| 2020-12-18 15:18:14 | 12/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| | MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM ITS |
| | PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| | DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| | EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE |
| | (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE |
| | DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE |
| | SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH |
| | CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS, |
| | INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| | HEAT PUMP, AND FILTER. ALL SYSTEM COMPONENTS EXCEPT THE |
| | PUMP. |
| | |
| | 2. IDENTIFY THE PUMP CURVE, WHICH CURVE KEY IS SPECIFIC |
| | TO THE PUMP BEING INSTALLED ON THIS POOL. IT IS NEEDED |
| | TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH |
| | CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. |
| | 4.4.9, 4.4.9.1. |
| | |
| | 3. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE HEAT PUMP PER THE WPB AMENDMENTS TO FBC SEC. |
| | 107.2.1. |
| | |
| | A. HEAT PUMP POOL HEATERS SHALL HAVE A MINIMUM COP OF |
| | 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2, |
| | STANDARD RATING CONDITIONS ? LOW AIR TEMPERATURE. A |
| | TEST REPORT FROM AN INDEPENDENT LABORATORY IS REQUIRED |
| | TO VERIFY PROCEDURE COMPLIANCE PER THE 2017 FBC-ENERGY |
| | ? SEC. R 403.10.5 |
| | |
| | 4. A PERMIT IS REQUIRED FOR BACKFLOW (PVB) ON THE |
| | AUTOFILL PER THE 2017 FBC-PLUMBING SEC.608.1. |
| | |
| | 5. NOTE: A REDUCED PRESSURE ZONE ASSEMBLY IS REQUIRED |
| | SINCE AN AUTO-FILL IS PRESENT PER THE CITY OF WEST PALM |
| | BEACH ORD #2853-95. A PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES BEFORE |
| | FINAL INSPECTION. PLEASE CONTACT THE CITY OF WPB |
| | UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS. A |
| | BACKFLOW PRESSURE VACUUM BREAKER IS REQUIRED WITH A |
| | PERMIT ON THE AUTOFILL BY A LICENSED CONTRACTOR AND |
| | MUST BE CERTIFIED PER THE 2017 FBC-PLUMBING SEC.608.1. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |