| Plan Review Stops For Permit 20120859 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-03-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-04 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-04 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-06 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-05 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2021-01-06 08:35:50 | POOL DECK REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE PAVILION METAL ROOF DETAILS - | | | PROVIDE THE ROOFING SYSTEM PRODUCT APPROVALS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2021-02-19 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-02-19 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-02-19 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2021-02-19 11:54:24 | SEE RESPONSE DOCUMENT FROM 2-11-2021. ELECTRICAL WORK | | | UNDER PERMIT 21020091. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-01-05 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-01-05 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-01-05 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2021-01-05 15:04:49 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED. | | | | | | 1) ELECTRICAL SCOPE OF WORK IS NOT CLEAR. THE NARRATIVE | | | PROVIDED MENTIONS THAT "THIS PLAN AND SCOPE OF WORK | | | WILL BE PERFORMED UNDER BUILDING PERMIT FOR PORTOFINO | | | PLACE??. MASTER PERMIT NUMBER #17120809 PER SHEET | | | E0.10". AND THEN THE NARRATIVE SAYS UNDER A) THAT THIS | | | PROPOSAL INCLUDES LIGHTING FIXTURES AND SOME CHARGING | | | STATIONS. | | | | | | AFTER CHECKING E0.10 (PERMIT 17120809) IT SEEMS THAT | | | THE ELECTRICAL WORK FOR POOL LIGHTING AND CHARGING | | | STATIONS WAS NOT INCLUDED THEN AND THE ELECTRICAL | | | APPROVED WAS FOR THE CLUBHOUSE. | | | | | | PLEASE CLARIFY. IF ELECTRICAL WORK IS BEING DONE THAT | | | WAS NOT INCLUDED ON PERMIT 17120809 PLEASE PROVIDE | | | ELECTRICAL DRAWINGS SHOWING CIRCUITS, WIRE AND BREAKER | | | SIZES, PANELS SCHEDULES AFFECTED, LOCATION OF CHARGING | | | STATIONS. THE LIGHTING DETAILS SHEET (LA2.40) ONLY | | | PROVIDES SPECS ON FIXTURES AND CHARGING STATIONS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-02-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-02-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-02-22 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2020-12-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-12-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-12-22 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2020-12-22 14:14:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET LA 2.10 - THERE ARE INDICATIONS OF A FIREPIT; | | | HOWEVER, THERE ARE NO DETAILS. | | | | | | PLEASE PROVIDE DETAILS REGARDING WHAT THE DEFINITION OF | | | "FIRE MEDIA" & "FIRE BOX" ARE? | | | | | | THERE SHALL BE DETERANTS IN PLACE TO PROTECT AGAINST | | | ACCIDENTAL/INTENTIONAL FLAME CONTACT. | | | | | | WHAT IS THE PROPOSED DIMENSION FROM THE TOP OF ANY | | | VIEWING PANE TO THE TOP OF THE FLAME?( PREVENT REACHING | | | OVER TO MAKE FLAME CONTACT) | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF FUEL SUPPLY FOR THE | | | FIREPIT. | | | | | | PLEASE PROVIDE DETAILS, AS WELL AS, A MANUFACTURER'S | | | SPEC SHEET FOR REVIEW. | | | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF AN EMERGENCY SHUTOFF FOR | | | THE FUEL SUPPLY. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 4) THERE ARE NO INDICATIONS OF FUEL SUPPLY FOR THE | | | GRILLS. | | | | | | PLEASE PROVIDE DETAILS, AS WELL AS, A MANUFACTURER'S | | | SPEC SHEET FOR REVIEW. | | | | | | | | | 4A) SHEET LA 1.10 - THERE IS AN INDICATION OF GRILL | | | LOCATED NEAR AN AREA OF TREES AND AN OUTLINE OF A | | | BUILDING. | | | | | | WHAT ARE THE DIMENSIONS TO THESE OBJECTS? | | | | | | 10.10.6 COOKING EQUIPMENT. | | | 10.10.6.1 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, | | | NO | | | HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR | | | COOKING, HEATING, | | | OR ANY OTHER PURPOSE SHALL BE USED OR KINDLED ON ANY | | | BALCONY, | | | UNDER ANY OVERHANGING PORTION, OR WITHIN 10 FT (3 M) OF | | | ANY | | | STRUCTURE. | | | | | | THE OPERATION OF A GRILL WILL PRODUCE SMOKE/VAPORS THAT | | | MAY ENTER AREA APARTMENTS WITH APPLICABLE COMPLAINTS. | | | | | | WHAT IS THE PROPOSED REMEDY SHOULD THIS OCCUR? | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 5) THERE ARE NO FIRE EXTINGUISHERS INDICATED NEAR THE | | | FIREPIT NOR THE BBQ GRILLS. | | | | | | PLEASE REVIEW AND PROVIDE. | | | | | | | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-02-23 |
Time |
21:14 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-02-23 |
Time |
21:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-02-23 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2020-12-28 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2020-12-28 |
Time |
19:14 |
Sent To |
|
|
| Notes |
| 2021-02-23 19:15:20 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT-20120859 | | | 12/29/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT MANUFACTURER?S SPECIFICATION | | | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR | | | 2017 FBC FUEL GAS RES. SEC. G2408.1. | | | 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL | | | GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES | | | SECS. G2413.4.1, G2413.4.2. | | | 3) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. | | | 409.4, FBC FUEL GAS RES. SEC. G2420.4. | | | 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC | | | FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC. | | | G2413.4.1. | | | 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC | | | FUEL GAS RES. SEC. G2421.1. | | | 6) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE | | | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE | | | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, | | | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. 2017 FBC FUEL GAS SEC. 401.4, 401.8, | | | 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS SECS.G2412.4, | | | G2412.8, G2413.1, G2413.2, G2413.3. | | | 7) GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC | | | SEC. 107.5.1.5 (9) COMMERCIAL GAS | | | 8) SUBMIT COPY OF THE SIZING TABLE USED IN THE DESIGN | | | FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF | | | PLANS LISTING THE SIZING TABLES FROM GAS CODES OR | | | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS | | | SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL | | | GAS RES. SEC. G2413.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-04 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-02-11 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-06 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-12-21 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-06 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-06 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2021-02-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-02-18 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-02-18 |
Time |
17:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2020-12-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-12-22 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-12-22 |
Time |
16:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-02-23 |
Time |
21:29 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-02-23 |
Time |
20:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-03-04 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-03-04 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-03-04 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-01-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-01-06 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-01-06 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2021-01-06 08:39:13 | THE STRUCTURAL PAVILION DRAWINGS = SIGNED AND SEALED | | | DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-02-22 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-02-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
2021-02-22 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-12-30 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-12-30 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2020-12-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-12-30 12:25:37 | *************ZONING REVIEW FAILED*************** | | | | | | THIS PERMIT REQUIRES A MINOR AMENDMENT TO THE LAGUNA | | | LAKES PLANNED DEVELOPMENT, DUE TO THE CHANGES BEING | | | MADE TO THE APPROVED LANDSCAPE PLAN. | | | | | | A SEPARATE LANDSCAPE PERMIT WILL BE REQUIRED. | | | | | | PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON THE | | | PROPERTY, A TREE ALTERATION PERMIT SHALL BE SUBMITTED, | | | REVIEWED, AND APPROVED BY THE DEVELOPMENT SERVICES | | | DEPARTMENT, PLANNING DIVISION. | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] | | | | | | |
|
|