Plan Review Details - Permit 20121129
Plan Review Stops For Permit 20121129
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status P Date 2021-07-09 Cont ID  
Sent By jleahy Date 2021-07-09 Time 15:51 Rev Time 0.00
Received By jleahy Date 2021-07-09 Time 15:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2021-06-22 Cont ID  
Sent By ccole Date 2021-06-22 Time 14:55 Rev Time 0.00
Received By ccole Date 2021-06-22 Time 14:55 Sent To  
Notes
2021-06-22 14:56:484TH ASBESTOS REVIEW
 6/22/2021
  
 COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-05-04 Cont ID  
Sent By rmcdouga Date 2021-05-04 Time 11:36 Rev Time 0.00
Received By rmcdouga Date 2021-05-04 Time 11:36 Sent To  
Notes
2021-05-04 11:37:16COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-03-22 Cont ID  
Sent By jwitmer Date 2021-03-22 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2021-03-22 Time 10:31 Sent To  
Notes
2021-03-22 11:02:35COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-01-21 Cont ID  
Sent By jwitmer Date 2021-01-21 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2021-01-21 Time 08:30 Sent To  
Notes
2021-01-21 10:54:45COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-22 Cont ID  
Sent By jwitmer Date 2021-03-22 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2021-03-22 Time 10:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-21 Cont ID  
Sent By jwitmer Date 2021-01-21 Time 10:57 Rev Time 0.00
Received By jwitmer Date 2021-01-21 Time 08:30 Sent To  
Notes
2021-01-21 10:53:19WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20121129
 ADD: 5215 GEORGIA AVE.
 CONT: MCCABE BROTHERS CONSTRUCTION
 TEL: 561-310-6473
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET:
 1A) UNDER THE HEADING CODE DATA THE CONSTRUCTION TYPE
 IS LISTED AS TYPE IB. WITH THAT CONSTRUCTION TYPE IN
 THE 2017 FBC-B TABLE 601 REQUIRES THE EXTERIOR WALLS TO
 BE 2 HR. FIRE RATED AND THE ROOF CONSTRUCTION AND
 ASSOCIATES SECONDARY MEMBERS AND DECK TO BE 1-HOUR FIRE
 RATED, HOW IS THIS ACCOMPLISHED? SHEET A5.01 DETAIL 5
 SHOWS WOOD TRUSSES AND SHEATHING. DID YOU MEAN
 CONSTRUCTION TYPE III-B?
 1B) THE PROPOSED OCCUPANCY LOAD GIVES THE OCCUPANT LOAD
 FACTORS OF 60 FOR MERCANTILE AND 300 FOR STORAGE BUT
 THE PLANS ARE SILENT TO THE OVERALL ALL SQUARE FOOTAGE
 OF THE BUILDING AND THE SQ. FT. FOR THE MERCANTILE AND
 S1 OCCUPANCY. PLEASE PROVIDE THE MISSING INFORMATION TO
 BE ABLE TO DETERMINE THE OCCUPANT LOAD FOR THE
 MIXED-USE BUILDING. FBC-B TABLE 1004.1.2.
 1C)(1) THE 2017 FBC-B TABLE 508.4 SHOWS NO REQUIREMENT
 FOR OCCUPANCY SEPARATION BETWEEN MERCANTILE AND S1
 OCCUPANCY TYPES. PLEASE NOTE THE FIRE DEPARTMENT
 REQUIREMENTS WHICH APPEAR TO BE MORE RESTRICTIVE. WHEN
 THE 2 CODES DO NOT AGREE THE MOST RESTRICTIVE OF THE
 CODES IS REQUIRED TO BE FOLLOWED.
 1C)(2) I BELIEVE THIS IS A FISH MARKET AND THE BACK
 HALF OF THE BUILDING IS A FISH PROCESSING PORTION( SEE
 306.2 F-1 FOOD PROCESSING ESTABLISHMENTS NOT PART OF A
 RESTAURANT) OF THE BUILDING. WITH THIS BEING SAID,
 TABLE 508.4 STILL DOES NOT SHOW A REQUIRED OCCUPANCY
 SEPARATION.
 1D)(1) DEPENDING ON THE OUTCOME OF THE OCCUPANCY TYPE
 FOR THE REAR PORTION OF THE BUILDING IF THE REAR
 PORTION IS DECLARED STORAGE PLEASE REVIEW THE
 REQUIREMENTS FOR EGRESS THROUGH INTERVENING SPACES FOR
 A MERCANTILE OCCUPANCY AND REAR STORAGE ROOM. SEE 2017
 FBC-B 1016.25( 2.1-2.4).
 1D)(1) THE OTHER REAR OCCUPANCY IF DECLARED A F1
 OCCUPANCY BECAUSE OF THE SINKS AND FOOD PREPARATION, NO
 RATED WALLS BETWEEN OCCUPANCY TYPE A VESTIBULE BEING
 BUILT TO GO OUT THE SIDE EXIT, THAT COULD BE USED FROM
 EITHER OCCUPANCY TYPE.
 1E) THE OTHER ISSUE WITH EXITING IS THE EXIT SIGNS
 WITHIN HALLWAY 101. THEY APPEAR TO BE ON THE WRONG SIDE
 OF THE DOOR (IN THE MERCANTILE & F1/ S1 SIDE OF THE
 DOOR AS A AN DIRECTIONAL SIGN) AND THERE SHOULD BE AN
 EXIT SIGN AT THE TRUE EXIT TO THE EXTERIOR. 2017 FBC-B
 1013.1 WHERE REQUIRED.
 2) SHEET A2.01 THE EXTERIOR ELEVATION SHEET SHOWS NEW
 EXTERIOR WINDOWS AND DOORS. NO ARCHITECTURAL SHEET
 PROVIDES THE WIND DESIGN CRITERIA? PLEASE PROVIDE
 COMPLIANCE WITH THE 2017 FBC-B 1603.1.4 WIND DESIGN
 DATA. THE FOLLOWING INFORMATION RELATED TO WIND LOADS
 SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN
 THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3) THE LIFE SAFETY SHEET INDICATES A REQUEST FOR
 DEFERRED SUBMITTALS FOR EXTERIOR DOORS SHEET A2.0 NOTE
 3 INDICATES NEW PROPOSED WINDOWS. ADD TO DEFERRED
 SUBMITTAL SCHEDULE OR SUBMIT PRODUCT APPROVALS.
  
 4) SHEET A4.0 THE ENLARGED INTERIOR PLANS:
 4A) THE DETAIL # 1 IS MISSING THE REQUIRED DIMENSIONS
 FROM FINISH FLOOR FOR THE MIRROR. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 603.3 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 4B) THE DETAIL # 1 DOES NOT SHOW COMPLIANCE WITH
 SECTION 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED
 CLEAR FLOOR SPACE ON THE FLOOR PLAN AND 606.5 EXPOSED
 PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
  
 4C) THE DETAIL C FOR DRINKING FOUNTAINS DOES NOT SHOW
 COMPLIANCE WITH, PROTRUDING OBJECTS 307.2 PROTRUSION
 LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 5) THE PLANS DID NOT HAVE A FINISH SCHEDULE FOR THE
 INTERIOR OF THE BUILDING. 2017 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION ON 06/2020. IN RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 5A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 5B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 5C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-21 Cont ID  
Sent By jleahy Date 2021-01-21 Time 10:33 Rev Time 0.00
Received By jleahy Date 2021-01-21 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-18 Cont ID  
Sent By pleduc Date 2021-03-18 Time   Rev Time 0.00
Received By pleduc Date 2021-03-18 Time 16:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By pleduc Date 2020-12-29 Time   Rev Time 0.00
Received By pleduc Date 2020-12-29 Time 14:17 Sent To  
Notes
2020-12-29 15:25:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET ALS 1.1 - THERE IS AN INDICATION UNDER THE
 SCOPE OF WORK OF 3,033 SQ FT. THERE IS ALSO INDICATIONS
 OF A MIXED OCCUPANCY/ STORAGE - MERCANTILE.
  
 THERE ARE NO INDICATIONS OF SEPARATION MAKING IT
 MERCANTILE OCCUPANCY - CLASS B, REQUIREING TWO EXITS .
  
 36.1.2.2 SUBCLASSIFICATION OF OCCUPANCY.
 36.1.2.2.1 MERCANTILE OCCUPANCIES SHALL BE
 SUBCLASSIFIED AS
 FOLLOWS:
 (1) CLASS A, ALL MERCANTILE OCCUPANCIES HAVING AN
 AGGREGATE
 GROSS AREA OF MORE THAN 30,000 FT2 (2800 M) OR
 OCCUPYING
 MORE THAN THREE STORIES FOR SALES PURPOSES
 (2) CLASS B, AS FOLLOWS:
 (A) ALL MERCANTILE OCCUPANCIES OF MORE THAN 3000 FT2
 (280
 M2), BUT NOT MORE THAN 30,000 FT2 (2800 M2), AGGREGATE
 GROSS AREA AND OCCUPYING NOT MORE THAN THREE STORIES
 FOR
 SALES PURPOSES
 (B) ALL MERCANTILE OCCUPANCIES OF NOT MORE THAN 3000
 FT2
 (280 M3) GROSS AREA AND OCCUPYING TWO OR THREE STORIES
 FOR SALES PURPOSES
 (3) CLASS C, ALL MERCANTILE OCCUPANCIES OF NOT MORE
 THAN 3000
 FT2 (280 M2) GROSS AREA AND USED FOR SALES PURPOSES
 OCCUPYING ONE STORY ONLY
  
 THERE ARE ALSO INDICATIONS OF ONE ONLY EXIT FROM EACH
 SPACE - STORAGE & MERCANTILE.
  
 PLEASE REVIEW AND PROVIDE DETAILS OF THE OCCUOANCY
 CLASSIFICATION PER NFPA 101, CH 36 AND CH 6
  
  
  
 1A) PROVIDE THE APPLICABLE NUMBER OF EXITS PER THAT
 CLASSIFICATION.
  
 36.2 MEANS OF EGRESS REQUIREMENTS.
 36.2.1 GENERAL.
 36.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER
 7 AND THIS CHAPTER.
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
 ENSURE COMPLIANCE .
  
 2) PLEASE PROVIDE THE STORAGE TYPE INCLUDING RACKS
 LOCATION, RACK HEIGHTS, COMMODITY STORED, PALLETS,
 WRAPPING, ETC.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-06-22 Cont ID  
Sent By ccole Date 2021-06-22 Time 14:48 Rev Time 0.00
Received By ccole Date 2021-06-22 Time 13:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-04-29 Cont ID  
Sent By ccole Date 2021-04-29 Time 17:50 Rev Time 0.00
Received By ccole Date 2021-04-29 Time 17:50 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-04-07 Cont ID  
Sent By ccole Date 2021-04-07 Time 13:52 Rev Time 0.00
Received By ccole Date 2021-04-07 Time 12:37 Sent To  
Notes
2021-04-07 13:53:592ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 20121129
 4/7/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NO CORRECTED PLANS OR NARRATIVE RESPONSES WERE
 SUBMITTED.
  
 1) SHEET P5.1 GAS RISER:
 A) SHOW THE METER AND THE GAS DELIVERY PRESSURE AT THE
 METER- SECTION 402.1 & 401.2 FBC FG.
 B) INDICATE THE TYPE OF GAS PIPING- SECTION 402.3 FBC
 FG.
 C) SHOW THE LOCATION OF THE REGULATOR AT THE WATER
 HEATER AND INDICATE THE REQUIRED GAS INPUT PRESSURE-
 SECTION 410.1 & 410.2 FBC FG.
  
 2) P5.1: PLEASE UPDATE THE FBC-2004 FUEL GAS CODE
 REFERENCE TO THE CODE IN FORCE FOR THIS PERMIT- 2017-
 SECTION 107.2.1 WPB.
  
 3) P0.1 & P5.1: PROVIDE A WATER HEATER EQUIPMENT
 SCHEDULE ON THE PLAN AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION G2448.1 FBC FG AND TABLE C404.2
 FBC EC.
  
 4) PROVIDE A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-01-20 Cont ID  
Sent By ccole Date 2021-01-20 Time 14:27 Rev Time 0.00
Received By ccole Date 2021-01-20 Time 11:45 Sent To  
Notes
2021-01-20 14:49:221ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20121129
 1/20/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P5.1 GAS RISER:
 A) SHOW THE METER AND THE GAS DELIVERY PRESSURE AT THE
 METER- SECTION 402.1 & 401.2 FBC FG.
 B) INDICATE THE TYPE OF GAS PIPING- SECTION 402.3 FBC
 FG.
 C) SHOW THE LOCATION OF THE REGULATOR AT THE WATER
 HEATER AND INDICATE THE REQUIRED GAS INPUT PRESSURE-
 SECTION 410.1 & 410.2 FBC FG.
  
 2) P5.1: PLEASE UPDATE THE FBC-2004 FUEL GAS CODE
 REFERENCE TO THE CODE IN FORCE FOR THIS PERMIT- 2017-
 SECTION 107.2.1 WPB.
  
 3) P0.1 & P5.1: PROVIDE A WATER HEATER EQUIPMENT
 SCHEDULE ON THE PLAN AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION G2448.1 FBC FG AND TABLE C404.2
 FBC EC.
  
 4) PROVIDE A GAS SUB-PERMIT APPLICATION- SECTION 105.1
 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
2021-01-20 14:27:43 
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-09 Cont ID  
Sent By jleahy Date 2021-07-09 Time 15:52 Rev Time 0.00
Received By jleahy Date 2021-07-07 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-06-22 Time   Rev Time 0.00
Received By aoliver Date 2021-06-02 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-04 Cont ID  
Sent By rmcdouga Date 2021-05-04 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2021-04-14 Time 14:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-04-07 Time   Rev Time 0.00
Received By aoliver Date 2021-03-17 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-01-21 Time 10:57 Rev Time 0.00
Received By lmarchan Date 2020-12-23 Time 09:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-06-21 Cont ID  
Sent By medwards Date 2021-06-21 Time 09:44 Rev Time 0.00
Received By medwards Date 2021-06-21 Time 09:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-05-03 Cont ID  
Sent By medwards Date 2021-05-03 Time 09:29 Rev Time 0.00
Received By medwards Date 2021-05-03 Time 09:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-04-02 Cont ID  
Sent By medwards Date 2021-04-02 Time 14:11 Rev Time 0.00
Received By medwards Date 2021-04-02 Time 14:11 Sent To  
Notes
2021-04-02 14:13:16PLEASE ADDRESS COMMENTS FROM 1ST CYCLE REVIEW.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-14 Cont ID  
Sent By medwards Date 2021-01-14 Time 08:26 Rev Time 0.00
Received By medwards Date 2021-01-14 Time 08:26 Sent To  
Notes
2021-01-14 08:26:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20121129
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.1: OUTDOOR AIR CALCULATIONS FOR THE SALES
 AREA APPEAR TO BE LOW.
 1450/1000 = 1.45 X 15 X 7.5 = 163.125 + 1450 X .12 =
 174; 163.125 + 174 = 338 CFM OF OUTDOOR AIR FOR THE
 SALES AREA. FBC M TABLE 403.3.1.1
  
 2) PLEASE PROVIDE ANCHORAGE DETAILS FOR THE OARTU. FBC
 107.2.1
  
 3) PLEASE SHOW THAT THE OARTU LOCATION AND ACCESS
 LOCATION MEETS FBC M 306.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-06-22 Cont ID  
Sent By ccole Date 2021-06-22 Time 14:47 Rev Time 0.00
Received By ccole Date 2021-06-22 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-04-29 Cont ID  
Sent By ccole Date 2021-04-29 Time 17:22 Rev Time 0.00
Received By ccole Date 2021-04-29 Time 17:22 Sent To  
Notes
2021-04-29 17:24:473RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20121129
 4/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST AND 2ND REVIEW ARE LISTED
 BELOW WITH NOTES ADDED IN CAPS.
  
 1) FAILED. P0.1: PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.3 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF REQUIRED FIXTURES. PLEASE NOTE THAT A SERVICE
 SINK IS A REQUIRED FOR MERCANTILE AND STORAGE
 OCCUPANCIES. REVISE THE PLANS ACCORDINGLY. THE COMMENT
 RESPONSE NARRATIVE STATES THE FIXTURES CALCULATIONS ARE
 ON A4.0.1 HOWEVER THEY ARE NOT SHOWN THERE.
  
