Plan Review Details - Permit 20121294
Plan Review Stops For Permit 20121294
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-01-05 Cont ID  
Sent By cpuell Date 2022-01-05 Time 11:50 Rev Time 0.00
Received By cpuell Date 2022-01-05 Time 11:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2021-12-09 Cont ID  
Sent By rmcphers Date 2021-12-09 Time 07:56 Rev Time 0.00
Received By rmcphers Date 2021-12-09 Time 07:56 Sent To  
Notes
2021-12-09 07:56:51PROPOSED POLE TO BE A SEPARATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2021-06-17 Cont ID  
Sent By rmcphers Date 2021-06-17 Time 13:18 Rev Time 0.00
Received By rmcphers Date 2021-06-17 Time 13:18 Sent To  
Notes
2021-06-17 13:18:55PROPOSED POLE IS SAID TO BE IN THE RW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-13 Cont ID  
Sent By rmcphers Date 2021-04-13 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2021-04-13 Time 14:04 Sent To  
Notes
2021-04-13 14:05:14ANTENNA POLE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE POLE DETAILS TO COMPLY WITH THE WIND
 LOADS PER FBC 1609 OR STATE ON THE PLANS THAT POLE IS
 TO BE UNDER A SEPARATE PERMIT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By rmcphers Date 2021-01-28 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2021-01-28 Time 14:42 Sent To  
Notes
2021-01-28 14:47:53ANTENNA POLE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE POLE DETAILS TO COMPLY WITH THE WIND
 LOADS PER FBC 1609 OR STATE ON THE PLANS THAT POLE IS
 TO BE UNDER A SEPARATE PERMIT.
 2) CODE IN EFFECT HAS CHANGED ON 1/1/21 - PLEASE REVISE
 THE DRAWINGS TO REFLECT THE DESIGN TO BE BASED ON THE
 2020 FBC
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 15:42 Rev Time 0.00
Received By jleahy Date 2022-09-29 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-02-22 Cont ID  
Sent By mpeterso Date 2022-02-22 Time 16:40 Rev Time 0.00
Received By mpeterso Date 2022-02-22 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-12-22 Cont ID  
Sent By mpeterso Date 2021-12-22 Time 10:12 Rev Time 0.00
Received By mpeterso Date 2021-12-22 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-15 Cont ID  
Sent By equinone Date 2021-04-15 Time 14:14 Rev Time 0.00
Received By equinone Date 2021-04-15 Time 14:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-25 Cont ID  
Sent By equinone Date 2021-01-25 Time 09:27 Rev Time 0.00
Received By equinone Date 2021-01-25 Time 09:27 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2021-06-16 Cont ID  
Sent By gpatrie Date 2021-06-11 Time 07:30 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-06-11 07:30:401.SEE 19020382.
  
  
 CONTACT: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By aoliver Date 2022-10-04 Time 07:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 16:23 Rev Time 0.00
Received By jleahy Date 2022-09-06 Time 13:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-03-22 Cont ID  
Sent By cthroop Date 2022-03-22 Time 13:50 Rev Time 0.00
Received By cthroop Date 2022-02-06 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-05 Cont ID  
Sent By cpuell Date 2022-01-05 Time 11:50 Rev Time 0.00
Received By cpuell Date 2021-12-01 Time 06:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-14 Cont ID  
Sent By rmcdouga Date 2021-06-14 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2021-04-08 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-28 Cont ID  
Sent By rmcphers Date 2021-01-28 Time 14:49 Rev Time 0.00
Received By rmcphers Date 2021-01-12 Time 08:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-09-29 Cont ID  
Sent By jleahy Date 2022-09-29 Time 15:43 Rev Time 0.00
Received By jleahy Date 2022-09-29 Time 15:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-03-22 Cont ID  
Sent By cthroop Date 2022-03-22 Time 13:50 Rev Time 0.00
Received By cthroop Date 2022-03-22 Time 13:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-12-09 Cont ID  
Sent By rmcphers Date 2021-12-09 Time 08:00 Rev Time 0.00
Received By rmcphers Date 2021-12-09 Time 08:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-13 Cont ID  
Sent By rmcphers Date 2021-04-13 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2021-04-13 Time 14:07 Sent To  
Notes
2021-04-13 14:09:54DRAWINGS LOADED TO PROJECTDOX ON 12/29/2020 = SIGNED
 AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By rmcphers Date 2021-01-28 Time 14:49 Rev Time 0.00
Received By rmcphers Date 2021-01-28 Time 14:48 Sent To  
Notes
2021-01-28 14:49:30SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ckimmerl Date 2022-10-14 Time 15:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date 2022-09-29 Cont ID  
Sent By ckimmerl Date 2022-09-29 Time 16:16 Rev Time 0.00
Received By ckimmerl Date 2022-09-29 Time 16:16 Sent To  
Notes
2022-09-29 16:16:34PERMIT 20121294 - UG POWER - 223 @ FERN ST.
 1. THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH
 THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED
 WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS
 BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS
 WELL AS WITH THIS PERMIT.
  
