Plan Review Details - Permit 20121276
Plan Review Stops For Permit 20121276
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-04-13 Cont ID  
Sent By jwitmer Date 2021-04-13 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2021-04-13 Time 15:45 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-03-24 Cont ID  
Sent By jwitmer Date 2021-03-24 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2021-03-24 Time 11:02 Sent To  
Notes
2021-03-24 11:45:26COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-20 Cont ID  
Sent By jwitmer Date 2021-02-20 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2021-02-20 Time 09:27 Sent To  
Notes
2021-02-20 11:51:39COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-13 Cont ID  
Sent By jwitmer Date 2021-04-13 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2021-04-13 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-24 Cont ID  
Sent By jwitmer Date 2021-03-24 Time 11:44 Rev Time 0.00
Received By jwitmer Date 2021-03-24 Time 11:02 Sent To  
Notes
2021-03-24 11:43:56WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20121276 APPLY DATE 12/29/2020 2017
 FBC-B
 ADD: 439 NORTHWOOD RD.
 CONT: HORMAK CONSTRUCTION & ROOFING
 TEL: 561-635-9837
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 24TH/ 2021
 ACTION: DENIED
  
 1A) COMPLIED.
  
 1B) 2ND REQUEST. WITH THE PLANS SHOWING A NEW OCCUPANCY
 CLASSIFICATION, (BUSINESS) AND USAGE SMALL ASSEMBLY
 LESS THAN 50 OCCUPANTS THE AMOUNT OF WORK (LABOR &
 MATERIALS) THE DOLLAR AMOUNT STATED $25,500.00 DOLLARS
 IN VALUE IS LOW.
 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, CANOPIES, ALL LOW VOLTAGE PERMITS, GENERATORS
 & FUEL TANKS WITH FILL STATIONS, GAS PERMIT, POOL,
 JACUZZI AND ASSOCIATED SUB-PERMITS, AWNING, SCREEN
 ENCLOSURES, CANOPY, FENCE, LANDSCAPE, IRRIGATION, AUGER
 CAST PILE AND OR FOUNDATION OR STRUCTURE ONLY PERMIT
 WILL BE SEPARATE REVIEWS AND ASSOCIATED FEES WITH EACH
 PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 1C-G) COMPLIED.
  
 2-3) COMPLIED
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-20 Cont ID  
Sent By jwitmer Date 2021-02-20 Time 12:00 Rev Time 0.00
Received By jwitmer Date 2021-02-20 Time 09:27 Sent To  
Notes
2021-02-20 11:59:52WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20121276 APPLY DATE 12/29/2020 2017
 FBC-B
 ADD: 439 NORTHWOOD RD.
 CONT: INFINITY CONSTRUCTION AND HANDYMAN
 TEL: 561-856-5941
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. FEB. 20TH/ 2021
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION FOR PERMIT 20121276 436
 NORTHWOOD RD. STATES THE WORK TO BE PREFORMED UNDER
 THIS PERMIT IS REMODELING EXISTING RESTROOMS TO ADA
 STANDARDS. THE SCOPE OF WORK INDICATED ON THE
 COVERSHEET OF THE PLANS INDICATES THIS IS A CHANGE OF
 OCCUPANCY FROM A MERCANTILE OCCUPANCY (ELITE SKIN &
 BEAUTY COSMETICS, BEAUTY SUPPLIES & PERFUMES) TO A
 BUSINESS OCCUPANCY, RESTAURANT LESS THAN 50 OCCUPANTS.
 VALUE OF THE PROJECT $25,500.00 DOLLARS IN VALUE.
  
 1A) THERE IS A DISCREPANCY IN THE SCOPE OF WORK BETWEEN
 THE CONTRACTOR AND DESIGNER OF RECORD. PLEASE CORRELATE
 THE SCOPE OF WORK. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. THE COVERSHEET LIST THE LEVEL OF CONSTRUCTION
 AS LEVEL III. PLEASE NOTE THIS BUILDING IS UNDERGOING A
 CHANGE OF OCCUPANCY MERCANTILE TO BUSINESS AND NEEDS TO
 FOLLOW THE CHANGE OF OCCUPANCY REQUIREMENTS LISTED IN
 THE 2017 EXISTING BUILDING CODE 1001.2.1. SECTIONS 1002
 THROUGH 1011.
  
 1B) WITH THE PLANS SHOWING A NEW OCCUPANCY
 CLASSIFICATION, (BUSINESS) AND USAGE SMALL ASSEMBLY
 LESS THAN 50 OCCUPANTS THE AMOUNT OF WORK (LABOR &
 MATERIALS) THE DOLLAR AMOUNT STATED $25,500.00 DOLLARS
 IN VALUE IS LOW.
 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, CANOPIES, ALL LOW VOLTAGE PERMITS, GENERATORS
 & FUEL TANKS WITH FILL STATIONS, GAS PERMIT, POOL,
 JACUZZI AND ASSOCIATED SUB-PERMITS, AWNING, SCREEN
 ENCLOSURES, CANOPY, FENCE, LANDSCAPE, IRRIGATION, AUGER
 CAST PILE AND OR FOUNDATION OR STRUCTURE ONLY PERMIT
 WILL BE SEPARATE REVIEWS AND ASSOCIATED FEES WITH EACH
 PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 1C) THE TITLEBLOCK INDICATES THE METRO ARCHITECTURAL
 GROUP HAS DESIGNED THE PLANS, BUT THERE IS NO SIGNATURE
 OR SEAL BY EITHER THE ARCHITECT OR ENGINEER.
 ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005.
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (ENGINEER) (DIGITAL
 SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 1D) THERE IS A QUESTION WHEREAS WHERE THE WORK WILL BE
 PERFORMED. THE PLANS (COVERSHEET) INDICATE 439
 NORTHWOOD RD. BUT THE KEY PLAN IDENTIFIES THE BUILDING
 325 NORTHWOOD RD. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1E) THE COVERSHEET STATES THE OCCUPANT LOAD OF 36
 PEOPLE, BUT NO FORMULA AS TO HOW THE DESIGNER OF RECORD
 GOT THIS NUMBER. SHEET A1.2 UNDER OCCUPANCY STATES 12
 PEOPLE USING 100 S. F. AS THE OCCUPANT LOAD FACTOR THEN
 STATES THE PROPOSED OCCUPANCY AS 26 PEOPLE OVERALL.
 PLEASE CORRELATE THE OCCUPANT LOAD MATCHES EVERYWHERE
 WITHIN THE SET OF PLANS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED. 2017 FBC-B TABLE 1004.1.2.
  
 1F) THE COVERSHEET INDICATES THE BUILDING CONSTRUCTION
 TYPE AS IIIB- UN-SPRINKLERED. THE PLANS ARE SILENT AS
 TO THE 2-HR. RATED EXTERIOR BEARING WALLS IN ACCORDANCE
 WITH THE 2017 FBC-B TABLE 602.
  
 1G) THE COVERSHEET DOES NOT LIST THE LENGTH OF THE
 BUILDING NOR IS THE LENGTH OF THE BUILDING GIVEN ON THE
 LIFE SAFETY SHEET. WITHOUT THE ACTUAL OCCUPANT LOAD
 COUNT KNOWN AND THE LENGTH OF THE BUILDING KNOWN OR
 STATED IN EITHER THE COVERSHEET AND OR LIFE SAFETY
 SHEET COMPLIANCE WITH HOW MANY EXITS OR EXIT ACCESS
 DOORWAYS AND COMPLIANCE WITH SECTION/ TABLE 1006.2.1.
 (2017 FBC-B) MAXIMUM PATH OF EGRESS TRAVEL CANNOT BE
 DETERMINED.
  
 2) SHEET A-1.0 FLOOR PLAN:
 2A) AT THE BACK OF THE TENANT SPACE THERE IS A
 STATEMENT SERVICE ENTRANCE BUT DOES NOT DECLARE WHERE
 THE SERVICE ENTRANCE IS LOCATED. 107 .2.1.2 ADDITIONAL
 INFORMATION, 1006.2.1 OF THE 2017 FBC-B.
  
 2B) PLEASE PROVIDE EITHER A SURVEY OR SITE PLAN SHOWING
 THE FRONT AND REAR PROPERTY LINES. BOTH OF THE EXIT/
 ENTRANCE DOORS ARE OUTSWING DOORS AND CAN NOT CROSS
 OVER THE PROPERTY LINE. 2017 FBC-B SECTION 3202.2.
  
 2C) THE SUBMITTED FLOOR PLAN SHOWS 2 EGRESS DOORS BUT
 DOES NOT GIVE THE INTERIOR FLOOR FINISH HEIGHT IN
 RELATION TO THE EXTERIOR SLAB OR FINISH GRADE. 2017
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION). 2003 IBC-B 1007.1 WHERE
 MORE THAN ONE MEANS OF EGRESS IS REQUIRED BY SECTIONS
 1014.1 OR 1018.1 FROM ANY ACCESSIBLE SPACE, EACH
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO MEANS OF EGRESS. ACCESS. CODE 404.2.5.
 THRESHOLDS. THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL
 BE ? INCH HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES
 IN LEVEL AT DOORWAYS SHALL COMPLY WITH 302 & 303.
  
 2D) THE FLOOR PLAN NOR THE LIFE SAFETY PLAN SHOW
 DIMENSIONS FOR THE 2 ACCESSIBLE RESTROOMS COMPLIANCE
 WITH CLEARANCES AT WATER CLOSETS CANNOT BE DETERMINED.
 . 604.3 CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS
 AND IN TOILET COMPARTMENTS SHALL COMPLY WITH 604.3.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE
 7-FOOT 1 INCH.
  
 2E) THE SHEET A1.0 NOR THE LIFE SAFETY PLAN SHOW
 COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS FOR:
 2E)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 2E)(2) 226.2 DISPERSION. DINING SURFACES REQUIRED TO
 COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE
 OR FACILITY CONTAINING DINING SURFACES. IS THERE
 OUTDOOR SEASONAL SEATING.
  
 2E)(3) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 2E)(4) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS
  
 2E)(5) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2E)(6) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) SHEET A-4 THE MECHANICAL SHEET HAS A NOTE SEE
 ENGINEERED HOOD DRAWING UNDER SEPARATE PERMIT. PLEASE
 ADD NOTES ON THE ARCHITECTURAL SHEETS THAT THE FRAMING
 FOR THE PROPOSED HOOD WILL BE UNDER THE HOOD PERMIT AS
 WELL AS THE ATTACHMENT OF THE HOOD TO THE ROOF FRAMING
 MEMBERS. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By equinone Date 2021-03-25 Time 14:27 Rev Time 0.00
Received By equinone Date 2021-03-25 Time 14:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By equinone Date 2021-02-12 Time 15:02 Rev Time 0.00
Received By equinone Date 2021-02-12 Time 14:28 Sent To  
Notes
2021-02-12 15:10:17CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) PERMIT APPLICATION ONLY MENTIONS IMPROVEMENTS TO
 BATHROOM FOR ADA COMPLIANCE BUT EQUIPMENT SCHEDULE ON
 SHEET A1.0 AND ELECTRICAL POWER DIAGRAM ON A2.0 SEEM TO
 INDICATE OTHER NEW EQUIPMENT IS BEING INSTALLED. PLEASE
 CLARIFY SCOPE AND WORK AND INCLUDE ANY NEW EQUIPMENT ON
 YOUR ELECTRICAL SHEETS. FBC 107
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-22 Cont ID  
Sent By pleduc Date 2021-03-22 Time   Rev Time 0.00
Received By pleduc Date 2021-03-22 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-02-03 Cont ID  
Sent By pleduc Date 2021-02-03 Time   Rev Time 0.00
Received By pleduc Date 2021-02-03 Time 14:28 Sent To  
Notes
2021-02-03 14:54:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEETS A 1.2 & A 1.0 - THERE ARE INDICATIONS THAT
 DOOR # 2 OPEND OUT INTO THE EXIT TRAVEL PATH.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
 2) MECHANICAL SHEETS - THERE ARE INDICATIONS OF A
 GREASE HOOD AND FIRE SUPPRESSION INSTALLATIONS.
  
 THE GREASE HOOD AND FIRE SUPPRESSION INSTALLATIONS
 SHALL BE SUBMITTED UNDER SEPARATE PERMITS AND SHOP
 DRAAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT ON THE PLAN
 SHEET.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By ccole Date 2021-03-25 Time 14:33 Rev Time 0.00
Received By ccole Date 2021-03-25 Time 13:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By ccole Date 2021-02-12 Time 15:03 Rev Time 0.00
Received By ccole Date 2021-02-12 Time 14:07 Sent To  
Notes
2021-02-12 15:04:001ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20121276
 2/12/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.0P: PLEASE UPDATE THE 5TH EDITION FBC- 2014
 REFERENCE BY THE RISER DRAWING- SECTION 107.2.1 WPB.
  
 2) 4.0P: SHOW THE TANKLESS WATER HEATER IN THE RISER-
 SECTION 402.2 FBC FG.
  
 3) 4.0P: SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 AND TOTAL LOAD- SECTIONS 402.2 AND 402.4.1.
  
 4) 4.0P: SHOW REGULATORS AT THE WATER HEATER AND
 APPLIANCES- SECTION 410.1 & 410.2 FBC FG.
  
 5) 4.0P: PROVIDE EQUIPMENT SCHEDULES FOR THE WATER
 HEATER AND COOKING APPLIANCES AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS- SECTIONS 624.1 AND 623.1.
  
 6) 4.0P: CONCERNING THE COMBUSTION AIR CALCULATIONS
 PLEASE REFER TO THE MECHANICAL REVIEW COMMENTS
 REQUESTING REVISED O/A CALCULATIONS IN ORDER TO VERIFY
 COMPLIANCE WILL BE MET- SECTION 304.9.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-04-13 Time 16:13 Rev Time 0.00
Received By aoliver Date 2021-04-12 Time 10:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-03-25 Time   Rev Time 0.00
Received By lmarchan Date 2021-03-19 Time 07:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-02-20 Time 12:00 Rev Time 0.00
Received By lmarchan Date 2021-02-01 Time 10:13 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2021-04-13 Cont ID  
Sent By jwitmer Date 2021-04-13 Time 16:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-02-20 Cont ID  
Sent By jwitmer Date 2021-02-20 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2021-02-20 Time 11:49 Sent To  
Notes
2021-02-20 11:50:36IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By medwards Date 2021-03-23 Time 13:59 Rev Time 0.00
Received By medwards Date 2021-03-23 Time 13:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-02-09 Cont ID  
Sent By medwards Date 2021-02-09 Time 11:18 Rev Time 0.00
Received By medwards Date 2021-02-09 Time 11:17 Sent To  
Notes
2021-02-09 11:18:191ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20121276
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR CALCULATIONS BASED ON SECTION
 403.3.1.1 AND TABLE 403.3.1.1 USING THE HEADING (FOOD
 AND BEVERAGE SERVICE) AND THEN (DINING ROOMS). THIS
 SHOULD BE BASED ON THIS TABLE AND NOT THE NUMBER OF
 PEOPLE THE DESIGNER HAS SHOWN. FBC M
  
 2) PLEASE SHOW IN THE OUTDOOR AIR CALCULATIONS, THE
 REQUIRED COMBUSTION AIR CALCULATIONS FOR THE HOOD BASED
 ON SHEET 4.0P. FBC M 508.1.2
  
 3) PLEASE PROVIDE AN AIR BALANCE REPORT. FBC M 508.1.2
  
 4) PLEASE SHOW THE PLACEMENT OF THE KITCHEN EXHAUST AND
 MUA WILL MEET THE PROTECTIONS OF FBC M 304.11 AND 306.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-25 Cont ID  
Sent By ccole Date 2021-03-25 Time 14:33 Rev Time 0.00
Received By ccole Date 2021-03-25 Time 13:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By ccole Date 2021-02-12 Time 15:04 Rev Time 0.00
Received By ccole Date 2021-02-12 Time 11:23 Sent To  
Notes
2021-02-12 15:06:191ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20121276
 2/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C-1: THE PLUMBING FIXTURE CALCULATIONS DO NOT
 INCLUDE THE REQUIRED DRINKING FOUNTAIN FOR BUSINESS
 OCCUPANCIES ACCORDING TO TABLE 403.1 FBC P, AND THE
 PLANS DO NOT SHOW A DRINKING FOUNTAIN TO BE INSTALLED.
 PLEASE SEE SECTION 410.4 FOR ADDITIONAL INFORMATION.
  
 2) 1.0A, 1.2A, 4.0P: PLEASE IDENTIFY THE SINGLE USER
 TOILET ROOMS AS EITHER MALE OR FEMALE- SEE SECTION
 403.2(4) FBC P.
  
 3) 1.0A: PLEASE PROVIDE WALL AND FLOOR FINISH MATERIAL
 SPECIFICATIONS FOR THE NEW TOILET ROOM- REFER TO
 SECTION 310.3 FBC P, AND SECTIONS 1210.2.2 FBC B.
 PLEASE NOTE THAT PAINTED DRYWALL IS NOT IN COMPLIANCE
 WITH THE CODE SECTIONS.
  
 4) 1.0A: PLEASE PROVIDE THE NEW TOILET ROOM WIDTH AND
 LENGTH DIMENSIONS- SECTION 107.2.1 WPB AND 604.3.2 FBC
 ACC.
  