 2) FAILED. SHEETS P0.1, P2.1 & P5.1: A GREASE
 INTERCEPTOR IS REQUIRED IN ACCORDANCE WITH 1003.3.1 FBC
 P TO RECEIVE THE DRAINAGE FROM THE 3-COMPARTMENT SINK
 (SK-3) AND THE SK SINKS. THE LARGE SK SINK APPEARS TO
 BE FOR FOOD PREP OR POT OR DISHWASHING WHICH REQUIRES
 AN INDIRECT WASTE PIPE. SIZING CALCULATIONS FOR THE
 INTERCEPTORS HAVE NOT BEEN PROVIDED. SEE COMMENT 4
 BELOW CONCERNING PLUMBING PIPING INSTALLATION AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 4) FAILED. P0.1: REFER TO SECTION 802.1 FBC P AND
 PROVIDE AN INDIRECT WASTE DETAIL FOR SK-3 AND THE LARGE
 SK SINK. INDIRECT WASTE DETAIL NOT PROVIDED. PLEASE
 NOTE THAT THE PLUMBING PLANS ARE SHOWING A DIRECT
 CONNECTION FROM THE 3-BAY SINK AND PREP SINK TO THE
 INTERCEPTORS WHICH IS NOT IN COMPLIANCE WITH SECTION
 802.1. PLEASE PROVIDE GREASE INTERCEPTOR PLUMBING
 DIAGRAMS FROM THE MANUFACTURER TO VERIFY COMPLIANCE-
 SECTION 1003.3.5.
  
 6) FAILED. P2.1 & P5.1: INDICATE HOW TRAP SEALS WILL BE
 PROVIDED FOR THE TRENCH DRAINS- SECTIONS 901.2 &
 1002.4.1 FBC P. TRAPS HAVE BEEN ADDED BUT NOT TRAP
 SEALS-
 1002.4.1 TRAP SEAL PROTECTION. TRAP SEALS OF EMERGENCY
 FLOOR DRAIN TRAPS AND TRAP SEALS SUBJECT TO EVAPORATION
 SHALL BE PROTECTED BY ONE OF THE METHODS IN SECTIONS
 1002.4.1.1 THROUGH 1002.4.1.4.
 1002.4.1.1 POTABLE WATER-SUPPLIED TRAP SEAL PRIMER
 VALVE. A POTABLE WATER-SUPPLIED TRAP SEAL PRIMER VALVE
 SHALL SUPPLY WATER TO THE TRAP. WATER-SUPPLIED TRAP
 SEAL PRIMER VALVES SHALL CONFORM TO ASSE 1018. THE
 DISCHARGE PIPE FROM THE TRAP SEAL PRIMER VALVE SHALL
 CONNECT TO THE TRAP ABOVE THE TRAP SEAL ON THE INLET
 SIDE OF THE TRAP.
  
 8) FAILED. A1.1.1, P2.1 & P5.1: THE FLOOR PLAN SHOWS AN
 ICE MACHINE WITH NO WASTE RECEPTOR TO RECEIVE THE
 DRAINAGE FROM THE ICE AND THE CONDENSATION. PLEASE
 INDICATE HOW THE DRAINAGE WILL BE DISCHARGED TO AN
 APPROVED LOCATION- SECTION 314.2 FBC P. THE RESPONSE
 NARRATIVE STATES THAT THE ICE MACHINE HAS BEEN REMOVED
 HOWEVER SHEET A1.1.1 IS SHOWING THE ICE MACHINE AND
 ALS1.1 SHOWS A LOBSTER TANK. THE PLANS ARE IN CONFLICT.
  
 9) PLEASE PROVIDE THE WATER HEATER COMPLAINCE DATA ON
 THE ENERGY EFFICIENCY REPORT- TABLE C404.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
2021-04-29 17:23:10 
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-04-07 Cont ID  
Sent By ccole Date 2021-04-07 Time 13:37 Rev Time 0.00
Received By ccole Date 2021-04-07 Time 12:37 Sent To  
Notes
2021-04-07 13:37:322ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20121129
 4/7/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NO REVISED PLANS OR NARRATIVE RESPONSES WERE PROVIDED.
  
 1) P0.1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 REQUIRED FIXTURES. PLEASE NOTE THAT A SERVICE SINK IS A
 REQUIRED FOR MERCANTILE AND STORAGE OCCUPANCIES. REVISE
 THE PLANS ACCORDINGLY.
  
 2) SHEETS P0.1, P2.1 & P5.1: A GREASE INTERCEPTOR IS
 REQUIRED IN ACCORDANCE WITH 1003.3.1 FBC P TO RECEIVE
 THE DRAINAGE FROM THE 3-COMPARTMENT SINK (SK-3) AND THE
 SK SINKS. THE LARGE SK SINK APPEARS TO BE FOR FOOD PREP
 OR POT OR DISHWASHING WHICH REQUIRES AN INDIRECT WASTE
 PIPE.
  
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL
 BE PERMITTED TO BE INSTALLED ON OR ABOVE THE FLOOR AND
 UPSTREAM OF AN EXISTING GREASE INTERCEPTOR.
  
 3) P0.1, P2.1 & P5.1: THE PLANS DO NOT MAKE CLEAR THE
 NEED FOR THE LARGE TRENCH DRAINS AND WHAT DRAINAGE THEY
 WILL RECEIVE. PLEASE NOTE THE REQUIREMENT IN COMMENT #1
 FOR THAT DRAINAGE TO BE DISCHARGED INTO A GREASE
 INTERCEPTOR AND PLEASE CLARIFY- SECTION 1003.3.1 AND
 SECTION 107.2.1 WPB.
  
 4) P0.1: REFER TO SECTION 802.1 AND PROVIDE AN INDIRECT
 WASTE DETAIL FOR SK-3 AND THE LARGE SK SINK.
  
 5) P0.1, P2.1 & P5.1: THE TRENCH DRAIN FIXTURE
 SPECIFICATIONS INDICATE THE DRAINS ARE FOR CORROSIVE OR
 ACID WASTE APPLICATIONS. PLEASE CLARIFY WHAT DRAINAGE
 THEY WILL RECEIVE AND NOTE SECTION 803.1 REQUIRES
 CORROSIVE LIQUIDS, SPENT ACIDS, OR OTHER HARMFUL
 CHEMICALS TO BE NEUTRALIZED OR DILUTED BY A DEVICE
 BEFORE DISCHARGING INTO THE PLUMBING SYSTEM.
  
 6) P2.1 & P5.1: INDICATE HOW TRAP SEALS WILL BE
 PROVIDED FOR THE TRENCH DRAINS- SECTIONS 901.2 &
 1002.4.1 FBC P.
  
 7) P2.1 & P5.1: INDICATE HOW THE TWO LARGE TRENCH
 DRAINS AND FLOOR SINK FOR THE 3-COMPARRTMENT SINK ARE
 BEING VENTED- SECTION 901.2.1 FBC P.
  
 8) A1.1.1, P2.1 & P5.1: THE FLOOR PLAN SHOWS AN ICE
 MACHINE WITH NO WASTE RECEPTOR TO RECEIVE THE DRAINAGE
 FROM THE ICE AND THE CONDENSATION. PLEASE INDICATE HOW
 THE DRAINAGE WILL BE DISCHARGED TO AN APPROVED
 LOCATION- SECTION 314.2 FBC P.
  
 9) P0.1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE ON
 THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECTION G2448.1 FBC FG AND TABLE C404.2 FBC EC.
  
 10) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 NEW COMMENT.
  
 1) PLEASE SHOW THE LOCATION OF THE REQUIRED SINK ON THE
 PLANS AND ISOMETRIC DRAWINGS, AND ADD THE SINK TO THE
 FIXTURE SCHEDULE- TABLE 403.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-20 Cont ID  
Sent By ccole Date 2021-01-20 Time 14:29 Rev Time 0.00
Received By ccole Date 2021-01-20 Time 10:29 Sent To  
Notes
2021-01-20 14:30:121ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20121129
 1/20/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P0.1: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE
 THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF
 REQUIRED FIXTURES. PLEASE NOTE THAT A SERVICE SINK IS A
 REQUIRED FOR MERCANTILE AND STORAGE OCCUPANCIES. REVISE
 THE PLANS ACCORDINGLY.
  
 2) SHEETS P0.1, P2.1 & P5.1: A GREASE INTERCEPTOR IS
 REQUIRED IN ACCORDANCE WITH 1003.3.1 FBC P TO RECEIVE
 THE DRAINAGE FROM THE 3-COMPARTMENT SINK (SK-3) AND THE
 SK SINKS. THE LARGE SK SINK APPEARS TO BE FOR FOOD PREP
 OR POT OR DISHWASHING WHICH REQUIRES AN INDIRECT WASTE
 PIPE.
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES; WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. WHERE LACK
 OF SPACE OR OTHER CONSTRAINTS PREVENT THE INSTALLATION
 OR REPLACEMENT OF A GREASE INTERCEPTOR, ONE OR MORE
 GREASE INTERCEPTORS SHALL BE PERMITTED TO BE INSTALLED
 ON OR ABOVE THE FLOOR AND UPSTREAM OF AN EXISTING
 GREASE INTERCEPTOR.
  
