Plan Review Details - Permit 20120964
Plan Review Stops For Permit 20120964
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-07-05 Cont ID  
Sent By jwitmer Date 2022-04-12 Time 15:37 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By jwitmer Date 2021-09-07 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2021-09-07 Time 13:11 Sent To  
Notes
2021-09-07 13:12:11COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-07-05 Cont ID  
Sent By jwitmer Date 2022-07-05 Time 09:02 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-06-27 Cont ID  
Sent By jwitmer Date 2022-06-27 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2022-06-27 Time 11:56 Sent To  
Notes
2022-06-27 15:03:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW/ 12/18/2020
 W. P. B. PERMIT: 20120964
 ADD: 1301 BELVEDERE RD.
 CONT: OCC CONSTRUCTION LLC/ CLARK S. HARDEN- QUALIFIER
 TEL: 561-281-0454
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JUNE 27TH/2022
 ACTION: DENIED
 6/27/2022 UNABLE TO READ ANY WRITING AND OR NOTES THIS
 SHEET LS-101. SHEET LS-102 NOT OPENING FOR REVIEW.
 UNABLE TO VERIFY THE INTEGRITY OF THE CONFIGURATION
 DATA, BIG RED NOTE. THE CLIENT ENCOUNTERED A PROBLEM
 WITH THE PREVIOUS REQUEST.
  
 1) THE LS-101 GROUND FLOOR LIFE SAFETY PLAN, A-102 &
 A-102A DOES NOT SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE, (SUBMITTED ON 12/18/2020 THE
 2020 FBC FAMILY OF CODES (ACCESSIBILITY INCLUDED) WAS
 ADOPTED STATEWIDE ON 12/31/2020.
  
 1A) SEMI-COMPLIED. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 1B)2ND REQUEST. THE HUDDLE SPOTS 123 AND HI-TOPS 128 DO
 NOT SHOW COMPLIANCE WITH THE HEIGHT REQUIREMENT FOUND
 IN 902.3 FOR DINING AND OR WORK SURFACES.
 1ST ROUND COMMENTS. 226.2 DISPERSION. DINING SURFACES
 AND WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 1C) COMPLIED.
  
 1D) SEMI-COMPLIED I DO NOT SEE A CUT SECTION THROUGH
 THE BAR SHOWING COMPLIANCE WITH 902.2 OR 902.3 OF THE
 2017 ACCESSIBILITY CODE. SEMI-COMPLIED.
 1ST ROUND COMMENTS. 902.1. DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, HIGH TOPS, TABLES, LUNCH COUNTERS,
 AND BOOTHS. EXAMPLES OF WORK SURFACES INCLUDE WRITING
 SURFACES, STUDY CARRELS, STUDENT LABORATORY STATIONS,
 BABY CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ADA
 SCOPING PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 1E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1F)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1G-H) COMPLIED.
  
 2A) 6/27/2022 NOT ABLE TO VERIFY WITH LIFE SAFETY
 SHEETS NOT IN WORKING ORDER TO REVIEW.
 W SHEETS SEMI-COMPLIED. OCCUPANCY INDICATES HOTELS
 TRANSIENT R-1. MISSING OCCUPANCIES ARE EITHER:
 RESTAURANT A-2 OR BUSINESS LESS THAN 50 OCCUPANTS,
 BUSINESS: FRONT COUNTER AND ASSOCIATED OFFICE AREAS
 GYMNASIUM: A-3
 POOL AND POOL DECK: A-4
  
 MISSING THE SQUARE FOOTAGE FOR EACH OCCUPANCY TYPE,
 OCCUPANT LOAD FOR EACH OCCUPANCY.
 1ST ROUND OF COMMENTS. SHEET LS-102 2NSD FLOOR LIFE
 SAFETY PLAN. 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION: 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS AND OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 CODE DATA/ BUILDING DATA
 OCCUPANCY GROUP
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 2B)(1) RESPONSE STATES THAT FOR A R-1 HOTEL OCCUPANCY
 DRINKING FOUNTAINS ARE NOT REQUIRED PER THE 2017
 FBC-PLUMBING CODE. THIS IS TRUE BUT THE DRINKING
 FOUNTAINS ARE REQUIRED FOR A3 OCCUPANCY LECTURE HALLS,
 EXHIBITION HALLS AND AUDITORIUMS. DRINKING FOUNTAINS
 ARE ALSO REQUIRED FOR A4 OCCUPANCIES POOL AND POOL
 DECKS. A2 OCCUPANCIES RESTAURANTS AND BARS MAY NOT
 REQUIRE DRINKING FOUNTAINS IF THE PLAN STATES THEY ARE
 USING SECTION 410.4 WHERE RESTAURANTS PROVIDE DRINKING
 WATER IN A CONTAINER FREE OF CHARGE, THIS WAS NOTED ON
 THE LIFE SAFETY PLAN NOR PLUMBING SHEETS.
 THE OTHER ISSUE IS WITH SHEET A-106 ELEVATION 2
 DRINKING FOUNTAIN WITH BOTTLE FILLER. PLEASE SEE IN THE
 2017 FBC-PLUMBING CODE SECTION 410. 4 FOR SUBSTITUTION
 AND PLUMBING COMMENTS.
 1ST ROUND OF COMMENTS. 2017 FBC-ACCESSIBILITY CODE.
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 2ND REQUEST.(2B(2) PROTRUDING OBJECTS 307.2 PROTRUSION
 LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 2ND REQUEST. 2B)(3) 602.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 2ND REQUEST. 2B)(4) SPOUT OUTLETS/ DRINKING FOUNTAINS.
 2017 ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 3, 3A & 3B) N/A, NOT APPLICABLE. THIS PERMIT IS FOR
 INTERIOR RENOVATIONS ONLY. UNDER PARKING RE-SEALING/
 RESTRIPING SEPARATE PERMIT. CONTRACTOR LETTER DATED MAY
 12TH/ 2022.
  
  
 4)N/A. NOT APPLICABLE. THIS PERMIT IS FOR INTERIOR
 RENOVATIONS ONLY. CONTRACTOR LETTER DATED MAY 12TH/
 2022. AS-101A, POOL.
  
 5A) 2ND REQUEST. RESPONSE STATES THAT FOR A R-1 HOTEL
 OCCUPANCY DRINKING FOUNTAINS ARE NOT REQUIRED PER THE
 2017 FBC-PLUMBING CODE. THIS IS TRUE BUT THE DRINKING
 FOUNTAINS ARE REQUIRED FOR A3 OCCUPANCY LECTURE HALLS,
 EXHIBITION HALLS AND AUDITORIUMS. DRINKING FOUNTAINS
 ARE ALSO REQUIRED FOR A4 OCCUPANCIES POOL AND POOL
 DECKS. A2 OCCUPANCIES RESTAURANTS AND BARS MAY NOT
 REQUIRE DRINKING FOUNTAINS IF THE PLAN STATES THEY ARE
 USING SECTION 410.4 WHERE RESTAURANTS PROVIDE DRINKING
 WATER IN A CONTAINER FREE OF CHARGE, THIS WAS NOTED ON
 THE LIFE SAFETY PLAN NOR PLUMBING SHEETS.
 1ST ROUND OF COMMENTS. SHEET A-102 THE FITNESS ROOM 107
 SHOWS THE USE OF A WATER COOLER RATHER THAN DRINKING
 FOUNTAINS. 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 5B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 5C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 5D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 5E) 211.3 MORE THAN MINIMUM NUMBER. WHERE MORE THAN THE
 MINIMUM NUMBER OF DRINKING FOUNTAINS SPECIFIED IN
 211.2ARE PROVIDED, 50 PERCENT OF THE TOTAL NUMBER OF
 DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND 50 PERCENT SHALL OF THE TOTAL NUMBER
 OF DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.7.
  
 6) DISPROPORTIONATE COST LETTER REVIEWED. THE 202.4.1.
 DISPROPORTIONATE COST IS FIGURED ON THE TOTAL CONTRACT
 VALUE, OVER AND ABOVE THE CONTRACT VALUE. THIS ISSUE
 HAS TO BE DISCUSSED WITH THE BUILDING OFFICIAL BEFORE
 FURTHER COMMENT. RESEALING & RESTRIPING OF THE PARKING
 LOT NOT INCLUDED IN CONTRACTOR COST BREAKDOWN NOR WERE
 THERE DOLLAR AMOUNTS SHOWN WHERE THE COST FOR
 DISPROPORTION MAKE UP 21% OF THE BUDGET.
 1ST ROUND OF COMMENTS. NEW COMMENT 11/09/2021 TO
 ADDRESS THE DESIGNER OF RECORD E-MAIL. FLORIDA
 ACCESSIBILITY CODE SECTION: DISPROPORTIONATE COST
 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% ($585,000.00 X
 0.20= $117,000.00 UP TO) DISPROPORTIONATE FUNDS LISTED
 FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN
 THE ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE
 COST OF THE 2020 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-04-12 Cont ID  
Sent By jwitmer Date 2022-04-12 Time 15:36 Rev Time 0.00
Received By jwitmer Date 2022-04-12 Time 11:21 Sent To  
Notes
2022-04-12 15:36:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW/ 12/18/2020
 W. P. B. PERMIT: 20120964
 ADD: 1301 BELVEDERE RD.
 CONT: OCC CONSTRUCTION LLC/ CLARK S. HARDEN- QUALIFIER
 TEL: 561-281-0454
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 12TH/2022
 ACTION: DENIED
 1) THE LS-101 GROUND FLOOR LIFE SAFETY PLAN, A-102 &
 A-102A DOES NOT SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE (SUBMITTED ON 12/18/2020 THE
 2020 FBC FAMILY OF CODES (ACCESSIBILITY INCLUDED) WAS
 ADOPTED STATEWIDE ON 12/31/2020.
  
 1A) SEMI-COMPLIED. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 1B)2ND REQUEST. THE HUDDLE SPOTS 123 AND HI-TOPS 128 DO
 NOT SHOW COMPLIANCE WITH THE HEIGHT REQUIREMENT FOUND
 IN 902.3 FOR DINING AND OR WORK SURFACES.
 1ST ROUND COMMENTS. 226.2 DISPERSION. DINING SURFACES
 AND WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 1C) COMPLIED.
  
 1D) SEMI-COMPLIED I DO NOT SEE A CUT SECTION THROUGH
 THE BAR SHOWING COMPLIANCE WITH 902.2 OR 902.3 OF THE
 2017 ACCESSIBILITY CODE. SEMI-COMPLIED.
 1ST ROUND COMMENTS. 902.1. DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, HIGH TOPS, TABLES, LUNCH COUNTERS,
 AND BOOTHS. EXAMPLES OF WORK SURFACES INCLUDE WRITING
 SURFACES, STUDY CARRELS, STUDENT LABORATORY STATIONS,
 BABY CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ADA
 SCOPING PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 1E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1F)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1G-H) COMPLIED.
  
 2A) SEMI-COMPLIED. OCCUPANCY INDICATES HOTELS TRANSIENT
 R-1. MISSING OCCUPANCIES ARE EITHER:
 RESTAURANT A-2 OR BUSINESS LESS THAN 50 OCCUPANTS,
 BUSINESS: FRONT COUNTER AND ASSOCIATED OFFICE AREAS
 GYMNASIUM: A-3
 POOL AND POOL DECK: A-4
  
 MISSING THE SQUARE FOOTAGE FOR EACH OCCUPANCY TYPE,
 OCCUPANT LOAD FOR EACH OCCUPANCY.
 1ST ROUND OF COMMENTS. SHEET LS-102 2NSD FLOOR LIFE
 SAFETY PLAN. 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION: 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS AND OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 CODE DATA/ BUILDING DATA
 OCCUPANCY GROUP
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 2B)(1) RESPONSE STATES THAT FOR A R-1 HOTEL OCCUPANCY
 DRINKING FOUNTAINS ARE NOT REQUIRED PER THE 2017
 FBC-PLUMBING CODE. THIS IS TRUE BUT THE DRINKING
 FOUNTAINS ARE REQUIRED FOR A3 OCCUPANCY LECTURE HALLS,
 EXHIBITION HALLS AND AUDITORIUMS. DRINKING FOUNTAINS
 ARE ALSO REQUIRED FOR A4 OCCUPANCIES POOL AND POOL
 DECKS. A2 OCCUPANCIES RESTAURANTS AND BARS MAY NOT
 REQUIRE DRINKING FOUNTAINS IF THE PLAN STATES THEY ARE
 USING SECTION 410.4 WHERE RESTAURANTS PROVIDE DRINKING
 WATER IN A CONTAINER FREE OF CHARGE, THIS WAS NOTED ON
 THE LIFE SAFETY PLAN NOR PLUMBING SHEETS.
 THE OTHER ISSUE IS WITH SHEET A-106 ELEVATION 2
 DRINKING FOUNTAIN WITH BOTTLE FILLER. PLEASE SEE IN THE
 2017 FBC-PLUMBING CODE SECTION 410. 4 FOR SUBSTITUTION
 AND PLUMBING COMMENTS.
 1ST ROUND OF COMMENTS. 2017 FBC-ACCESSIBILITY CODE.
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 2ND REQUEST.(2B(2) PROTRUDING OBJECTS 307.2 PROTRUSION
 LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 2ND REQUEST. 2B)(3) 602.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 2ND REQUEST. 2B)(4) SPOUT OUTLETS/ DRINKING FOUNTAINS.
 2017 ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 3) AS-101 NOTE# 3 INDICATES RESEAL AND RESTRIPE PARKING
 LOT. PROVIDE THE TOTAL PARKING SPACES AVAILABLE. SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE TABLE 208.2
 MINIMUM NUMBER OF REQUIRED ACCESSIBLE PARKING SPACES.
  
 3A) THE RESPONSE STATES THE INTENT IS TO RESEAL AND
 RESTRIPE THE PARKING LOT. PLEASE PROVIDE A PARKING
 DETAIL THAT IS COMPLIANCE WITH THE WEST PALM MUNI-CODE
 ARTICLE XV PARKING DETAIL, 94-485 ILLUSTRATES WITH
 MEASUREMENTS FOR DOUBLE STRIPE STALL PAINTING.
 1ST ROUND OF COMMENTS. 2017 ACCESSIBILITY CODE SECTION
 502.2 VEHICLE SPACES. EACH PARKING SPACE MUST BE AT
 LEAST 12 FEET WIDE, SHALL BE MARKED TO DEFINE THE
 WIDTH, AND SHALL HAVE AN ADJACENT ACCESS AISLE
 COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 3B) PLEASE PROVIDE ELEVATIONS FOR ALL ACCESS AISLES AND
 ACCESSIBLE PARKING SPACES. THIS IS IN COMPLIANCE WITH
 THE DISPROPORTIONATE COST, THE LAST THING ON THE LIST.
 1ST ROUND OF COMMENTS.502.4 ACCESS AISLE & PARKING
 SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND SURFACES.
 PARKING SPACES AND THE ACCESS AISLES SERVING THEM SHALL
 COMPLY WITH 302. ACCESS AISLES SHALL BE AT THE SAME
 LEVEL AS THE PARKING SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 4) 2ND REQUEST, AS-101A, PLEASE SHOW HOW AN ACCESSIBLE
 ENTRY INTO THE POOL IS TO OCCUR. NOTE 1 STATES TO
 REPAIR/ REFINISH POOL FINISH WORK IS BEING COMPLETE IN
 THE POOL PLEASE SHOW HOW COMPLIANCE WILL OCCUR WITH THE
 ACCESSIBILITY CODE.
 1ST ROUND OF COMMENTS. AS-101A POOL DECK. AT LEAST TWO
 ACCESSIBLE MEANS OF ENTRY SHALL BE PROVIDED FOR
 SWIMMING POOLS. ACCESSIBLE MEANS OF ENTRY SHALL BE
 SWIMMING POOL LIFTS COMPLYING WITH 1009.2; SLOPED
 ENTRIES COMPLYING WITH 1009.3; TRANSFER WALLS COMPLYING
 WITH 1009.4; TRANSFER SYSTEMS COMPLYING WITH 1009.5:
 AND POOL STAIRS COMPLYING WITH 1009.6. AT LEAST ONE
 ACCESSIBLE MEANS OF ENTRY PROVIDED SHALL COMPLY WITH
 1009.2 OR 1009.3.
  
 5A) 2ND REQUEST. RESPONSE STATES THAT FOR A R-1 HOTEL
 OCCUPANCY DRINKING FOUNTAINS ARE NOT REQUIRED PER THE
 2017 FBC-PLUMBING CODE. THIS IS TRUE BUT THE DRINKING
 FOUNTAINS ARE REQUIRED FOR A3 OCCUPANCY LECTURE HALLS,
 EXHIBITION HALLS AND AUDITORIUMS. DRINKING FOUNTAINS
 ARE ALSO REQUIRED FOR A4 OCCUPANCIES POOL AND POOL
 DECKS. A2 OCCUPANCIES RESTAURANTS AND BARS MAY NOT
 REQUIRE DRINKING FOUNTAINS IF THE PLAN STATES THEY ARE
 USING SECTION 410.4 WHERE RESTAURANTS PROVIDE DRINKING
 WATER IN A CONTAINER FREE OF CHARGE, THIS WAS NOTED ON
 THE LIFE SAFETY PLAN NOR PLUMBING SHEETS.
 1ST ROUND OF COMMENTS. SHEET A-102 THE FITNESS ROOM 107
 SHOWS THE USE OF A WATER COOLER RATHER THAN DRINKING
 FOUNTAINS. 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 5B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 5C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 5D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 5E) 211.3 MORE THAN MINIMUM NUMBER. WHERE MORE THAN THE
 MINIMUM NUMBER OF DRINKING FOUNTAINS SPECIFIED IN
 211.2ARE PROVIDED, 50 PERCENT OF THE TOTAL NUMBER OF
 DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND 50 PERCENT SHALL OF THE TOTAL NUMBER
 OF DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.7.
  
 6) 2ND REQUEST. THE 202.4.1. DISPROPORTIONATE COST IS
 FIGURED ON THE TOTAL CONTRACT VALUE, OVER AND ABOVE THE
 CONTRACT VALUE. THIS ISSUE HAS TO BE DISCUSSED WITH THE
 BUILDING OFFICIAL BEFORE FURTHER COMMENT. RESEALING &
 RESTRIPING OF THE PARKING LOT NOT INCLUDED IN
 CONTRACTOR COST BREAKDOWN NOR WERE THERE DOLLAR AMOUNTS
 SHOWN WHERE THE COST FOR DISPROPORTION MAKE UP 21% OF
 THE BUDGET.
 1ST ROUND OF COMMENTS. NEW COMMENT 11/09/2021 TO
 ADDRESS THE DESIGNER OF RECORD E-MAIL. FLORIDA
 ACCESSIBILITY CODE SECTION: DISPROPORTIONATE COST
 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% ($585,000.00 X
 0.20= $117,000.00 UP TO) DISPROPORTIONATE FUNDS LISTED
 FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN
 THE ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE
 COST OF THE 2020 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By jwitmer Date 2021-09-07 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2021-09-07 Time 13:13 Sent To  
Notes
2021-09-07 15:27:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120964
 ADD: 1301 BELVEDERE RD.
 CONT: OCC CONSTRUCTION LLC
 TEL: 561-281-0454
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 07/2021
 ACTION: DENIED
 1) THE LS-101 GROUND FLOOR LIFE SAFETY PLAN, A-102 &
 A-102A DOES NOT SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE.
  
 1A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 1B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 1C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS HIGH TOPS, AND OUTDOOR DINING
 AREAS.
  
 1D) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 HIGH TOPS, TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES
 OF WORK SURFACES INCLUDE WRITING SURFACES, STUDY
 CARRELS, STUDENT LABORATORY STATIONS, BABY CHANGING AND
 OTHER TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 1E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1F)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1G) BUFFET AREA ROOM 131 DOES NOT SHOW COMPLIANCE THE
 2017 FBC-ACCESSIBILITY CODE 904.5 FOOD SERVICE LINES.
 SECTIONS 904.5.1 THROUGH 904.6.
  
 1H) THE RECEPTION AREA IT MAY APPEAR THERE MAYBE A
 DROPPED PORTION OF THE DESK WITH SIDE APPROACH. IF SIDE
 APPROACH NOT INDICATED AS A SIDE APPROACH. CHECK
 WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 HOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
 904.4 SERVICE COUNTERS. SERVICE COUNTERS SHALL COMPLY
 WITH 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTERTOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTERTOP.
  
 2A) SHEET LS-102 2NSD FLOOR LIFE SAFETY PLAN. 107.3.5
 MINIMUM PLAN REVIEW CRITERIA
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION: 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS AND OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA:
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 CODE DATA/ BUILDING DATA
 OCCUPANCY GROUP
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 2B)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 2B)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 2B)(3) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 2B)(4) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 3) AS-101 NOTE# 3 INDICATES RESEAL AND RESTRIPE PARKING
 LOT. PROVIDE THE TOTAL PARKING SPACES AVAILABLE. SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESS. CODE TABLE 208.2
 MINIMUM NUMBER OF REQUIRED ACCESSIBLE PARKING SPACES.
  
 3A) 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE
 SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 FEET
 WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND SHALL
 HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 3B) 502.4 ACCESS AISLE & PARKING SPACE SAME LEVEL/
 502.4, FLOOR AND GROUND SURFACES. PARKING SPACES AND
 THE ACCESS AISLES SERVING THEM SHALL COMPLY WITH 302.
 ACCESS AISLES SHALL BE AT THE SAME LEVEL AS THE PARKING
 SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 4) AS-101A POOL DECK. AT LEAST TWO ACCESSIBLE MEANS OF
 ENTRY SHALL BE PROVIDED FOR SWIMMING POOLS. ACCESSIBLE
 MEANS OF ENTRY SHALL BE SWIMMING POOL LIFTS COMPLYING
 WITH 1009.2; SLOPED ENTRIES COMPLYING WITH 1009.3;
 TRANSFER WALLS COMPLYING WITH 1009.4; TRANSFER SYSTEMS
 COMPLYING WITH 1009.5: AND POOL STAIRS COMPLYING WITH
 1009.6. AT LEAST ONE ACCESSIBLE MEANS OF ENTRY PROVIDED
 SHALL COMPLY WITH 1009.2 OR 1009.3.
  
 5A ) SHEET A-102 THE FITNESS ROOM 107 SHOWS THE USE OF
 A WATER COOLER RATHER THAN DRINKING FOUNTAINS. 2017
 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 5B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE
 MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION
 PATH.
  
 5C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 5D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 5E) 211.3 MORE THAN MINIMUM NUMBER. WHERE MORE THAN THE
 MINIMUM NUMBER OF DRINKING FOUNTAINS SPECIFIED IN
 211.2ARE PROVIDED, 50 PERCENT OF THE TOTAL NUMBER OF
 DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND 50 PERCENT SHALL OF THE TOTAL NUMBER
 OF DRINKING FOUNTAINS PROVIDED SHALL COMPLY WITH 602.7.
  
 6) NEW COMMENT 11/09/2021 TO ADDRESS THE DESIGNER OF
 RECORD E-MAIL. FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% ($585,000.00 X 0.20= $117,000.00 UP TO)
 DISPROPORTIONATE FUNDS LISTED FOR EACH ELEMENT WHERE
 THE FUNDS ARE BEING SPENT AND IN THE ORDER LISTED IN
 SECTION 202.4.1 DISPROPORTIONATE COST OF THE 2020
 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
  
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 17:03 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 16:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-30 Cont ID  
Sent By jleahy Date 2021-09-30 Time 13:04 Rev Time 0.00
Received By jleahy Date 2021-09-30 Time 13:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-06-08 Cont ID  
Sent By cwalker Date 2022-06-08 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-01 Cont ID  
Sent By cwalker Date 2022-04-01 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-19 Cont ID  
Sent By pleduc Date 2021-08-19 Time   Rev Time 0.00
Received By pleduc Date 2021-08-17 Time 11:34 Sent To  
Notes
2021-08-17 13:25:04FIRE PROVISO:
 THE HOOD & SUPPRESSION SYSTEMS SHALL BE INSTALLED
 UNDER SEPARATE PERMITS & SHOP DRAWINGS
  
  
 ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 ENSURE EXITS TRAVEL PATHS & EXITS ARE MAINTAINED AND
 UNOBSTRUCTED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 10:13 Rev Time 0.00
Received By rwbrown Date 2022-06-29 Time 10:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 10:15 Rev Time 0.00
Received By rwbrown Date 2022-06-07 Time 07:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-13 Cont ID  
Sent By pvalenti Date 2022-04-13 Time 16:10 Rev Time 0.00
Received By pvalenti Date 2022-03-31 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-30 Cont ID  
Sent By jleahy Date 2021-09-30 Time 13:04 Rev Time 0.00
Received By jleahy Date 2021-08-16 Time 14:58 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-09-07 Cont ID  
Sent By jwitmer Date 2021-09-07 Time 15:28 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-07-06 Cont ID  
Sent By medwards Date 2022-06-11 Time 12:11 Rev Time 0.00
Received By medwards Date 2022-06-11 Time 12:11 Sent To  
Notes
2022-06-11 12:13:47 
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-04-11 Cont ID  
Sent By medwards Date 2022-04-11 Time 10:29 Rev Time 0.00
Received By medwards Date 2022-04-11 Time 10:29 Sent To  
Notes
2022-04-11 10:31:47THE MECHANICAL DRAWINGS SUBMITTED ARE FOR DEMO FOR THE
 FIRSTFLOOR ONLY, PLEASE SUBMIT THE MECHANICAL DESIGN
 FOR THE CHANGES. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-31 Cont ID  
Sent By medwards Date 2021-08-31 Time 09:27 Rev Time 0.00
Received By medwards Date 2021-08-31 Time 09:27 Sent To  
Notes
2021-08-31 09:28:55PLEASE PROVIDE A DETAIED SCOPE OF WORK FOR THE
 MECHANICAL SYSTEMS OF THIS PROJECT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 10:13 Rev Time 0.00
Received By rwbrown Date 2022-06-29 Time 10:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-04-12 Cont ID  
Sent By jesmith Date 2022-04-12 Time 16:56 Rev Time 0.00
Received By jesmith Date 2022-04-07 Time 13:53 Sent To  
Notes
2022-04-12 16:53:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20120964 1301 BELVEDERE RD
  
 2ND REVIEW
 PLUMBING /GAS COMMENTS: DENIED
 THERE WAS NO RESPONSE OR ACKNOWLEDGEMENT OF THE
 PLUMBING/GAS COMMENTS FROM REVIEW 1.
  
 1.SECOND REQUEST: A SERVICE SINK IS REQUIRED PER FBC PL
 TABLE 403.1.
 TO BE CLEAR, REFER TO COMMENT 7 BELOW; PROVIDE A
 PLUMBING FIXTURE SCHEDULE NOTING REQUIRED PLUMBING
 FIXTURES AND QUANTITIES AS REQUIRED BY FBC PL TABLE
 403.1 FOR THE OCCUPANCY (OCCUPANCIES) AND THE ACTUAL
 FIXTURES AND QUANTITIES PROVIDED.
  
 2. SECOND REQUEST: PROPOSED LOBBY AREA HAS A LARGE
 DINING AREA AND PHYSICAL FITNESS ROOM AND APPEARS TO
 FIT THE DESCRIPTION FOR ASSEMBLY. PLAN SHEET T-001
 INDICATES R-1 OCCUPANCY. PER WPB FBC 107.2.1, CLARIFY
 OCCUPANCY TYPES AND LOADS.
  
 3. SECOND REQUEST: PROPOSED SECOND FLOOR IS MADE UP OF
 MEETING ROOMS, LOUNGE AREAS AND LECTURE HALLS AND
 APPEARS TO FIT THE DESCRIPTION FOR ASSEMBLY. PER WPB
 FBC 107.2.1, CLARIFY OCCUPANCY TYPES AND LOADS.
  
 4. SECOND REQUEST: PER FBC PL TABLE 403.1 AND FBC ACC
 211.2, PROVIDE DRINKING FOUNTAIN(S) COMPLYING WITH FBC
 PL 410.3 AND FBC ACC 602.1 THROUGH 606.7, 305, 306 AND
 307.2.
 PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING COMPLIANCE
 WITH FBC ACC 602.1 THROUGH 606.7, 305, 306 AND 307.2.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 EXCEPTIONS:
 ...A SINGLE DRINKING FOUNTAIN WITH TWO SEPARATE SPOUTS
 THAT COMPLIES WITH THE REQUIREMENTS FOR PEOPLE WHO USE
 A WHEELCHAIR AND STANDING PERSONS SHALL BE PERMITTED TO
 BE SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS.
  
 5. N/A-PLAN SHEET T-001 INDICATES ALL CODES ARE 2017
 EDITION. PERMIT APPLICATION IS DATED 8/16/2021. PER WPB
 FBC 107.2.1, FLORIDA BUILDING CODES SHALL BE 2020,
 SEVENTH EDITION. N/A; IT IS RECOGNIZED THE PERMIT WAS
 APPLIED FOR PRIOR TO IMPLEMENTATION OF THE 2020 FBC.
  
 6. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE ON THE
 LIFE SAFETY PLANS THE OCCUPANCY GROUP AND OCCUPANCY
 LOAD. THE POOL AREA SHALL BE CONSIDERED. SEE FBC PL
 403.6.
  
 7. SECOND REQUEST: PER WPB FBC 107.2.1 AND 107.3.5.1.3
 PROVIDE
 ...A) MINIMUM PLUMBING FACILITIES
 ...B) FIXTURE REQUIREMENTS
 SEE COMMENT 1
  
 8A. SECOND REQUEST: THE FOLLOWING NOTATIONS ARE MADE ON
 THE PLANS:
 ***A) A-001; NOTE: REMOVE EXISTING HOOD AND ALL KITCHEN
 EQUIPMENT TO ACCOMMODATE NEW EQUIPMENT CONFIGURATION.
 SEE PROPOSED FLOOR PLANS.
 ***B) A-102A; NOTE: KITCHEN DESIGN AND BUFFET AREA BY
 FOOD AND BEVERAGE CONSULTANT. REFER TO SHEET A-102B FOR
 REFERENCE
 ***C)A-101 (PROPOSED FLOOR PLAN) NOTES EXISTING KITCHEN
 PER WPB FBC 107.2.1, PROVIDE CLARIFICATION
  
 8B. SECOND REQUEST: PLAN SHEET A-102B; ENLARGED KITCHEN
 PLAN FOR REFERENCE ONLY: PER WPB FBC 105.1, THE
 APPROPRIATE PLANS AND PERMITS ARE REQUIRED FOR NEW
 EQUIPMENT REQUIRING MECHANICAL, ELECTRICAL, PLUMBING
 (WATER AND DRAIN) OR GAS (SEE COMMENT 8C) CONNECTIONS
 IN THE KITCHEN; THIS INCLUDES REPLACEMENT OF EXISTING
 WITH NEW.
 ***A) PER WPB FBC 107.2.1, REVISE KITCHEN EQUIPMENT
 SCHEDULE TO INDICATING ANY WATER, DRAIN, GAS
 CONNECTIONS AS WELL AS ANY INCLUSIVE OF NEW AND
 EXISTING. NEW EQUIPMENT THAT REQUIRES WATER, DRAIN
 AND/OR GAS (SEE COMMENT 8C) CONNECTIONS SHALL BE
 CLARIFIED, NOTED ON THE SCHEDULE AND DETAILS PROVIDED
 PER WPB FBC 107.2.1. PLANS SHALL INCLUDE ANY PIPING
 INFRASTRUCTURE EXISTING AND NEW REQUIRED TO PROVIDE
 FULL AND ACCURATE INFORMATION (SEE WPB FBC 107.2.1 AND
 107.3.5) AND BE SUBMITTED FOR PLUMBING IN ACCORDANCE
 WITH WPB FBC 107. 3.5.1.3, AND GAS IN ACCORDANCE WITH
 WPB FBC 107.3.5.1.5.
  
 8C. SECOND REQUEST: SEE COMMENT 8B; PLAN SHEET A-102B
 INDICATES TAG 1A DOUBLE OVEN AS NEW. PER WPB FBC
 107.2.1, INDICATE THE ENERGY SOURCE FOR THIS UNIT. IF
 SOURCE IS GAS, A PLAN TO INCLUDE BUT IS NOT LIMITED TO
 SCOPE OF WORK, EQUIPMENT, PIPING, SIZING CALCULATIONS,
 COMBUSTION AIR. THIS INCLUDES EXISTING INFRASTRUCTURE
 AS WELL AS NEW.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-23 Cont ID  
Sent By pvalenti Date 2021-09-23 Time 13:08 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 15:18 Sent To  
Notes
2021-09-23 13:17:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20120964 1301 BELVEDERE RD
  
 1ST REVIEW
 PLUMBING /GAS COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1.
  
 2. PROPOSED LOBBY AREA HAS A LARGE DINING AREA AND
 PHYSICAL FITNESS ROOM AND APPEARS TO FIT THE
 DESCRIPTION FOR ASSEMBLY. PLAN SHEET T-001 INDICATES
 R-1 OCCUPANCY. PER WPB FBC 107.2.1, CLARIFY OCCUPANCY
 TYPES AND LOADS.
  
 3. PROPOSED SECOND FLOOR IS MADE UP OF MEETING ROOMS,
 LOUNGE AREAS AND LECTURE HALLS AND APPEARS TO FIT THE
 DESCRIPTION FOR ASSEMBLY. PER WPB FBC 107.2.1, CLARIFY
 OCCUPANCY TYPES AND LOADS.
  
 4. PER FBC PL TABLE 403.1 AND FBC ACC 211.2, PROVIDE
 DRINKING FOUNTAIN(S) COMPLYING WITH FBC PL 410.3 AND
 FBC ACC 602.1 THROUGH 606.7, 305, 306 AND 307.2.
 PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING COMPLIANCE
 WITH FBC ACC 602.1 THROUGH 606.7, 305, 306 AND 307.2.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 EXCEPTIONS:
 ...A SINGLE DRINKING FOUNTAIN WITH TWO SEPARATE SPOUTS
 THAT COMPLIES WITH THE REQUIREMENTS FOR PEOPLE WHO USE
 A WHEELCHAIR AND STANDING PERSONS SHALL BE PERMITTED TO
 BE SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS.
  
 5. PLAN SHEET T-001 INDICATES ALL CODES ARE 2017
 EDITION. PERMIT APPLICATION IS DATED 8/16/2021. PER WPB
 FBC 107.2.1, FLORIDA BUILDING CODES SHALL BE 2020,
 SEVENTH EDITION.
  
 6. PER WPB FBC 107.2.1, PROVIDE ON THE LIFE SAFETY
 PLANS THE OCCUPANCY GROUP AND OCCUPANCY LOAD. THE POOL
 AREA SHALL BE CONSIDERED. SEE FBC PL 403.6.
  
 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3 PROVIDE
 ...A)MINIMUM PLUMBING FACILITIES
 ...B)FIXTURE REQUIREMENTS
  
 8A.THE FOLLOWING NOTATIONS ARE MADE ON THE PLANS:
 ?A)A-001; NOTE: REMOVE EXISTING HOOD AND ALL KITCHEN
 EQUIPMENT TO ACCOMMODATE NEW EQUIPMENT CONFIGURATION.
 SEE PROPOSED FLOOR PLANS.
 ?B)A-102A; NOTE: KITCHEN DESIGN AND BUFFET AREA BY FOOD
 AND BEVERAGE CONSULTANT. REFER TO SHEET A-102B FOR
 REFERENCE
 ?C)A-101 (PROPOSED FLOOR PLAN) NOTES EXISTING KITCHEN
 PER WPB FBC 107.2.1, PROVIDE CLARIFICATION
  
 8B. PLAN SHEET A-102B; ENLARGED KITCHEN PLAN FOR
 REFERENCE ONLY: PER WPB FBC 105.1, THE APPROPRIATE
 PLANS AND PERMITS ARE REQUIRED FOR NEW EQUIPMENT
 REQUIRING MECHANICAL, ELECTRICAL, PLUMBING (WATER AND
 DRAIN) OR GAS (SEE COMMENT 8C) CONNECTIONS IN THE
 KITCHEN; THIS INCLUDES REPLACEMENT OF EXISTING WITH
 NEW.
 PER WPB FBC 107.2.1, REVISE KITCHEN EQUIPMENT SCHEDULE
 TO INDICATING ANY WATER, DRAIN, GAS CONNECTIONS AS WELL
 AS ANY INCLUSIVE OF NEW AND EXISTING. NEW EQUIPMENT
 THAT REQUIRES WATER, DRAIN AND/OR GAS (SEE COMMENT 8C)
 CONNECTIONS SHALL BE CLARIFIED, NOTED ON THE SCHEDULE
 AND DETAILS PROVIDED PER WPB FBC 107.2.1. PLANS SHALL
 INCLUDE ANY PIPING INFRASTRUCTURE EXISTING AND NEW
 REQUIRED TO PROVIDE FULL AND ACCURATE INFORMATION (SEE
 WPB FBC 107.2.1 AND 107.3.5) AND BE SUBMITTED FOR
 PLUMBING IN ACCORDANCE WITH WPB FBC 107. 3.5.1.3, AND
 GAS IN ACCORDANCE WITH WPB FBC 107.3.5.1.5.
  
 8C. SEE COMMENT 8B; PLAN SHEET A-102B INDICATES TAG 1A
 DOUBLE OVEN AS NEW. PER WPB FBC 107.2.1, INDICATE THE
 ENERGY SOURCE FOR THIS UNIT. IF SOURCE IS GAS, A PLAN
 TO INCLUDE BUT IS NOT LIMITED TO SCOPE OF WORK,
 EQUIPMENT, PIPING, SIZING CALCULATIONS, COMBUSTION AIR.
 THIS INCLUDES EXISTING INFRASTRUCTURE AS WELL AS NEW.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 20120964 1301 BELVEDERE RD
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 09:46 Rev Time 0.00
Received By rwbrown Date 2022-06-29 Time 09:46 Sent To  
Notes
2022-06-11 12:15:07DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME
2022-06-10 17:04:37ELECTRICAL SIGNATURE APPROVED JLEAHY
2022-06-09 16:47:22SIGNATURES FOR PLUMBING/GAS ARE VALID. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-13 Cont ID  
Sent By pvalenti Date 2022-04-13 Time 16:10 Rev Time 0.00
Received By pvalenti Date 2022-04-13 Time 16:05 Sent To  
Notes
2022-04-12 16:59:32NO PLUMBING PLANS SUBMITTED. JS
2022-04-11 10:32:37DIGITAL SIGNATURES FOR THE MECHANICAL SHEETS SUBMITTED
 ARE APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-31 Cont ID  
Sent By medwards Date 2021-08-31 Time 09:32 Rev Time 0.00
Received By medwards Date 2021-08-31 Time 09:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-06-17 Cont ID  
Sent By llouie Date 2022-06-17 Time   Rev Time 0.00
Received By llouie Date 2022-06-17 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-11 Cont ID  
Sent By llouie Date 2022-04-11 Time   Rev Time 0.00
Received By llouie Date 2022-04-11 Time   Sent To  
Notes
2022-04-11 14:19:51* SEPARATE PERMITS REQUIRED FOR EXTERIOR WORK.
  
 * LANDSCAPE IMPROVEMENTS REQUIRED PER RESOLUTION NO.
 338-20.
  
 REFERENCE: HOLIDAY INN EXPRESS OCPD.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-08-26 Cont ID  
Sent By llouie Date 2021-08-26 Time   Rev Time  
Received By llouie Date 2021-08-26 Time   Sent To  
Notes
***NONE***