  
 PERMIT 19020382 - POLE - 223 @ FERN ST.
 1. PLEASE PROVIDE SURVEY FOR ENTIRE SCOPE OF PROJECT,
 INCLUDING THE POWER ROUTE. STAFF WOULD LIKE TO VERIFY
 THAT ALL PROPOSED WORK AND CONNECTIONS ARE WITHIN THE
 RIGHT-OF-WAY.
  
 2. PROPOSED POLE LOCATIONS OR BORE PITS SHOWN TO
 POTENTIALLY CONFLICT WITH EXISTING PRIVATE
 COMMUNICATIONS LINE, PLEASE PROVIDE THE NECESSARY
 UTILITY LETTERS GRANTING APPROVAL/NO OBJECTION OF THIS
 POLE LOCATION AND DEPTH, IF NO RESPONSE CAN BE OBTAINED
 FROM UTILITY PROVIDER, PLEASE PROVIDE PROOF OF
 COMMUNICATION AND A LETTER OF NO RESPONSE.
  
 3. PLEASE PROVIDE PROOF THAT ADA CLEARANCE IS NOT
 IMPEDED IN THE SPACE BETWEEN BACK OF CURB AND THE FACE
 OF THE POLE, MUST MAINTAIN AT LEAST 36??? OF CLEARANCE.
  
 4. PLEASE BE SURE THAT SITE PLAN PROVIDES FULL SCOPE OF
 WORK.
  
 5. THE POLE STEALTH DESIGN AND COLOR MEETS CITY
 STANDARDS.
  
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 (561)822-1426 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date 2022-03-21 Cont ID  
Sent By eschneid Date 2022-03-21 Time 16:27 Rev Time 0.25
Received By eschneid Date 2022-03-21 Time 16:26 Sent To  
Notes
2022-03-21 16:28:27FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH
 THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED
 WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS
 BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS
 WELL AS WITH THIS PERMIT.
  
 2) UPDATED COMMENT: THE POWER ROUTE PLAN SHEET P-1
 STATES THAT FPL WILL MAKE THE ELECTRICAL WIRE TAP FROM
 AN EXISTING POLE TO A PROPOSED HANDHOLE; HOWEVER, SHEET
 P-2 STATES THAT IT WILL COME FROM AN EXISTING
 TRANSFORMER. IF IT IS NOT FROM THE TRANSFORMER, YOU
 MUST SHOW WHICH POLE IS BEING USED SO THAT STAFF CAN
 VERIFY IMPACTS. IF YOU ARE USING THE TRANSFORMER, YOU
 MUST PROVIDE VERIFICATION THAT THERE IS A UTILITY
 EASEMENT THAT ALLOWS POWER SUPPLYING YOUR FACILITY TO
 CROSS CITY OWNED PROPERTY. IF THERE IS NO EASEMENT,
 POWER TO SUPPLY YOUR FACILITY MAY NOT CROSS CITY OWNED
 PROPERTY. THE BEST METHOD IS ON A SURVEY; HOWEVER,
 RECORDED DOCUMENTATION THAT CLEARLY IDENTIFIES THIS
 LOCATION IS ALSO ACCEPTABLE. NOTE: FPL STATING THEY
 HAVE AN EASEMENT, DOES NOT VERIFY THAT THEY HAVE AN
 EASEMENT. IF NO EASEMENT IS PRESENT THE UNDERGROUND
 ELECTRIC MUST COME FROM AN ALTERNATIVE LOCATION.
  
 3) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, SIDEWALK
 AND LANDSCAPE AREAS WILL NEED RESTORATION. PLEASE
 UPDATE THE NOTATIONS ACCORDINGLY.
  
 4) THE EASTERNMOST BORE PIT APPEARS TO CROSS THE
 RIGHT-OF-WAY LINE ONTO CITY PROPERTY, WHICH IS NOT
 PERMITTED. ALL WORK IS TO REMAIN IN THE RIGHT-OF-WAY
 UNLESS THERE IS A UTILITY EASEMENT PRESENT AND SHOWN ON
 THE SURVEY. THIS GOES FOR ALL THE INSTALLATIONS THAT
 ARE IMMEDIATELY ADJACENT TO THE RIGHT-OF-WAY LINE.
  
 5) REPEAT COMMENT: THE PLANS SHOW THE GAS LINE WITHIN
 2-FEET OF THE CAISSON AND THROUGH THE MAJORITY OF YOUR
 BORE PITS. IN ORDER TO VERIFY THAT THE INSTALLATION
 WILL NOT INTERFERE WITH THE EXISTING FACILITIES,
 PROVIDE A PUBLIC UTILITY LETTER OF NO OBJECTION FROM
 FPU REGARDING THE INSTALLATION.
  
 6) THIS POLE LOCATION IS APPROVED BY SPECIAL EVENTS.
  
 7) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7022 UMBRA GREY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-01-04 Cont ID  
Sent By eschneid Date 2022-01-04 Time 18:10 Rev Time 0.25
Received By eschneid Date 2022-01-04 Time 17:13 Sent To  
Notes
2022-01-04 18:11:21FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. THE PLANS INCLUDED WITH
 THIS ELECTRICAL PERMIT MUST MATCH THE PLANS APPROVED
 WITH THE AFOREMENTIONED PERMIT. SOME OF THE COMMENTS
 BELOW ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS
 WELL AS WITH THIS PERMIT.
  
 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR IS TO MATCH THE EXISTING DECORATIVE CITY
 LIGHT POLES (SPECKLED BLACK) LOCATED ALONG FERN STREET.
  
 3) THIS POLE LOCATION IS APPROVED BY SPECIAL EVENTS.
  
 4) THE PLANS SHOW THE GAS LINE WITHIN 2-FEET OF THE
 CAISSON AND THROUGH THE MAJORITY OF YOUR BORE PITS. IN
 ORDER TO VERIFY THAT THE INSTALLATION WILL NOT
 INTERFERE WITH THE EXISTING FACILITIES, PROVIDE A
 PUBLIC UTILITY LETTER OF NO OBJECTION FROM FPU
 REGARDING THE INSTALLATION.
  
 5) THANK YOU FOR PROVIDING THE UTILITY POWER PLAN,
 INCLUDING A PARTIAL SURVEY; HOWEVER, THE SURVEY NEEDS
 TO SHOW THE FULL LENGTH OF THE UNDERGROUND POWER RUN SO
 THAT STAFF CAN VERIFY THAT THE UNDERGROUND ELECTRIC IS
 FULLY WITHIN THE RIGHT-OF-WAY.
  
 6) THE SUBMITTED PLANS SHOW THE UNDERGROUND ELECTRIC
 BEING SUPPLIED FROM AN FPL TRANSFORMER THAT IS LOCATED
 ON CITY PROPERTY ON THE EAST SIDE OF EVERNIA STREET.
 THE SURVEY NEEDS TO SHOW THAT THE AREA WHERE YOU PLAN
 TO PULL POWER FROM ACROSS CITY PROPERTY IS LOCATED
 WITHIN A UTILITY EASEMENT. IF NO EASEMENT IS PRESENT,
 YOU WILL NEED TO GET THE POWER FROM AN ALTERNATIVE
 LOCATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-05-11 Cont ID  
Sent By eschneid Date 2021-05-11 Time 16:46 Rev Time 0.25
Received By eschneid Date 2021-05-11 Time 16:46 Sent To  
Notes
2021-05-11 16:48:01FAILED
  
 1) THIS POLE LOCATION IS NOT APPROVED BY SPECIAL
 EVENTS. YOU MUST DISCUSS AN ALTERNATIVE LOCATION WITH
 THEM.
  
 2) PROVIDE VERIFICATION THAT THE SITE HAS BEEN ISSUED A
 COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY AND A RIGHT-OF-WAY USE PERMIT FOR THE
 PLACEMENT OF THE POLE WITHIN THE FERN STREET
 RIGHT-OF-WAY. THE PLANS INCLUDED WITH THIS ELECTRICAL
 PERMIT MUST MATCH THE PLANS APPROVED WITH THE
 AFOREMENTIONED PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-14 Cont ID  
Sent By ckimmerl Date 2021-01-14 Time 15:44 Rev Time 0.25
Received By eschneid Date 2021-01-14 Time 15:44 Sent To  
Notes
2021-01-14 15:45:13FAILED
  
 PROVIDE VERIFICATION THAT THE SITE HAS BEEN ISSUED A
 COMMUNICATION FACILITY PLACEMENT PERMIT ? CITY
 RIGHTS-OF-WAY AND A RIGHT-OF-WAY USE PERMIT FOR THE
 PLACEMENT OF THE POLE WITHIN THE FERN STREET
 RIGHT-OF-WAY. THE PLANS INCLUDED WITH THIS ELECTRICAL
 PERMIT MUST MATCH THE PLANS APPROVED WITH THE
 AFOREMENTIONED PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  