| 2021-01-21 10:53:19 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20121129 |
| | ADD: 5215 GEORGIA AVE. |
| | CONT: MCCABE BROTHERS CONSTRUCTION |
| | TEL: 561-310-6473 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | 1) THE LIFE SAFETY SHEET: |
| | 1A) UNDER THE HEADING CODE DATA THE CONSTRUCTION TYPE |
| | IS LISTED AS TYPE IB. WITH THAT CONSTRUCTION TYPE IN |
| | THE 2017 FBC-B TABLE 601 REQUIRES THE EXTERIOR WALLS TO |
| | BE 2 HR. FIRE RATED AND THE ROOF CONSTRUCTION AND |
| | ASSOCIATES SECONDARY MEMBERS AND DECK TO BE 1-HOUR FIRE |
| | RATED, HOW IS THIS ACCOMPLISHED? SHEET A5.01 DETAIL 5 |
| | SHOWS WOOD TRUSSES AND SHEATHING. DID YOU MEAN |
| | CONSTRUCTION TYPE III-B? |
| | 1B) THE PROPOSED OCCUPANCY LOAD GIVES THE OCCUPANT LOAD |
| | FACTORS OF 60 FOR MERCANTILE AND 300 FOR STORAGE BUT |
| | THE PLANS ARE SILENT TO THE OVERALL ALL SQUARE FOOTAGE |
| | OF THE BUILDING AND THE SQ. FT. FOR THE MERCANTILE AND |
| | S1 OCCUPANCY. PLEASE PROVIDE THE MISSING INFORMATION TO |
| | BE ABLE TO DETERMINE THE OCCUPANT LOAD FOR THE |
| | MIXED-USE BUILDING. FBC-B TABLE 1004.1.2. |
| | 1C)(1) THE 2017 FBC-B TABLE 508.4 SHOWS NO REQUIREMENT |
| | FOR OCCUPANCY SEPARATION BETWEEN MERCANTILE AND S1 |
| | OCCUPANCY TYPES. PLEASE NOTE THE FIRE DEPARTMENT |
| | REQUIREMENTS WHICH APPEAR TO BE MORE RESTRICTIVE. WHEN |
| | THE 2 CODES DO NOT AGREE THE MOST RESTRICTIVE OF THE |
| | CODES IS REQUIRED TO BE FOLLOWED. |
| | 1C)(2) I BELIEVE THIS IS A FISH MARKET AND THE BACK |
| | HALF OF THE BUILDING IS A FISH PROCESSING PORTION( SEE |
| | 306.2 F-1 FOOD PROCESSING ESTABLISHMENTS NOT PART OF A |
| | RESTAURANT) OF THE BUILDING. WITH THIS BEING SAID, |
| | TABLE 508.4 STILL DOES NOT SHOW A REQUIRED OCCUPANCY |
| | SEPARATION. |
| | 1D)(1) DEPENDING ON THE OUTCOME OF THE OCCUPANCY TYPE |
| | FOR THE REAR PORTION OF THE BUILDING IF THE REAR |
| | PORTION IS DECLARED STORAGE PLEASE REVIEW THE |
| | REQUIREMENTS FOR EGRESS THROUGH INTERVENING SPACES FOR |
| | A MERCANTILE OCCUPANCY AND REAR STORAGE ROOM. SEE 2017 |
| | FBC-B 1016.25( 2.1-2.4). |
| | 1D)(1) THE OTHER REAR OCCUPANCY IF DECLARED A F1 |
| | OCCUPANCY BECAUSE OF THE SINKS AND FOOD PREPARATION, NO |
| | RATED WALLS BETWEEN OCCUPANCY TYPE A VESTIBULE BEING |
| | BUILT TO GO OUT THE SIDE EXIT, THAT COULD BE USED FROM |
| | EITHER OCCUPANCY TYPE. |
| | 1E) THE OTHER ISSUE WITH EXITING IS THE EXIT SIGNS |
| | WITHIN HALLWAY 101. THEY APPEAR TO BE ON THE WRONG SIDE |
| | OF THE DOOR (IN THE MERCANTILE & F1/ S1 SIDE OF THE |
| | DOOR AS A AN DIRECTIONAL SIGN) AND THERE SHOULD BE AN |
| | EXIT SIGN AT THE TRUE EXIT TO THE EXTERIOR. 2017 FBC-B |
| | 1013.1 WHERE REQUIRED. |
| | 2) SHEET A2.01 THE EXTERIOR ELEVATION SHEET SHOWS NEW |
| | EXTERIOR WINDOWS AND DOORS. NO ARCHITECTURAL SHEET |
| | PROVIDES THE WIND DESIGN CRITERIA? PLEASE PROVIDE |
| | COMPLIANCE WITH THE 2017 FBC-B 1603.1.4 WIND DESIGN |
| | DATA. THE FOLLOWING INFORMATION RELATED TO WIND LOADS |
| | SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN |
| | THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 2.2. RISK CATEGORY. |
| | |
| | 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 3) THE LIFE SAFETY SHEET INDICATES A REQUEST FOR |
| | DEFERRED SUBMITTALS FOR EXTERIOR DOORS SHEET A2.0 NOTE |
| | 3 INDICATES NEW PROPOSED WINDOWS. ADD TO DEFERRED |
| | SUBMITTAL SCHEDULE OR SUBMIT PRODUCT APPROVALS. |
| | |
| | 4) SHEET A4.0 THE ENLARGED INTERIOR PLANS: |
| | 4A) THE DETAIL # 1 IS MISSING THE REQUIRED DIMENSIONS |
| | FROM FINISH FLOOR FOR THE MIRROR. PLEASE SHOW |
| | COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION |
| | 603.3 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 4B) THE DETAIL # 1 DOES NOT SHOW COMPLIANCE WITH |
| | SECTION 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE REQUIRED |
| | CLEAR FLOOR SPACE ON THE FLOOR PLAN AND 606.5 EXPOSED |
| | PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER |
| | LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE |
| | CONFIGURED TO PROTECT AGAINST CONTACT. |
| | |
| | 4C) THE DETAIL C FOR DRINKING FOUNTAINS DOES NOT SHOW |
| | COMPLIANCE WITH, PROTRUDING OBJECTS 307.2 PROTRUSION |
| | LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 |
| | INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR |
| | SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO |
| | THE CIRCULATION PATH. |
| | |
| | 5) THE PLANS DID NOT HAVE A FINISH SCHEDULE FOR THE |
| | INTERIOR OF THE BUILDING. 2017 FBC-B 1210.2.2. WALLS & |
| | PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING |
| | OFFICIAL INTERPRETATION ON 06/2020. IN RESTROOMS & |
| | SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED |
| | A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | |
| | 5A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 5B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS |
| | SHALL COMPLY WITH 1210.2. |
| | |
| | 5C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND |
| | PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH |
| | SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |