Plan Review Details - Permit 20121003
Plan Review Stops For Permit 20121003
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-04 Cont ID  
Sent By rmcphers Date 2021-05-04 Time 11:18 Rev Time 0.00
Received By rmcphers Date 2021-05-04 Time 11:18 Sent To  
Notes
2021-05-04 11:26:19ANTENNA
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE
 REVISE THE DRAWING TO SHOW THE DESIGN PER THE CODE IN
 EFFECT (2020 FBC USING ASCE 7-16 FOR WIND DESIGN)
 2) PLEASE PROVIDE A SIGNED AND SEALED UTILITY POLE
 STRUCTURAL ANALYSIS FROM A STRUCTURAL ENGINEER FOR THE
 ADDED COMPONENTS TO THE EXISTING POLE PER NOTE ON
 DRAWING C-3

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2021-04-30 Cont ID  
Sent By jleahy Date 2021-04-30 Time 10:14 Rev Time 0.00
Received By jleahy Date 2021-04-30 Time 10:14 Sent To  
Notes
2021-04-30 10:15:38RESULTED BY MISTAKE JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-10 Cont ID  
Sent By jleahy Date 2021-05-10 Time 10:25 Rev Time 0.00
Received By jleahy Date 2021-04-30 Time 10:15 Sent To  
Notes
2021-05-10 10:27:28 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 WHO IS RESPONSIBLE FOR THE DIRECTIONAL BORE, IF IT IS
 NOT FPL PLEASE INCLUDE THE VALUE IN YOUR PERMIT
 APPLICATION FOR THIS WORK. SUBMIT A LEETER FROM FPL
 STATING IDF IT IS THEIR WORK.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2021-06-11 Cont ID  
Sent By gpatrie Date 2021-06-11 Time 08:11 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-06-11 08:11:351. NOT IN THE CITY RIGHT-OF-WAY / FDOT PERMIT REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 13:26 Rev Time 0.00
Received By shill Date 2021-04-16 Time 10:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-04 Cont ID  
Sent By rmcphers Date 2021-05-04 Time 11:57 Rev Time 0.00
Received By rmcphers Date 2021-05-04 Time 11:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-05-20 Cont ID  
Sent By eschneid Date 2021-05-20 Time 10:31 Rev Time 0.25
Received By eschneid Date 2021-05-20 Time 10:05 Sent To  
Notes
2021-05-20 10:32:09FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE EXISTING UTILITY
 POLE LOCATION, THE RIGHT-OF-WAY LINE AND THE EDGE OF
 PAVEMENT SO THAT STAFF CAN VERIFY THAT THE WIRELESS
 COMMUNICATION FACILITY IS WITHIN THE RIGHT-OF-WAY AND
 NOT ON PRIVATE PROPERTY. THE SURVEY SHALL SHOW THE
 DIMENSION FROM THE EDGE OF THE UTILITY POLE TO THE
 RIGHT-OF-WAY LINE AND THE DIMENSION FROM THE EDGE OF
 PAVEMENT TO THE RIGHT-OF-WAY LINE.
  
 2) THE ENGINEERING PLAN SHALL BE BASED ON THE SURVEY
 REQUIRED IN COMMENT #1. IT SHALL SHOW THE DIMENSIONS
 FROM THE FURTHEST PROJECTION OF THE PANEL ANTENNA
 ARRAY/ANTENNAS TO THE RIGHT-OF-WAY LINE AND THE
 DIMENSION FROM THE FURTHEST PROJECTION OF THE
 METER/DISCONNECT TO THE RIGHT-OR-WAY LINE. NOTHING IS
 PERMITTED TO CROSS ONTO PRIVATE PROPERTY AS PART OF
 THIS INSTALLATION.
  
 3) PROVIDE A COPY OF THE FDOT APPROVAL FOR THE PROPOSED
 WIRELESS COMMUNICATION FACILITY IN THE RIGHT-OF-WAY.
  
 4) THE PROPOSED CONCRETE PEDESTAL WITH ATTACHED UTILITY
 METER, NEMA BOX AND DISCONNECT DOES NOT MEET THE CITY
 OF WEST PALM BEACH CONCEALMENT (STEALTH), STYLE
 REQUIRED BY SECTIONS 78-411(E) AND 78-411(F) OF THE
 CITY CODE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  