Plan Review Details - Permit 20120862
Plan Review Stops For Permit 20120862
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-12-29 Cont ID  
Sent By cthroop Date 2020-12-29 Time 13:18 Rev Time 0.00
Received By cthroop Date 2020-12-29 Time 13:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-22 Cont ID  
Sent By ppetty Date 2021-03-22 Time 08:56 Rev Time 0.00
Received By ppetty Date 2021-03-22 Time 08:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By cthroop Date 2020-12-29 Time 13:15 Rev Time 0.00
Received By cthroop Date 2020-12-29 Time 11:48 Sent To  
Notes
2020-12-29 13:17:39PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE UPDATED LOAD CALC'S.
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 2. PROVIDE EQUIPMENT SERVICE OUTLET.
 E3901.12
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 3. GFCI PROTECTION REQUIRED.
 E4203.1.3GFCI PROTECTION.
 ALL 15- AND 20-AMPERE, SINGLE PHASE, 125-VOLT
 RECEPTACLES LOCATED WITHIN 20 FEET (6096 MM) OF THE
 INSIDE WALLS OF POOLS AND OUTDOOR SPAS AND HOT TUBS
 SHALL BE PROTECTED BY A GROUND-FAULT CIRCUIT
 INTERRUPTER. OUTLETS SUPPLYING POOL PUMP MOTORS
 SUPPLIED FROM BRANCH CIRCUITS RATED AT 120 VOLTS
 THROUGH 240 VOLTS, SINGLE PHASE, WHETHER BY RECEPTACLE
 OR DIRECT CONNECTION, SHALL BE PROVIDED WITH
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL. [680.21(C) AND 680.22(A)(4)]
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-02-25 Cont ID  
Sent By lcrespo Date 2021-02-25 Time 10:58 Rev Time 0.00
Received By lcrespo Date 2021-02-25 Time 10:58 Sent To  
Notes
2021-02-25 10:58:01GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-22 Cont ID  
Sent By ppetty Date 2021-03-22 Time 08:56 Rev Time 0.00
Received By ppetty Date 2021-02-23 Time 06:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-30 Cont ID  
Sent By lmarchan Date 2020-12-30 Time 10:59 Rev Time 0.00
Received By lmarchan Date 2020-12-17 Time 16:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-25 Cont ID  
Sent By lcrespo Date 2021-02-25 Time 10:58 Rev Time 0.00
Received By lcrespo Date 2021-02-25 Time 10:47 Sent To  
Notes
2021-02-25 10:58:5002/25/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By lcrespo Date 2020-12-18 Time 15:39 Rev Time 0.00
Received By lcrespo Date 2020-12-18 Time 15:17 Sent To  
Notes
2020-12-18 15:18:1412/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM ITS
 PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEAT PUMP, AND FILTER. ALL SYSTEM COMPONENTS EXCEPT THE
 PUMP.
  
 2. IDENTIFY THE PUMP CURVE, WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. IT IS NEEDED
 TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1.
  
 3. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE HEAT PUMP PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 A. HEAT PUMP POOL HEATERS SHALL HAVE A MINIMUM COP OF
 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2,
 STANDARD RATING CONDITIONS ? LOW AIR TEMPERATURE. A
 TEST REPORT FROM AN INDEPENDENT LABORATORY IS REQUIRED
 TO VERIFY PROCEDURE COMPLIANCE PER THE 2017 FBC-ENERGY
 ? SEC. R 403.10.5
  
 4. A PERMIT IS REQUIRED FOR BACKFLOW (PVB) ON THE
 AUTOFILL PER THE 2017 FBC-PLUMBING SEC.608.1.
  
 5. NOTE: A REDUCED PRESSURE ZONE ASSEMBLY IS REQUIRED
 SINCE AN AUTO-FILL IS PRESENT PER THE CITY OF WEST PALM
 BEACH ORD #2853-95. A PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES BEFORE
 FINAL INSPECTION. PLEASE CONTACT THE CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS. A
 BACKFLOW PRESSURE VACUUM BREAKER IS REQUIRED WITH A
 PERMIT ON THE AUTOFILL BY A LICENSED CONTRACTOR AND
 MUST BE CERTIFIED PER THE 2017 FBC-PLUMBING SEC.608.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 06:07 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 06:07 Sent To  
Notes
2021-03-01 06:08:24ORIGINAL SIGNED AND SEALED PAPER DRAWINGS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-12-17 Cont ID  
Sent By medwards Date 2020-12-17 Time 17:17 Rev Time 0.00
Received By medwards Date 2020-12-17 Time 17:17 Sent To  
Notes
2020-12-17 17:17:43ORIGINAL SIGNED AND SEALED DRAWINGS ROUTED TO STORAGE.
 ME

Review Stop Z ZONING
Rev No 1 Status P Date 2020-12-30 Cont ID  
Sent By jroach Date 2020-12-30 Time 10:43 Rev Time 0.00
Received By jroach Date 2020-12-30 Time 10:43 Sent To  
Notes
2020-12-30 10:43:24PROVISOS:
  
 1. ALL POOL EQUIPMENT SHALL BE A MINIMUM OF ONE (1)
 FOOT FROM THE SIDE PROPERTY LINE.
  
 2. POOL SHALL BE ENCLOSED BY A PERMANENT FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED
 (?BABY FENCE? DOES NOT MEET THIS REQUIREMENT). BARRIERS
 OR FENCES SHALL BE AT LEAST 4 FEET IN HEIGHT ABOVE
 GRADE.
  
 3. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.
  
 4. PATIO OR PAVED AREA ADJACENT TO OR SURROUNDING THE
 POOL SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT
 NOT ONTO ADJACENT PROPERTIES.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved