Plan Review Details - Permit 20120918
Plan Review Stops For Permit 20120918
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-04-26 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2021-04-26 Time 15:00 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-02-10 Cont ID  
Sent By jwitmer Date 2021-02-10 Time 09:01 Rev Time 0.00
Received By jwitmer Date 2021-02-10 Time 09:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-01-25 Cont ID  
Sent By jwitmer Date 2021-01-25 Time 12:14 Rev Time 0.00
Received By jwitmer Date 2021-01-25 Time 08:56 Sent To  
Notes
2021-01-25 12:14:12COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-19 Cont ID  
Sent By jwitmer Date 2021-05-19 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2021-05-19 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-26 Cont ID  
Sent By jwitmer Date 2021-04-26 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2021-04-26 Time 15:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-25 Cont ID  
Sent By jwitmer Date 2021-01-25 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2021-01-25 Time 08:57 Sent To  
Notes
2021-01-25 12:13:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120918
 ADD: 509 21ST. STREET
 CONT: PATTERSON CONSTRUCTION
 TEL: 561-437-3059
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 25TH/ 2021
 ACTION: DENIED
  
 1) THE PLANS AND PERMIT APPLICATION INDICATE THE WORK
 TO BE PREFORMED AT THIS LOCATION IS A PHASED PROJECT.
 THE SHEET A-3.1 STATES THAT THERE IS ONLY 280 SQUARE
 FEET OF WORK TO BE COMPLETED WITH A VALUE OF $200,
 000.00 DOLLARS IN VALUE. THE WORK AREA METHOD IS TO
 IDENTIFY ON THE CONSTRUCTION DOCUMENTS WHERE THIS AREA
 IS TO OCCUR. REPLACEMENT OR REPAIRS OF FLOOR JOIST, AND
 THE CONCRETE RESTORATION AND SQUARE FOOTAGE IN EACH OF
 THESE AREAS. PLEASE ALSO REVIEW IN THE 2017
 FBC-EXISTING BUILDING CODE SECTION 907.4.2 SUBSTANTIAL
 IMPROVEMENTS INCLUDE STRUCTURAL ALTERATIONS THAT HAVE
 BEEN OR PROPOSED WITHIN A 5-YEAR PERIOD.
  
 2A) MISSING IS A LIFE SAFETY PLAN FOR THE BASEMENT AND
 FIRST FLOOR LEVEL.
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
  
 MISSING CODE DATA:
 OCCUPANCY GROUP
 MINIMUM TYPE OF CONSTRUCTION
 FIRE RESISTANCE SEPARATION
 FIRE SPRINKLERED OR NOT.
  
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 CODE DATA/ BUILDING DATA
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 2B) WITHOUT THE SQUARE FOOTAGE OF EACH FLOOR AND THE
 OCCUPANT LOAD FACTOR FOR EACH AREA THE TOTAL OCCUPANT
 LOAD CAN NOT BE DETERMINED. THIS PROPOSED ALTERATION
 MAY QUALIFY AS A THRESHOLD PROJECT F. S. 553.71(7)
 THRESHOLD BUILDING.
  
 2C) SINCE THE PLANS SHOW BOTH FLOOR JOIST REPAIR AND
 CONCRETE COLUMN REPAIRS ANY MANY REPEAT INSPECTIONS
 THIS IF NOT A THRESHOLD BUILDING WOULD QUALIFY FOR
 RESIDENT INSPECTOR PROGRAM. FURTHER INFORMATION THROUGH
 PLAN DOCUMENTATION OF FLOOR JOIST REPAIR AND OR
 REPLACEMENT AS WELL AS CONCRETE RESTORATION LOCATION IS
 REQUIRED TO DETERMINE CANDIDACY FOR THE RESIDENT
 INSPECTOR PROGRAM.
  
 3) SHEET A-3.1/ PROPOSED BASEMENT FLOOR PLAN:
 3A) THIS PLAN SHOWS THE EXTERIOR STAIR REMOVED FROM THE
 MENS RESTROOM. BACK OF THE CHURCH THERE IS TO EXISTING
 WOODEN STAIRS LEADING UP TO THE 1ST FLOOR. JUST TO THE
 SIDE OF THE CHAPEL ALTER THERE IS A EXIT SIGN TO THE
 BACK OF HOUSE 2 STAIRS. THE PRIEST OFFICE DOOR WHEN IN
 THE OPEN POSITION BLOCKS EGRESS TO THE BACK OF HOUSE
 STAIRS. 2017 1005.7.1.
  
 3B) THE BASEMENT BACK OF HOUSE STAIRS TO THE FIRST
 FLOOR HAVE AN OPEN STAIRWAY NOT ENCLOSED ON THE
 BASEMENT LEVEL. THE FIRST-FLOOR LEVEL BOTH STAIRS HAVE
 A LARGE ENCLOSED STAIR VESTIBULE, IS THIS ROOM USED FOR
 ANYTHING ELSE OTHER THAN PART OF THE VERTICAL EXIT FORM
 THIS BUILDING? THERE SHOULD NOT BE ANY STORAGE WITHIN
 THE ENCLOSED PORTION OF THE STAIR WAY. WHILE THE
 FIRST-FLOOR WEST EXIT LOBBY DOES SHOW AN EXIT SIGN TO
 THE EXTERIOR OF THE BUILDING. THE EAST STAIR YOU
 RE-ENTER THE CHURCH AFTER LEAVING THE ENCLOSED EXIT.
 HOW ARE YOU GOING TO STOP THE OCCUPANTS FROM USING THIS
 STAIR INCASE OF AN EMERGENCY?
  
 3C) THE PLANS RE SILENT AS TO WHAT FINISHES ARE GOING
 TO BE IN THE BACK OF HOUSE EXIT STAIRWAY? TABLE 803.11
 OF THE 2017 FBC-B.
  
 3D) IN THE FRONT ENTRYWAY OF THE CHURCH ON THE WEST
 SIDE OF THE BUILDING THERE IS A ROOM AND NOTE STATING
 THAT THE EXISTING STAIR TO BE REMOVED, REPLACED WITH
 WOOD FLOOR OVER EXISTING METAL POST. HOW ARE THE
 EXISTING METAL POST GOING TO TRANSFER THE FLOOR LOADS
 WITHOUT FLOOR JOIST AND HORIZONTAL BEAMS TRANSFERRING
 THE LOADS TO THE COLUMNS. THE BASEMENT S-1 NOR DOES
 SHEET S-2 FIRST FLOOR PLAN MAKE MENTION OF HOW THESE
 LOADS ARE GOING TO BE TRANSFERRED. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. THIS
  
 3E) THE PROPOSED BASEMENT FLOOR PLAN INDICATES ON THE
 NORTH-WALL NEW GLASS BLOCK PANELS IN 5 WINDOWS. SHEET
 A-6.2 THE NORTH ELEVATION ALSO REFERS TO THE EXISTING
 OPENINGS WITH NEW 8X8X4 INCH GLASS BLOCK, TYPICAL OF
 THE 5 OPENINGS. THE SITE PLAN SHOWED LESS THAN A FOOT
 TO THE PROPERTY LINE. TABLE 602 WILL REQUIRE THIS WALL
 TO BE 1-HOUR FIRE RATED. ONE FOOT AWAY FROM THE
 PROPERTY LINE WALL OPENINGS NOT ALLOWED. WITH THE
 14-FOOT ALLEY WAY ? OF THAT DISTANCE CAN BE USED OR 7
 FEET FROM THE CENTER LINE OF THE ALLEY ALLOWING 10 %
 OPENINGS IN THAT WALL LINE TAKEN FOR THAT FLOOR. THE
 VERTICAL HEIGHT IS TO BE TAKEN FROM GRADE TO THE
 CEILING LEVEL WHERE THE WINDOWS ARE LOCATED, FOR A
 NON-SPRINKLERED NON-PROTECTED OPENING. IF THE 10 % OF
 NON-PROTECTED OPENINGS IS EXCEEDED, FIRE RATED OPENINGS
 ALLOW 25% OF THE FIRST-FLOOR WALL TO HAVE OPENINGS IF
 THE GLASS BLOCK IS FIRE RATED IN ACCORDANCE 705.8.2,
 SECTION 716.6 AND TABLE 716.6 FOR
 EXTERIOR WALLS, OPENING PROTECTION OF ? HOUR FIRE
 RATING. WE WOULD NEED TO SEE THE UL FIRE RATED
 ASSEMBLY.
  
 4A) THE WEST ELEVATION SHOWS NEW IMPACT WINDOWS ON THE
 BASEMENT LEVEL. PLEASE SHOW COMPLIANCE WITH
 THE 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 4C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 4D) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By equinone Date 2021-04-30 Time 09:26 Rev Time 0.00
Received By equinone Date 2021-04-30 Time 09:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-22 Cont ID  
Sent By equinone Date 2021-01-22 Time 09:25 Rev Time 0.00
Received By equinone Date 2021-01-21 Time 15:18 Sent To  
Notes
2021-01-22 09:30:56CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 1) CALCULATED OCCUPANT LOAD IS LISTED AS 147 (SHEET
 A-3.2). WIRING METHODS MUST COMPLY WITH NEC 518.4 FOR
 ASSEMBLY OCCUPANCIES. PLEASE PROVIDE SPECS/NOTES/DETAIL
 TO SHOW COMPLIANCE WITH THIS ARTICLE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-04-27 Cont ID  
Sent By pleduc Date 2021-04-27 Time   Rev Time 0.00
Received By pleduc Date 2021-04-23 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-01-15 Cont ID  
Sent By pleduc Date 2021-01-15 Time   Rev Time 0.00
Received By pleduc Date 2021-01-15 Time 14:06 Sent To  
Notes
2021-01-15 14:57:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE FOLLOWWING COMMENTS ARE RELATED TO THE EGRESS
 CAPACITY OF THE BASEMENT AREA.
  
 I BELIEVE THERE WAS EXTENSIVE DISCUSSION ON THIS ISSUE
 SOMETIME AGO.
  
  
 1) SHEET A 3.1 - THE REAR VESTIBULE AREA REQUIRES
 ADDITIONAL EXIT SIGNAGE ALONG THE PATH OF TRAVEL .
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS
 NOT READILY APPARENT TO THE OCCUPANTS.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) SHEET A 3.1 & 3.2 - THE SINGLE REAR EXIT UP THE WOOD
 STAIRS DOES NOT PROVIDE FOR THE REQUIRED OCCUPANCY
 LOAD.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.3.1 OCCUPANT LOAD.
 7.3.1.1 SUFFICIENT CAPACITY.
 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR
 ANY STORY,
 BALCONY, TIER, OR OTHER OCCUPIED SPACE SHALL BE
 SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF.
  
 CONSIDER USING THE EAST STAIR AS AN EXIT AS WELL AND
 PROVIDE FOR AN EXIT SIGN OVER THE E.ROOM DOOR LEADING
 PEOPLE THROUGH THE OPEN ASSEMBLY AREA TO THE FRONT EXIT
 DOORS.
  
 THE E. ROOM DOOR WOULD BE REQUIRED TO SWING IN THE PATH
 OF TRAVEL.
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) SHEET A 3.1 & 3.2 - THE REAR EXIT DOOR LEADING TO
 THE VESTIBULE IS REQUIRED TO SWING IN THE PATH OF
 TRAVEL.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
  
 PLEASE ENSURE IT HAS THE REQUIRED EXIT PANIC HARDWARE
  
 PER NFPA 101,CH 13 EXISTING ASSEMBLY OCCUPANCIES
  
 13.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR
 LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING
 WITH
 7.2.1.7, UNLESS OTHERWISE PERMITTED BY ONE OF THE
 FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 13.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS
 DOORS AS PERMITTED IN 13.2.2.2.6.
  
 7.2.1.7 PANIC HARDWARE AND FIRE EXIT HARDWARE.
 7.2.1.7.1 WHERE A DOOR ASSEMBLY IS REQUIRED TO BE
 EQUIPPED WITH
 PANIC OR FIRE EXIT HARDWARE, SUCH HARDWARE SHALL MEET
 ALL OF THE
 FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, THE
 ACTUATING
 PORTION OF WHICH EXTENDS ACROSS NOT LESS THAN ONE-HALF
 OF THE
 WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED
 15 LBF (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND
 LATCHES.
  
 PLEASE REVIEW AND CORRECT.
  
  
 3A) SHEET A 3.1 & 3.2 - IT APPEARS TO BE AN OPENING
 FROM THE KITCHEN TO THE VESTIBULE. THIS OPENING CAN
 SERVE AS AN EAST EXIT PATH TO THE REAR STAIRS.
  
 AN EXIT SIGN WOULD BE REQUIRED AT THE KITCHEN OPENING
 AND AGAIN AT THE OPEING TO THE VESTIBULE.
  
  
  
 4) SHEET A 3.2 & E11 - THERE ARE NO INDICATIONS OF
 MEANS OF EGRESS ILLUMINATION
  
 PER NFPA 101 CH 7, MEANS OF EGRESS & CH 13 EXISTING
 ASSEMBLY OCCUPANCIES
  
 13.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF
 EGRESS, OTHER
 THAN FOR PRIVATE PARTY TENTS NOT EXCEEDING 1200 FT2
 (112 M2), SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE
 TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS
 BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR
 SUCH PERIODS OF TIME AS ARE NECESSARY TO MAINTAIN THE
 ILLUMINATION TO THE
 MINIMUM CRITERIA VALUES HEREIN SPECIFIED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 5) SHEET A 3.2 & E11 - THERE ARE NO INDICATIONS OF
 EMERGENCY LIGHTING
  
 PER NFPA 101 CH 7, MEANS OF EGRESS & CH 13 EXISTING
 ASSEMBLY OCCUPANCIES
  
 13.2.9 EMERGENCY LIGHTING.
 13.2.9.1 EMERGENCY LIGHTING, OTHER THAN THAT PERMITTED
 BY 13.2.9.3,
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 7.9.
 13.2.9.2 PRIVATE PARTY TENTS NOT EXCEEDING 1200 FT2
 (112 M2) SHALL
 NOT BE REQUIRED TO HAVE EMERGENCY LIGHTING.
 13.2.9.3 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD NOT
 EXCEEDING 300 AND USED EXCLUSIVELY FOR A PLACE OF
 WORSHIP SHALL
 NOT BE REQUIRED TO HAVE EMERGENCY LIGHTING.
  
 7.9 EMERGENCY LIGHTING.
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE
 FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS
 ADDRESSED IN SECTION
 11.7
 (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS
 OF THIS CODE
 (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS
 (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF
 ENCLOSURES, FOR WHICH THE
 FOLLOWING ALSO APPLY:
 (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO
 INCLUDE A
 STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF
 ENCLOSURE MECHANICAL VENTILATION EQUIPMENT.
 (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED
 FOR THE
 STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER
 SUPPLY.
 (6) NEW ACCESS-CONTROLLED EGRESS DOORS IN ACCORDANCE
 WITH 7.2.1.6.2
 7.9.1.2 FOR THE PURPOSES OF 7.9.1.1, EXIT ACCESS SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, AND PASSAGEWAYS
 LEADING TO AN EXIT. FOR THE PURPOSES OF 7.9.1.1, EXIT
 DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS, RAMPS, AISLES,
 WALKWAYS, AND ESCALATORS
 LEADING TO A PUBLIC WAY.
 7.9.1.3 WHERE MAINTENANCE OF ILLUMINATION DEPENDS ON
 CHANGING FROM
 ONE ENERGY SOURCE TO ANOTHER, A DELAY OF NOT MORE THAN
 10 SECONDS SHALL
 BE PERMITTED.
  
 PLEASE REVIEW AND CORRECT.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-19 Cont ID  
Sent By lmarchan Date 2021-05-19 Time 10:02 Rev Time 0.00
Received By lmarchan Date 2021-05-18 Time 13:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-18 Cont ID  
Sent By lmarchan Date 2021-05-18 Time 11:04 Rev Time 0.00
Received By lmarchan Date 2021-05-06 Time 13:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-30 Cont ID  
Sent By medwards Date 2021-04-30 Time 15:38 Rev Time 0.00
Received By medwards Date 2021-04-21 Time 07:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-01-25 Time 12:15 Rev Time 0.00
Received By lmarchan Date 2021-01-11 Time 08:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-01-25 Cont ID  
Sent By jwitmer Date 2021-01-25 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2021-01-25 Time 08:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By medwards Date 2021-04-30 Time 15:29 Rev Time 0.00
Received By medwards Date 2021-04-30 Time 15:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-14 Cont ID  
Sent By medwards Date 2021-01-14 Time 11:18 Rev Time 0.00
Received By medwards Date 2021-01-14 Time 11:18 Sent To  
Notes
2021-01-14 11:21:07PRIVISO: THE DUCTLESS MINI SPLIT EQUIPMENT THAT
 PRODUCES CONDENSATE SHALL BE PROVIDED WITH AN INLINE
 CHECK VALVE LOCATED IN THE DRAIN LINE, OR TRAP. FBC M
 307.2.4.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-04-28 Cont ID  
Sent By ccole Date 2021-04-28 Time 16:49 Rev Time 0.00
Received By ccole Date 2021-04-28 Time 16:36 Sent To  
Notes
2021-04-28 16:52:40THERE ARE NO PLUMBING ALTERATIONS OR FIXTURE
 REPLACEMENTS INDICATED ON THE PLANS. THE CONDENSATE
 PIPING FOR THE NEW AC SYSTEMS SHOWN ON THE PLUMBING
 PLANS SHALL BE INSTALLED BY THE MECHANICAL CONTRACTOR
 UNDER THE MECHANICAL SUB-PERMIT.
 CCOLE- 4/28/21

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-01-22 Cont ID  
Sent By ccole Date 2021-01-22 Time 12:27 Rev Time 0.00
Received By ccole Date 2021-01-22 Time 11:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By medwards Date 2021-04-30 Time 15:38 Rev Time 0.00
Received By medwards Date 2021-04-30 Time 15:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-14 Cont ID  
Sent By medwards Date 2021-01-14 Time 11:35 Rev Time 0.00
Received By medwards Date 2021-01-14 Time 11:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2021-05-19 Cont ID  
Sent By llouie Date 2021-05-19 Time   Rev Time 0.00
Received By llouie Date 2021-05-19 Time   Sent To  
Notes
2021-05-19 09:03:49* SEPARATE PERMITS REQUIRED FOR: PAVING/PARKING AREA,
 A/C, FENCING AND LANDSCAPING.
  
  
 REFERENCES:
  
 * LANDSCAPE PERMIT: #21050907

Review Stop Z ZONING
Rev No 3 Status F Date 2021-05-18 Cont ID  
Sent By llouie Date 2021-05-18 Time   Rev Time 0.00
Received By llouie Date 2021-05-18 Time   Sent To  
Notes
2021-05-18 08:45:15** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION FROM PERMITS
 TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ($214,000.00) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY. [1/15/2021 AND 4/26/2021 REPEAT
 COMMENT: NOT ADDRESSED. TO DATE, A SEPARATE LANDSCAPE
 PERMIT HAS NOT BEEN SUBMITTED. A LANDSCAPE PERMIT SHALL
 BE SUBMITTED PRIOR TO ZONING SIGN-OFF OF THIS PERMIT.]
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: MF14 (EXISTING CHURCH)
  
 * VALUE OF SCOPE: $200,000.00
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-04-26 Cont ID  
Sent By llouie Date 2021-04-26 Time   Rev Time 0.00
Received By llouie Date 2021-04-26 Time   Sent To  
Notes
2021-04-26 11:11:55** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE VALUE OF THE CONSTRUCTION FROM PERMITS
 TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ($214,000.00) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY. [1/15/2012 REPEAT COMMENT: NOT
 ADDRESSED. TO DATE, A SEPARATE LANDSCAPE PERMIT HAS NOT
 BEEN SUBMITTED. A LANDSCAPE PERMIT SHALL BE SUBMITTED
 PRIOR TO ZONING SIGN-OFF OF THIS PERMIT.]
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: MF14 (EXISTING CHURCH)
  
 * VALUE OF SCOPE: $200,000.00
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-15 Cont ID  
Sent By llouie Date 2021-01-15 Time   Rev Time  
Received By llouie Date 2021-01-15 Time   Sent To  
Notes
2021-01-15 14:02:17** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY IS REQUIRED.
  
 2.) EXTERIOR MODIFICATIONS DETECTED (I.E. COMPRESSOR
 UNITS). THE SITE PLAN SHALL PROVIDE THE NUMERICAL
 DISTANCE FROM ANY PROPOSED NEW STRUCTURE(S) TO THE
 PROPERTY LINE(S).
  
 3.) SOME AREAS PROVIDED IN THE SITE PLAN ARE NOT
 CONSISTENT WITH THE EXISTING SITE (I.E. AREA OF THE
 BULLETIN BOARD IS NOT PERVIOUS). THE UPDATED SURVEY
 SHOULD VERIFY THIS, AND ALL ELEMENTS WITHIN THE UPDATED
 SURVEY SHOULD MATCH THE SITE PLAN (EXCEPT FOR THOSE
 AREAS SHOWING CHANGE).
  
 4.) THE VALUE OF THE CONSTRUCTION FROM PERMITS
 TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ($214,000.00) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: MF14 (EXISTING CHURCH)
  
 * VALUE OF SCOPE: $200,000.00
  