Plan Review Details - Permit 20120868
Plan Review Stops For Permit 20120868
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-03-18 Cont ID  
Sent By rmcphers Date 2021-03-18 Time 12:06 Rev Time 0.00
Received By rmcphers Date 2021-03-18 Time 12:06 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By rmcphers Date 2020-12-29 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2020-12-29 Time 15:08 Sent To  
Notes
2020-12-29 15:10:13PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-02 Cont ID  
Sent By rmcphers Date 2021-04-02 Time 14:08 Rev Time 0.00
Received By rmcphers Date 2021-04-02 Time 14:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-18 Cont ID  
Sent By rmcphers Date 2021-03-18 Time 12:06 Rev Time 0.00
Received By rmcphers Date 2021-03-18 Time 11:20 Sent To  
Notes
2021-03-18 12:02:53INTERIOR RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS IN PROJECTDOX SHOULD BE ENTERED AS A SINGLE
 DRAWING NOT A PACKAGE OF DRAWINGS - THE ARCHITECTURAL
 DRAWINGS ARE ALL IN ONE FOLDER WHILE THE ELEC, PLUMBING
 AND MECHANICAL ARE ALL SEPARATED. SO WHEN THE
 ARCHITECTURAL "PACKAGE" WAS REVISED THERE ARE DRAWINGS
 MISSING BECAUSE YOU DID NOT PROVIDE A COMPLETE
 ARCHITECTURAL PACKAGE FOR THIS ROUND. THE FIRST ROUND
 "PACKAGE" FOR THE ARCHITECTURAL WERE VOIDED IN
 PROJECTDOX.
 2) PLEASE SHOW THE GRAB BAR LOCATIONS MORE SPECIFICALLY
 TO AVOID INCORRECT INSTALLATION FBC ACCESSIBILITY
 604.5.1SIDE WALL. 604.5.2REAR WALL.
 3) PLEASE SHOW THE TOILET PAPER DISTANCE FROM THE FACE
 OF THE TOILET TO THE CENTER OF THE DISPENSER TO AVOID
 INCORRECT INSTALLATION FBC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By rmcphers Date 2020-12-29 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2020-12-29 Time 13:02 Sent To  
Notes
2020-12-29 14:28:16INTERIOR RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE CLARIFY EXISTING VERSES NEW - MEP DRAWINGS
 SHOW 2ND FLOOR AS OFFICE AND SHOW ROOM (MERCANTILE) -
 ARCHITECTURAL DRAWINGS SHOW 2ND FLOOR AS ALL STORAGE.
 2) OCCUPANT LOAD AND MEANS OF EGRESS WILL BE REVIEWED
 AFTER CLARIFICATION - PLEASE UP DATE OCCUPANT LOAD AND
 MEANS OF EGRESS FOR THE OCCUPANCY CLASSIFICATION.
 3) SHOW THE TOTAL TRAVEL DISTANCE FROM THE 2ND FLOOR TO
 THE EXIT. FBC 1017.3
 4) PLEASE SHOW THE OCCUPANT LOAD FOR EACH ROOM FBC
 1004.1.2
 5) PLEASE SHOW THE STAIR HEADROOM CLEARANCE TO COMPLY
 WITH FBC 1011.3
 6) DRAWING A1.0 SAYS TO REMOVE THE STEEL JOIST - I DO
 NOT SEE THE STRUCTURAL DRAWINGS THAT SHOW THE REMOVAL
 AND FIX.
 7) PLEASE SHOW ALL RESTROOM ACCESSIBILITY DETAILS -
 GRAB BAR SIZES AND HEIGHT, MIRROR HEIGHT, PAPER
 DISPENSER LOCATIONS, ETC. TO SHOW COMPLIANCE WITH FBC
 ACCESSIBILITY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By equinone Date 2021-03-09 Time 10:15 Rev Time 0.00
Received By equinone Date 2021-03-09 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-31 Cont ID  
Sent By equinone Date 2020-12-31 Time 08:48 Rev Time 0.00
Received By equinone Date 2020-12-31 Time 08:48 Sent To  
Notes
2020-12-31 08:52:30CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 NOTE: PLEASE SEE COMMENT 1) FROM BUILDING REVIEW BELOW
 AND CLARIFY SCOPE OF WORK:
  
 1) PLEASE CLARIFY EXISTING VERSUS NEW - MEP DRAWINGS
 SHOW 2ND FLOOR AS OFFICE AND SHOW ROOM (MERCANTILE) -
 ARCHITECTURAL DRAWINGS SHOW 2ND FLOOR AS ALL STORAGE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By pleduc Date 2021-03-09 Time   Rev Time 0.00
Received By pleduc Date 2021-03-09 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By pleduc Date 2020-12-18 Time   Rev Time 0.00
Received By pleduc Date 2020-12-18 Time 11:24 Sent To  
Notes
2020-12-18 12:38:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C 1 - THERE IS AN INDICATION OF A MIXED USE
 OCCUPANCY; HOWEVER, THERE IS NO INDICATIONS OF
 SEPARATIONS
  
 PER NFPA 101, CH 6
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 SHEET E 2.0 INDICATES A SHOWROOM WHICH CAN BE
 CONSIDERED MERCANTILE, NFPA 101, CH 36, NEW MERCANTILE
 OCCUPANCIES, AND THE PROPOSED SHALL COMPLY WITH THIS
 OCCUPANCY AS IT IS THE MOST RESTRICTIVE.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A DETAILED
 INFORMATIONAL NARRATIVE OF THE OCCUPANCY TYPE FOR
 CONSIDERATION.
  
  
  
 2) THERE IS NO LIFE SAFETY PLAN INDICATING OCCUPANCY
 LOADS, TRAVEL DISTANCES, TRAVEL PATHS, EXIT WIDTH, EXIT
 CAPACITY, ETC.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) THERE ARE NO STAIR & HANDRAIL DETAILS.
  
 36.2.2.3 STAIRS.
 36.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE WITH
 NFPA 101, CH 36 & 7
  
  
  
 4) PLEASE PROVIDE DETAILS OF WHAT THE SHOWROOM WILL
 CONSIST OF, PRODUCT, EQUIPMENT, SHELVEING, PRPOSED
 FLOOR PLAN.....
  
  
  
 5) THERE IS ONLY ONE EXIT FROM INDICATED FROM THE 2ND
 FL.
  
 PER NFPA 101, CH 36
  
 36.2.4 NUMBER OF MEANS OF EGRESS.
 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH
 36.2.4.5:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 SECTION 7.4.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
  
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 36.1.2.2 SUBCLASSIFICATION OF OCCUPANCY.
 36.1.2.2.1 MERCANTILE OCCUPANCIES SHALL BE
 SUBCLASSIFIED AS
 FOLLOWS:
  
 (3) CLASS C, ALL MERCANTILE OCCUPANCIES OF NOT MORE
 THAN 3000
 FT2 (280 M2) GROSS AREA AND USED FOR SALES PURPOSES
 OCCUPYING ONE STORY ONLY
  
 IF THIS OCCUPACNY IS MIXED, NONSEPARATED IT IS NOT A
 CLASS C 2 EXITS ARE REQUIRED.
  
  
  
 6) THERE IS NO EXIT DOOR HARDWARE INDICATED.
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 7) SHEET E 1.0 - THERE IS AN EXISTING DOOR AT THE
 PROPOSED LOBBY CONNECTING THE EXISTING STORAGE. THE
 DOOR IS MARKED WITH AN EXIT SIGN FROM THE STORAGE
 LEADING THRU THE LOBBY. THE DOOR IS INDICATED AS
 SWINGING AGAINST EGRESS.
  
 THOUGH EXISTING THIS DOOR IS REQUIRED TO SWING IN
 DIRECTION OF EGRESS PER CH 38 & CH 7
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-02 Cont ID  
Sent By rmcphers Date 2021-04-02 Time 14:22 Rev Time 0.00
Received By rmcphers Date 2021-03-25 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-18 Cont ID  
Sent By rmcphers Date 2021-03-18 Time 12:07 Rev Time 0.00
Received By rmcphers Date 2021-03-04 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-31 Cont ID  
Sent By equinone Date 2020-12-31 Time 08:52 Rev Time 0.00
Received By equinone Date 2020-12-17 Time 16:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-12-29 Cont ID  
Sent By rmcphers Date 2020-12-29 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2020-12-29 Time 15:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By medwards Date 2021-03-09 Time 17:01 Rev Time 0.00
Received By medwards Date 2021-03-09 Time 16:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By medwards Date 2020-12-18 Time 16:49 Rev Time 0.00
Received By medwards Date 2020-12-18 Time 16:49 Sent To  
Notes
2020-12-18 16:50:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20120868
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE RETURN AIR PATH BACK TO THE AHU?S AS
 THERE DOUBLE DOORS ENCLOSING THEM. ALSO PROVIDE
 INFORMATION ON THE DOORS FOR THE AHU PLENUM. FBC 107.2;
 FBC M 602.2; FBC M 601.6
  
 2) PLEASE SHOW THAT THE CONDENSING UNITS WILL BE
 PROTECTED FROM VEHICULAR TRAFFIC. FBC M 303.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-05 Cont ID  
Sent By lcrespo Date 2021-03-05 Time 09:56 Rev Time 0.00
Received By lcrespo Date 2021-03-05 Time 09:56 Sent To  
Notes
2021-03-05 09:56:2003/05/21 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By lcrespo Date 2020-12-29 Time 17:56 Rev Time 0.00
Received By lcrespo Date 2020-12-28 Time 18:51 Sent To  
Notes
2020-12-29 17:58:1912/29/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE ADDRESS COMMENT SEVEN ON THE BUILDING REVIEW
 TO COMPLY 2017 FBC ACCESSIBILITY CODE.
  
 2. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
  
 3. PLEASE PROVIDE THE LAVATORY KNEE AND TOE CLEARANCES
 PER THE 2017 FBC ACC SEC. 306.1 TOE CLEARANCE.
  
 4. PROVIDE CABINET DETAIL SHOWING THE SINK AND OR LAVS
 HEIGHT OF 34" INCHES MAXIMUM PER THE 2017 FBC ACC SEC.
 606.3.
  
 5. PLEASE SHOW THE DRINKING FOUNTAINS AND SHOW THE
 ACCESSIBILITY IN ACCORDANCE WITH 2017 FBC ACC SEC.
 211.2 & 602.1- 602.6. PROVIDE DRAWINGS AND DETAILS
 SHOWING: A) THE 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD APPROACH TO THE WHEELCHAIR ACCESSIBLE DRINKING
 FOUNTAIN 2017 FBC ACC SEC. 602.2 CLEAR FLOOR SPACE AND
 PLEASE SHOW KNEE AND TOE CLEARANCES, SPOUT HEIGHTS,
 SPOUT LOCATIONS PER THE 2017 FBC ACC SEC. 306, 307, &
 602.2, COMPLIANCE WITH 2017 FBC ACC SEC. 307.2
 PROTRUSION LIMITS.
  
 6. ON SHEET P2.0;
  
 A. THE IN THE ISOMETRIC, THE DRINKING FOUNTAIN AND MOP
 SINK ARE SHOWN ON A DISCHARGING ON A WET VENT. PLEASE
 SHOW DOWNSTREAM OF THE BATHROOM GROUP PER THE 2017 FBC
 SEC. P 912.1.
  
 B. PLEASE SHOW ON THE WATER RISER FOR THE LAVS THAT THE
 TEMPERING VALVES SHALL CONFORM TO ASSE 1070 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. PLEASE SHOW ON THE ISOMETRIC THE SHOW LOCATION AND
 TYPE OF MAIN SHUTOFF 2017 FBC SEC. P 606.1.
  
 7. ON SHEET C1;
 A. PLEASE PROVIDE UNDER CODES, THE YEAR, PLUMBING, AND
 ACCESSIBILITY REFERENCED USED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 101.4 REFERENCED CODES.
  
 B. PROJECT INDEX IS MISSING P2.0; PLEASE PROVIDE PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8. PLEASE PROVIDE A SLAB REPAIR DETAIL AND SHOW THE
 REPAIR'S WIDTH, THE MINIMUM THICKNESS OF THE CONCRETE
 TO BE REPLACED, AND THE CONCRETE'S PSI. SHOW THE
 DOWELS' SIZE AND LENGTH, THE MINIMUM EMBEDMENT DEPTH
 INTO THE EXISTING SLAB, AND THE DOWELS' SPACING IN THE
 CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AND THE REQUIRED VAPOR BARRIER OVER THE
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-02 Cont ID  
Sent By rmcphers Date 2021-04-02 Time 14:22 Rev Time 0.00
Received By rmcphers Date 2021-04-02 Time 14:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By medwards Date 2021-03-09 Time 17:06 Rev Time 0.00
Received By medwards Date 2021-03-09 Time 17:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-18 Cont ID  
Sent By medwards Date 2020-12-18 Time 16:53 Rev Time 0.00
Received By medwards Date 2020-12-18 Time 16:51 Sent To  
Notes
***NONE***