERE IS AN ABILITY TO FIT THEM
 INTO THE AREA AS WELL (IT APPEARS CLOSE WITH THE
 CONFIGURATION AS SHOWN). THIS FINAL LAYOUT IN THIS AREA
 MUST BE PROVIDED ON A BLOW UP INSET WITH DIMENSIONS.
  
 6) STAFF CAN PROVIDE THE ENGINEERING DRAWINGS SHOWING A
 DETAIL FOR THE BIOSWALE PIT WITH THE SURROUNDING
 STRUCTURAL SOIL IF YOU NEED IT.
  
 7) THE STEALTH POLE SHOWN ON SHEET C3, ELEVATION AND
 EQUIPMENT PLAN, HAS A 14-INCH DIAMETER. SCALING THE
 POLE ON THE SURVEY AND SITE PLAN SHOW A SEVEN (7) INCH
 DIAMETER POLE. THE SURVEY AND SITE PLAN NEED TO SHOW
 THE CORRECT POLE SIZE AND DIMENSIONS FROM THE VARIOUS
 FEATURES SHOWN.
  
 8) THE POLE NEEDS TO BE PUSHED AS CLOSE TO THE CURB AS
 POSSIBLE GIVEN THE OVERHEAD WIRE IN ORDER TO MAINTAIN
 AS MUCH OF A STREET FURNITURE RHYTHM AS POSSIBLE AND TO
 MAINTAIN A UNIFORM SIDEWALK WIDTH BEHIND THE PLANTERS.
  
 9) THE UTILITY POWER PLAN WAS NOT INCLUDED THAT SHOWS
 HOW THE UNDERGROUND POWER IS BEING PROVIDED TO THE
 POLE. THE UNDERGROUND POWER PATH, INCLUDING ANY BORE
 PITS AND HANDHOLES ARE REQUIRED TO BE SHOWN ON THE
 WIRELESS COMMUNICATION FACILITY ROW PERMIT APPLICATION.
 REMEMBER, THE POWER PATH MAY NOT DISTURB THE STRUCTURAL
 SOIL SYSTEM.
  
 10) PROVIDE A SURVEY, PREPARED BY A FLORIDA LICENSED
 SURVEYOR, SHOWING THE RIGHT-OF-WAY LINE AND THE EDGE OF
 THE SIDEWALK, WITH DIMENSIONS FOR THE UNDERGROUND POWER
 ROUTE SO THAT STAFF CAN VERIFY THAT IT IS WITHIN A
 RIGHT-OR-WAY AND DOES NOT CONFLICT WITH ANY UNDERGROUND
 FACILITIES, INCLUDING LANDSCAPE ROOT AREAS.
  
 11) THE ENGINEERING PLAN (UTILITY POWER PLAN) NEEDS TO
 SHOW THE RIGHT-OF-WAY LINE (BASED ON THE SURVEY) AND
 CLEARLY DEMONSTRATE THAT THE HANDHOLES, BORE PITS AND
 UNDERGROUND POWER BORE ARE COMPLETELY LOCATED WITHIN
 THE RIGHT-OF-WAY AS WELL AS AVOIDING THE STRUCTURAL
 SOIL SYSTEM.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-14 Cont ID  
Sent By eschneid Date 2021-01-14 Time 16:01 Rev Time 0.25
Received By eschneid Date 2021-01-14 Time 15:53 Sent To  
Notes
2021-01-14 16:03:02FAILED
  
 PROVIDE VERIFICATION THAT THE SITE HAS BEEN ISSUED A
 COMMUNICATION FACILITY PLACEMENT PERMIT ? CITY
 RIGHTS-OF-WAY AND A RIGHT-OF-WAY USE PERMIT FOR THE
 PLACEMENT OF THE POLE WITHIN THE FERN STREET
 RIGHT-OF-WAY. THE PLANS INCLUDED WITH THIS ELECTRICAL
 PERMIT MUST MATCH THE PLANS APPROVED WITH THE
 AFOREMENTIONED PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  