| 2020-12-30 09:54:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE INDICATIONS THROUGHOUT THE OCCUPANCY OF |
| | FIRE ALARM PULL STATIONS. |
| | |
| | IN AN EFFORT TO REDUCE THE POTENTIAL OF FALSE ALARMS |
| | REDUCE THE AMOUNT AND LOCATION OF PULL STATION PER NFPA |
| | 101, CH 28 & CH 9. |
| | |
| | 28.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 28.3.4.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE |
| | WITH SECTION |
| | 9.6, EXCEPT AS MODIFIED BY 28.3.4.2 THROUGH 28.3.4.6, |
| | SHALL BE |
| | PROVIDED. |
| | 28.3.4.2 INITIATION. THE REQUIRED FIRE ALARM SYSTEM |
| | SHALL BE |
| | INITIATED BY EACH OF THE FOLLOWING: |
| | (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2 |
| | (2) MANUAL FIRE ALARM BOX LOCATED AT THE HOTEL DESK OR |
| | OTHER |
| | CONVENIENT CENTRAL CONTROL POINT UNDER CONTINUOUS |
| | SUPERVISION BY RESPONSIBLE EMPLOYEES |
| | (3) REQUIRED AUTOMATIC SPRINKLER SYSTEM |
| | (4) REQUIRED AUTOMATIC DETECTION SYSTEM OTHER THAN |
| | SLEEPING |
| | ROOM SMOKE DETECTORS |
| | |
| | 9.6.2 SIGNAL INITIATION. |
| | 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE, |
| | ACTUATION |
| | OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF |
| | THE FOLLOWING |
| | MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH |
| | MEANS: |
| | (1) MANUAL FIRE ALARM INITIATION |
| | (2) AUTOMATIC DETECTION |
| | (3) EXTINGUISHING SYSTEM OPERATION |
| | |
| | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE |
| | DETECTION OR |
| | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM |
| | SYSTEM IN |
| | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN |
| | ONE MANUAL |
| | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY |
| | HAVING |
| | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE |
| | ALARM SIGNAL. |
| | |
| | THE SUBMITTED PLAN HAS BEEN MARKED-UP TO REMOVE PULL |
| | STATIONS. |
| | |
| | PLEASE REVIEW AND ADJUST, UNLESS THE OWNER HAS |
| | SPECIFIACCLY REQUESTED TO HAVE THEM AT THESE LOCATIONS. |
| | |
| | |
| | |
| | |
| | 2) THERE ARE INDICATIONS THROUGHOUT THE OCCUPANCY OF |
| | FIRE ALARM PULL STATIONS. |
| | |
| | IN AN EFFORT TO REDUCE THE POTENTIAL OF FALSE ALARMS |
| | REDUCE THE AMOUNT AND LOCATION OF PULL STATION PER NFPA |
| | 101, CH 28 & CH 9. |
| | |
| | 28.3.4.4 DETECTION. A CORRIDOR SMOKE DETECTION SYSTEM |
| | IN |
| | ACCORDANCE WITH SECTION 9.6 SHALL BE PROVIDED IN |
| | BUILDINGS OTHER |
| | THAN THOSE PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH 28.3.5.3. |
| | |
| | 9.6.2.9 WHERE A TOTAL (COMPLETE) COVERAGE SMOKE |
| | DETECTION |
| | SYSTEM IS REQUIRED BY ANOTHER SECTION OF THIS CODE, |
| | AUTOMATIC |
| | DETECTION OF SMOKE IN ACCORDANCE WITH NFPA 72, NATIONAL |
| | FIRE |
| | ALARM AND SIGNALING CODE, SHALL BE PROVIDED IN ALL |
| | OCCUPIABLE |
| | AREAS IN ENVIRONMENTS THAT ARE SUITABLE FOR PROPER |
| | SMOKE DETECTOR |
| | OPERATION. |
| | |
| | SMOKE DETECTION IS NOT REQUIRED THROUGHOUT THE |
| | OCCUPANCY DUE TO THE FIRE SPRINKLER SYSTEM. |
| | |
| | PLEASE REVIEW AND ADJUST WHERE NOT REQUIRED, UNLESS THE |
| | OWNER HAS SPECIFIACCLY REQUESTED TO HAVE THEM AT THE |
| | NOTED LOCATIONS. |
| | |
| | |
| | 3) THERE ARE INDICATIONS OF SMOKE DETECTORS IN EACH |
| | ROOM/SUITE. |
| | |
| | PER NFPA 101, CH 28 |
| | |
| | 28.3.4.5* SMOKE ALARMS. SMOKE ALARMS SHALL BE INSTALLED |
| | IN |
| | ACCORDANCE WITH 9.6.2.10 IN EVERY GUEST ROOM AND EVERY |
| | LIVING |
| | AREA AND SLEEPING ROOM WITHIN A GUEST SUITE. |
| | |
| | 9.6.2.10.6 SYSTEM SMOKE DETECTORS IN ACCORDANCE WITH |
| | NFPA 72, |
| | NATIONAL FIRE ALARM AND SIGNALING CODE, AND ARRANGED TO |
| | FUNCTION IN THE SAME MANNER AS SINGLE-STATION OR |
| | MULTIPLE-STATION |
| | SMOKE ALARMS SHALL BE PERMITTED IN LIEU OF SMOKE |
| | ALARMS. |
| | |
| | 9.6.2.10.8* IN NEW CONSTRUCTION, WHERE TWO OR MORE |
| | SMOKE ALARMS |
| | ARE REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR |
| | SIMILAR AREA, |
| | THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE |
| | ALARM SHALL |
| | CAUSE THE ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING |
| | UNIT, SUITE |
| | OF ROOMS, OR SIMILAR AREA TO SOUND, UNLESS OTHERWISE |
| | PERMITTED BY |
| | ONE OF THE FOLLOWING: |
| | (1) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY WHERE |
| | PERMITTED BY ANOTHER SECTION OF THIS CODE. |
| | (2) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY TO |
| | CONFIGURATIONS THAT PROVIDE EQUIVALENT DISTRIBUTION OF |
| | THE |
| | ALARM SIGNAL. |
| | 9.6.2.10.9 THE ALARMS DESCRIBED IN 9.6.2.10.8 SHALL |
| | SOUND ONLY |
| | WITHIN AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR |
| | SIMILAR AREA |
| | AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM, |
| | UNLESS |
| | OTHERWISE PERMITTED BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | 9.6.2.10.10 SMOKE ALARMS SHALL BE PERMITTED TO BE |
| | CONNECTED TO |
| | THE BUILDING FIRE ALARM SYSTEM FOR THE PURPOSE OF |
| | ANNUNCIATION IN |
| | ACCORDANCE WITH NFPA 72. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE WITH |
| | THE CODE. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |