| 2020-12-30 13:54:42 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20121023 |
| | 12/30/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A LP TANK INSTALLATION DETAIL SHOWING THE |
| | REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE STRUCTURAL |
| | SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATION WITH |
| | THE CONTAINER SUPPORTS- SECTION 6.6.3.1 NFPA 58. SHOW |
| | HOW THE TANK WILL BE ANCHORED TO RESIST WIND LOAD AND |
| | WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA 58. |
| | |
| | 2) INDICATE THE PIPING DOWNSTREAM OF THE 2ND STAGE |
| | REGULATOR WILL BE CAPPED GAS TIGHT- SECTION G2415.15 |
| | FBC RES. PLACE A NOTE ON THE PLAN INDICATING A SEPARATE |
| | PERMIT AND PLANS ARE REQUIRED FOR FUTURE GAS PIPING |
| | CONTINUATION AND APPLIANCE INSTALLATIONS- SECTION |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |