Plan Review Details - Permit 20120912
Plan Review Stops For Permit 20120912
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-04-02 Cont ID  
Sent By rmcdouga Date 2021-04-02 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2021-04-02 Time 16:19 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By rmcdouga Date 2021-01-07 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2021-01-07 Time 16:03 Sent To  
Notes
2021-01-07 16:16:25PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-23 Cont ID  
Sent By rmcdouga Date 2021-04-23 Time 14:50 Rev Time 0.00
Received By rmcdouga Date 2021-04-22 Time 15:58 Sent To  
Notes
2021-04-23 14:50:20BUILDING PROVISO
  
 1) SUBMIT THE ACTUAL TEST REPORTS FOR THE LAMINATE AND
 TILE FLOORING SOUND INSULATION FOR APPROVAL PRIOR TO
 INSTALLING. THE REPORTS ARE REQUIRED TO SHOW COMPLIANCE
 WITH FBC 1207.2 AIR-BORNE SOUND (ASTM E 90-04) AND FBC
 1207.3 STRUCTURE-BORNE SOUND (ASTM E 492-09). THE TEST
 REPORTS FOR FLAME SPREAD AND SMOKE DEVELOPED FOR THE
 SOUND INSULATION FBC 603.1 FLAME SPREAD (ASTM E 84-09)
 IS ALSO REQUIRED.
  
 2) NO WORK TO BE DONE TO PARTY WALLS OR FLOOR/CEILING
 ASSEMBLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-05 Cont ID  
Sent By rmcdouga Date 2021-04-05 Time 08:15 Rev Time 0.00
Received By rmcdouga Date 2021-04-02 Time 16:28 Sent To  
Notes
2021-04-05 08:15:20PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PARTIALLY ADDRESSED. [IN ADDITION TO THE DOOR
 WIDTHS, SPECIFY THE DOOR HEIGHTS ON THE PLANS.] PLEASE
 CLARIFY IF THE TWO DOORS THAT ARE BEING REPLACED ARE
 EXTERIOR DOORS OR INTERIOR DOORS THAT OPEN TO AN
 INTERIOR CORRIDOR. SPECIFY THE SIZES OF THE DOORS ON
 THE PLANS. FBC 107.1.2
  
 2) NOT ADDRESSED. [THIS PROJECT REQUIRES SIGNED AND
 SEALED PLANS FROM A FLORIDA LICENSED DESIGN
 PROFESSIONAL. WORK IS BEING DONE TO THE TENANT
 SEPARATION WALL, THE FLOOR WILL NEED TO BE CORE DRILLED
 FOR THE RELOCATED SINK DRAIN, THE CEILINGS ARE BEING
 FURRED DOWN WHICH MAY AFFECT THE FIRE SPRINKLERS.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS.] THIS IS A FOUR STORY COMMERCIAL
 BUILDING. IF THE DOORS ARE LOCATED ON THE BUILDINGS
 EXTERIOR, SUBMIT SIGNED AND SEALED COMPONENT AND
 CLADDING PRESSURES FOR THE OPENINGS FROM A FLORIDA
 LICENSED ENGINEER. SUBMIT REQUIRED COMPONENT AND
 CLADDING DESIGN PRESSURES FOR THE OPENINGS THAT HAVE
 BEEN PREPARED BY A FLORIDA LICENSED ENGINEER. THE
 DOCUMENTS ARE REQUIRED TO BE DIGITALLY SIGNED BY THE
 ENGINEER IF SUBMITTED ELECTRONICALLY AND THE ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE IF PAPER DOCUMENTS ARE
 SUBMITTED. FS 471 & FAC 61G15
  
 3) PARTIALLY ADDRESSED. [THE PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS WERE NOT APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.] FBC 107.3.4 - PROVIDE TWO SETS OF
 PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH EXTERIOR DOOR TYPE. ONLY ONE SET IS REQUIRED
 TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 4) NOT ADDRESSED. [PROVIDE THE TEST REPORTS FOR THE
 REQUIRED TILE FLOOR SOUND INSULATION.]
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 (UNLESS SUBMITTING ELECTRONICALLY)
 -FBC 603.1 FLAME SPREAD - ASTM E 84-09
 -FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5) NOT ADDRESSED. FBC 107.2.1 - INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By rmcdouga Date 2021-01-07 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2021-01-07 Time 16:03 Sent To  
Notes
2021-01-07 16:27:26PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLEASE CLARIFY IF THE TWO DOORS THAT ARE BEING
 REPLACED ARE EXTERIOR DOORS OR INTERIOR DOORS THAT OPEN
 TO AN INTERIOR CORRIDOR. SPECIFY THE SIZES OF THE DOORS
 ON THE PLANS. FBC 107.1.2
  
 2) THIS IS A FOUR STORY COMMERICAL BUILDING. IF THE
 DOORS ARE LOCATED ON THE BUILDINGS EXTERIOR, SUBMIT
 SIGNED AND SEALED COMPONENT AND CLADDING PRESSURES FOR
 THE OPENINGS FROM A FLORIDA LICENSED ENGINEER. SUBMIT
 REQUIRED COMPONENT AND CLADDING DESIGN PRESSURES FOR
 THE OPENINGS THAT HAVE BEEN PREPARED BY A FLORIDA
 LICENSED ENGINEER. THE DOCUMENTS ARE REQUIRED TO BE
 DIGITALLY SIGNED BY THE ENGINEER IF SUBMITTED
 ELECTRONICALLY AND THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE IF PAPER DOCUMENTS ARE SUBMITTED. FS 471 &
 FAC 61G15
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH EXTERIOR DOOR
 TYPE. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 4) PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 (UNLESS SUBMITTING ELECTRONICALLY)
 -FBC 603.1 FLAME SPREAD - ASTM E 84-09
 -FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-30 Cont ID  
Sent By equinone Date 2021-03-30 Time 14:53 Rev Time 0.00
Received By equinone Date 2021-03-30 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-11 Cont ID  
Sent By equinone Date 2021-01-11 Time 12:30 Rev Time 0.00
Received By equinone Date 2021-01-11 Time 12:20 Sent To  
Notes
2021-01-11 12:31:10CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1) PLEASE PROVIDE PANEL SCHEDULE FOR NEW PANEL SHOWING
 CIRCUITS, WIRE AND BREAKER SIZES. PLEASE ALSO SHOW
 FEEDER TO THIS PANEL AND SPECIFY WIRE SIZE AND
 GROUNDING EQUIPMENT CONDUCTOR SIZE.
  
 2) PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.
  
 3) DRAWINGS NEED TO HAVE NAME AND SIGNATURE OR
 CONTRACTOR QUALIFIER.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-29 Cont ID  
Sent By pleduc Date 2020-12-29 Time   Rev Time 0.00
Received By pleduc Date 2020-12-29 Time 13:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-23 Cont ID  
Sent By rmcdouga Date 2021-04-23 Time 14:50 Rev Time 0.00
Received By rmcdouga Date 2021-04-14 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-04-06 Time   Rev Time 0.00
Received By aoliver Date 2021-03-25 Time 15:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-11 Cont ID  
Sent By equinone Date 2021-01-11 Time 12:31 Rev Time 0.00
Received By equinone Date 2020-12-28 Time 09:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-04-01 Cont ID  
Sent By medwards Date 2021-04-01 Time 11:44 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 11:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-04 Cont ID  
Sent By hmoser Date 2021-01-04 Time 13:25 Rev Time 0.00
Received By hmoser Date 2021-01-04 Time 12:53 Sent To  
Notes
2021-01-04 13:24:59PLAN DENIED
 SHOW ON PLAN WHERE THE NEW A/C DROP IS GOING IN
 KITCHEN.
 PROVIDE A PLAN SHOWING SIZE OF A. C. DUCT, CAN SIZE,
 AND CFM. PROVIDE INFORMATION ON BATHROOM AND KITCHEN
 EXHAUST IF REPLACED.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-04-06 Cont ID  
Sent By ccole Date 2021-04-06 Time 12:28 Rev Time 0.00
Received By ccole Date 2021-04-06 Time 12:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By ccole Date 2021-01-07 Time 14:27 Rev Time 0.00
Received By ccole Date 2021-01-07 Time 13:49 Sent To  
Notes
2021-01-07 14:27:311ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120912
 1/7/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE SANITARY DRAINAGE AND WATER RISER DRAWINGS
 FOR THE RELOCATED SINK AND DISHWASHER- SECTION
 107.3.5.1.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-04-23 Cont ID  
Sent By rmcdouga Date 2021-04-22 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2021-04-22 Time 15:59 Sent To  
Notes
2021-04-22 15:59:24NO STRUCTURAL WORK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-04-05 Cont ID  
Sent By rmcdouga Date 2021-04-05 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2021-04-05 Time 08:16 Sent To  
Notes
2021-04-05 08:16:42ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By rmcdouga Date 2021-01-07 Time 16:26 Rev Time 0.00
Received By rmcdouga Date 2021-01-07 Time 16:26 Sent To  
Notes
2021-01-07 16:40:28ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15