 3) P0.1, P2.1 & P5.1: THE PLANS DO NOT MAKE CLEAR THE
 NEED FOR THE LARGE TRENCH DRAINS AND WHAT DRAINAGE THEY
 WILL RECEIVE. PLEASE NOTE THE REQUIREMENT IN COMMENT #1
 FOR THAT DRAINAGE TO BE DISCHARGED INTO A GREASE
 INTERCEPTOR AND PLEASE CLARIFY- SECTION 1003.3.1 AND
 SECTION 107.2.1 WPB.
  
 4) P0.1: REFER TO SECTION 802.1 AND PROVIDE AN INDIRECT
 WASTE DETAIL FOR SK-3 AND THE LARGE SK SINK.
  
 5) P0.1, P2.1 & P5.1: THE TRENCH DRAIN FIXTURE
 SPECIFICATIONS INDICATE THE DRAINS ARE FOR CORROSIVE OR
 ACID WASTE APPLICATIONS. PLEASE CLARIFY WHAT DRAINAGE
 THEY WILL RECEIVE AND NOTE SECTION 803.1 REQUIRES
 CORROSIVE LIQUIDS, SPENT ACIDS, OR OTHER HARMFUL
 CHEMICALS TO BE NEUTRALIZED OR DILUTED BY A DEVICE
 BEFORE DISCHARGING INTO THE PLUMBING SYSTEM.
  
 6) P2.1 & P5.1: INDICATE HOW TRAP SEALS WILL BE
 PROVIDED FOR THE TRENCH DRAINS- SECTIONS 901.2 &
 1002.4.1 FBC P.
  
 7) P2.1 & P5.1: PROVIDE VENTS FOR THE TWO LARGE TRENCH
 DRAINS- SECTION 901.2.1 FBC P.
  
 8) A1.1.1, P2.1 & P5.1: THE FLOOR PLAN SHOWS AN ICE
 MACHINE WITH NO WASTE RECEPTOR TO RECEIVE THE DRAINAGE
 FROM THE ICE AND THE CONDENSATION. PLEASE INDICATE HOW
 THE DRAINAGE WILL BE DISCHARGED TO AN APPROVED
 LOCATION- SECTION 314.2 FBC P.
 9) AD.1.1: PROVIDE A SLAB REPAIR DETAIL- SECTION
 107.2.1 WPB.
  
 10) P0.1: PROVIDE A WATER HEATER EQUIPMENT SCHEDULE ON
 THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECTION G2448.1 FBC FG AND TABLE C404.2 FBC EC.
  
 11) A4.01: MISSING ACCESSIBLE PLUMBING FIXTURE DETAILS
 PER FBC ACC:
  
 A) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 B) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2
 C) DRINKING FOUNTAIN KNEE AND TOE CLEARANCES, SPOUT
 HEIGHT FOR THE HI FOUNTAIN- SECTIONS 606.2 & 306. SHOW
 HOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS.
  
 12) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-06-21 Cont ID  
Sent By medwards Date 2021-06-21 Time 09:44 Rev Time 0.00
Received By medwards Date 2021-06-21 Time 09:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-05-03 Cont ID  
Sent By medwards Date 2021-05-03 Time 09:33 Rev Time 0.00
Received By medwards Date 2021-05-03 Time 09:33 Sent To  
Notes
2021-05-03 09:34:50PLEASE PROVIDE MECHANICAL AND PLUMBING SHEETS WITH THE
 DIGITAL SIGNATURES OF THE DESIGNERS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-07 Cont ID  
Sent By ccole Date 2021-04-07 Time 14:02 Rev Time 0.00
Received By ccole Date 2021-04-07 Time 13:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-14 Cont ID  
Sent By medwards Date 2021-01-14 Time 08:30 Rev Time 0.00
Received By medwards Date 2021-01-14 Time 08:30 Sent To  
Notes
***NONE***