 5) 1.0A: PROVIDE THE DIAMETER OF THE TURNING CIRCLE-
 SECTIONS 603.2.1 AND 304 FBC ACC.
  
 6) 4.0P: SHOW THE VENT FOR THE MOP SINK IN THE SANITARY
 ISOMETRIC- SECTION 909 FBC P.
  
 7) 4.0P: PROVIDE AN INDIRECT WASTE DETAIL FOR THE MOP
 SINK- SECTION 802.1.1 FBC P.
  
 8) 4.0P: THE PLAN APPEARS TO SHOW VENT SYMBOLS FOR THE
 GREASE INTERCEPTOR, HOWEVER VENTS ARE NOT SHOWN IN THE
 SANITARY RISER. PLEASE REVIEW THE INSTALLATION MANUAL
 FOR THE INTERCEPTOR AND SHOW HOW IT WILL BE VENTED-
 SECTION 1003.3.4 FBC P.
  
 9) 4.0P: PROVIDE A PLUMBING FIXTURE SCHEDULE- SECTIONS
 416, 418, 420, 424, & 427 AND TABLE 604.5 FBC P.
  
 10) 4.0P: THE WATER RISER IS MISLABELED AS SANITARY
 RISER- PLEASE CORRECT- SECTION 107.2.1 WPB.
  
 11) 4.0P: THE HAND SINK IS MISLABELED AS A LAV IN THE
 SANITARY RISER- PLEASE CORRECT- SECTION 107.2.1 WPB.
  
 12) 4.0P: LABEL THE SINK IN THE KITCHEN ON THE RISER
 DRAWINGS. IT APPEARS THAT THE SINK IS BEING SUPPLIED
 WITH COLD WATER BUT NOT HOT WATER AS REQUIRED BY
 SECTION 607.1 FBC P.
  
 13) 4.0P: SHOW THE LOCATIONS WHERE THE MIXING VALVE
 WILL BE INSTALLED- SECTIONS 416.5 AND 607.1.2 FBC P.
  
 14) 4.0P: CORRECT THE HOT AND COLD LINE LABELS AT THE
 EXISTING LAV TO MATCH WITH THE PIPES IN THE RISER
 DRAWING- SECTION 107.2.1 WPB.
  
 15) 4.0P: SHOW LOCATIONS OF WATER HAMMER ARRESTORS AND
 PROVIDE A SPEC- SECTION 604.5 FBC P.
  
 16) 4.0P: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE AND
 SHOW THE HWR LINE IN THE DETAIL- TABLE C404.2 FBC EC
 AND SECTION 607.2.1.2 FBC P. VERIFY THAT THE WATER
 HEATER IS FACTORY EQUIPPED WITH A RECIRCULATION PUMP OR
 SHOW AN INDEPENDENT PUMP IS TO BE INSTALLED- SEE
 SECTION C404.5.1 FBC EC.
  
 17) 4.0P: PROVIDE HOT WATER PIPE INSULATION
 SPECIFICATIONS- SECTION C403.2.10 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-13 Cont ID  
Sent By jwitmer Date 2021-04-13 Time 16:11 Rev Time 0.00
Received By jwitmer Date 2021-04-13 Time 16:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-23 Cont ID  
Sent By medwards Date 2021-03-23 Time 14:02 Rev Time 0.00
Received By medwards Date 2021-03-23 Time 14:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-02-09 Cont ID  
Sent By medwards Date 2021-02-09 Time 11:21 Rev Time 0.00
Received By medwards Date 2021-02-09 Time 11:18 Sent To  
Notes
2021-02-09 11:24:30DIGITALLY SUBMITTED PLANS MUST BE DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER. YOU MAY BRING TO OUR OFFICE
 ORIGINAL SIGNED AND SEALED PAPER DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 61G15?23.004 F.A.C.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL
 HAVE THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY AND SHALL ASSURE THAT THE DIGITAL SIGNATURE
 IS: (A) UNIQUE TO THE PERSON USING IT; (B) CAPABLE OF
 VERIFICATION; AS OF NOVEMBER 16, 2020 63 (C) UNDER THE
 SOLE CONTROL OF THE PERSON USING IT; AND, (D) LINKED TO
 A DOCUMENT IN SUCH A MANNER THAT THE DIGITAL SIGNATURE
 AND CORRESPONDINGLY THE DOCUMENT IS INVALIDATED IF ANY
 DATA IN THE DOCUMENT IS CHANGED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  