Plan Review Details - Permit 20121202
Plan Review Stops For Permit 20121202
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-07-29 Cont ID  
Sent By rmcphers Date 2021-07-29 Time 09:51 Rev Time 0.00
Received By rmcphers Date 2021-07-29 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-05-24 Cont ID  
Sent By rmcphers Date 2021-05-24 Time 16:38 Rev Time 0.00
Received By rmcphers Date 2021-05-24 Time 16:38 Sent To  
Notes
2021-05-24 16:39:29SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED BY PRODUCT APPROVAL NUMBER ON THE DRAWINGS.
 (WINDOW AND DOORS)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-06 Cont ID  
Sent By rmcphers Date 2021-05-06 Time 15:38 Rev Time 0.00
Received By rmcphers Date 2021-05-06 Time 15:38 Sent To  
Notes
2021-05-06 16:16:24SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) IN THE PRODUCT APPROVAL FOR THE ROOFING TILE YOU
 WILL NEED TO CIRCLE THE TILE ATTACHMENT TYPE ON PAGE 5
 OF 6 - TABLE 4, 5 OR 6
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED BY PRODUCT APPROVAL NUMBER ON THE DRAWINGS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By rmcphers Date 2021-01-12 Time 15:04 Rev Time 0.00
Received By rmcphers Date 2021-01-12 Time 13:59 Sent To  
Notes
2021-01-12 15:02:49SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE LOCATION OF THE SMOKE ALARMS PER FBC
 R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 2) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS.
 3) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING SYSTEM. PLEASE CIRCLE
 THE ROOFING ATTACHMENT TO BE USED IN THE ROOFING SYSTEM
 PRODUCT APPROVAL.
 4) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD OR BE
 LISTED BY PRODUCT APPROVAL NUMBER ON THE DRAWINGS.
 5) JOB VALUE AS DETERMINED IN THE ICC VALUATION DATA =
 318 SQ. FT. X $122.46 = $38,942.00 - PLEASE REVISE THE
 BUILDING PERMIT APPLICATION TO SHOW THE CORRECTED JOB
 VALUE FBC WPB 109.3 BUILDING PERMIT VALUATIONS. IF, IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE
 LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL
 CODE CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.
 6) ROOFING AND WINDOW AND DOOR PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-05 Cont ID  
Sent By jleahy Date 2021-05-05 Time 08:33 Rev Time 0.00
Received By jleahy Date 2021-05-03 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By cthroop Date 2021-01-12 Time 08:47 Rev Time 0.00
Received By cthroop Date 2021-01-12 Time 07:29 Sent To  
Notes
2021-01-12 09:02:30PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROVISO ON PLAN SHEET E-1. SMOKE ALARMS SHALL COMPLY
 WITH R314.2.2. CT
  
 1. PLAN SHEET E-1 STATES PANEL P LOCATED ON EAST WALL.
 SHOW LOCATION OF PANEL P ON PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE LOADS SERVED BY PANEL P.
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS
 FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR
 THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
 3. AHU LOCATED IN ATTIC. PROVIDE SERVICE OUTLET AND
 LUMINAIRE.
 AHU IN ATTICS
 M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 39. EXPOSED LAMPS SHALL BE
 PROTECTED FROM DAMAGE BY LOCATION OR LAMP GUARDS.
  
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 4. LIST PANEL BOARD AIC RATING.
 E3706.1PANELBOARD RATING.
 ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THAT
 OF THE MINIMUM SERVICE OR FEEDER CAPACITY REQUIRED FOR
 THE CALCULATED LOAD. (408.30)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-01-12 Cont ID  
Sent By cthroop Date 2021-01-12 Time 08:47 Rev Time 0.00
Received By cthroop Date 2021-01-12 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-29 Cont ID  
Sent By rmcphers Date 2021-07-29 Time 09:53 Rev Time 0.00
Received By rmcphers Date 2021-07-19 Time 12:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-24 Cont ID  
Sent By rmcphers Date 2021-05-24 Time 16:40 Rev Time 0.00
Received By rmcphers Date 2021-05-07 Time 15:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-06 Cont ID  
Sent By rmcphers Date 2021-05-06 Time 16:17 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-29 Cont ID  
Sent By jleahy Date 2021-01-29 Time 11:16 Rev Time 0.00
Received By jleahy Date 2020-12-30 Time 16:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-08-03 Cont ID  
Sent By lmarchan Date 2021-08-03 Time 09:06 Rev Time 0.00
Received By lmarchan Date 2021-05-07 Time 15:06 Sent To  
Notes
2021-07-29 10:13:46RECEIPT MU-2021-027642 - $546.52 PAID
2021-05-07 15:06:335/7/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By rmcphers Date 2021-01-12 Time 15:03 Rev Time 0.00
Received By rmcphers Date 2021-01-12 Time 15:03 Sent To  
Notes
2021-01-12 15:04:07PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-05-03 Cont ID  
Sent By medwards Date 2021-05-03 Time 07:58 Rev Time 0.00
Received By medwards Date 2021-05-03 Time 07:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-08 Cont ID  
Sent By medwards Date 2021-01-08 Time 15:09 Rev Time 0.00
Received By medwards Date 2021-01-08 Time 15:09 Sent To  
Notes
2021-01-08 15:09:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20121202
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THE NEW AHU IS TO BE INSTALLED IN
 THE ATTIC PLEASE SHOW THE ATTIC ACCESS. FBC RES
 M1305.1.3
  
 2) PLEASE SHOW THE RETURN AIR PATH FROM THE NEW
 ADDITION BACK TO THE AHU RETURN. FBC RES M1602.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-01-06 Cont ID  
Sent By lcrespo Date 2021-01-06 Time 06:25 Rev Time 0.00
Received By lcrespo Date 2021-01-06 Time 06:17 Sent To  
Notes
2021-01-06 06:27:28NO PLUMBING WORK DONE ON THE SCOPE OF WORK.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-05-24 Cont ID  
Sent By rmcphers Date 2021-05-24 Time 16:39 Rev Time 0.00
Received By rmcphers Date 2021-05-24 Time 16:39 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-05-06 Cont ID  
Sent By rmcphers Date 2021-05-06 Time 16:16 Rev Time 0.00
Received By rmcphers Date 2021-05-06 Time 16:16 Sent To  
Notes
2021-05-06 16:16:55SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By rmcphers Date 2021-01-12 Time 15:03 Rev Time 0.00
Received By rmcphers Date 2021-01-12 Time 15:02 Sent To  
Notes
2021-01-12 15:03:19SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-29 Cont ID  
Sent By rmcphers Date 2021-07-29 Time 09:51 Rev Time 0.00
Received By rmcphers Date 2021-07-29 Time 09:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-03 Cont ID  
Sent By medwards Date 2021-05-03 Time 07:59 Rev Time 0.00
Received By medwards Date 2021-05-03 Time 07:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-08 Cont ID  
Sent By medwards Date 2021-01-08 Time 15:21 Rev Time 0.00
Received By medwards Date 2021-01-08 Time 15:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-26 Cont ID  
Sent By kalexand Date 2021-01-26 Time 16:59 Rev Time 0.00
Received By kalexand Date 2021-01-26 Time 16:59 Sent To I
Notes
***NONE***