Plan Review Details - Permit 20120859
Plan Review Stops For Permit 20120859
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-04 Cont ID  
Sent By rmcphers Date 2021-03-04 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-03-04 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By rmcphers Date 2021-01-06 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2021-01-05 Time 15:57 Sent To  
Notes
2021-01-06 08:35:50POOL DECK REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE PAVILION METAL ROOF DETAILS -
 PROVIDE THE ROOFING SYSTEM PRODUCT APPROVALS.
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2021-02-19 Cont ID  
Sent By equinone Date 2021-02-19 Time 11:52 Rev Time 0.00
Received By equinone Date 2021-02-19 Time 11:40 Sent To  
Notes
2021-02-19 11:54:24SEE RESPONSE DOCUMENT FROM 2-11-2021. ELECTRICAL WORK
 UNDER PERMIT 21020091.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-05 Cont ID  
Sent By equinone Date 2021-01-05 Time 15:03 Rev Time 0.00
Received By equinone Date 2021-01-05 Time 11:48 Sent To  
Notes
2021-01-05 15:04:49CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) ELECTRICAL SCOPE OF WORK IS NOT CLEAR. THE NARRATIVE
 PROVIDED MENTIONS THAT "THIS PLAN AND SCOPE OF WORK
 WILL BE PERFORMED UNDER BUILDING PERMIT FOR PORTOFINO
 PLACE??. MASTER PERMIT NUMBER #17120809 PER SHEET
 E0.10". AND THEN THE NARRATIVE SAYS UNDER A) THAT THIS
 PROPOSAL INCLUDES LIGHTING FIXTURES AND SOME CHARGING
 STATIONS.
  
 AFTER CHECKING E0.10 (PERMIT 17120809) IT SEEMS THAT
 THE ELECTRICAL WORK FOR POOL LIGHTING AND CHARGING
 STATIONS WAS NOT INCLUDED THEN AND THE ELECTRICAL
 APPROVED WAS FOR THE CLUBHOUSE.
  
 PLEASE CLARIFY. IF ELECTRICAL WORK IS BEING DONE THAT
 WAS NOT INCLUDED ON PERMIT 17120809 PLEASE PROVIDE
 ELECTRICAL DRAWINGS SHOWING CIRCUITS, WIRE AND BREAKER
 SIZES, PANELS SCHEDULES AFFECTED, LOCATION OF CHARGING
 STATIONS. THE LIGHTING DETAILS SHEET (LA2.40) ONLY
 PROVIDES SPECS ON FIXTURES AND CHARGING STATIONS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By pleduc Date 2021-02-22 Time   Rev Time 0.00
Received By pleduc Date 2021-02-22 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-12-22 Cont ID  
Sent By pleduc Date 2020-12-22 Time   Rev Time 0.00
Received By pleduc Date 2020-12-22 Time 13:41 Sent To  
Notes
2020-12-22 14:14:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LA 2.10 - THERE ARE INDICATIONS OF A FIREPIT;
 HOWEVER, THERE ARE NO DETAILS.
  
 PLEASE PROVIDE DETAILS REGARDING WHAT THE DEFINITION OF
 "FIRE MEDIA" & "FIRE BOX" ARE?
  
 THERE SHALL BE DETERANTS IN PLACE TO PROTECT AGAINST
 ACCIDENTAL/INTENTIONAL FLAME CONTACT.
  
 WHAT IS THE PROPOSED DIMENSION FROM THE TOP OF ANY
 VIEWING PANE TO THE TOP OF THE FLAME?( PREVENT REACHING
 OVER TO MAKE FLAME CONTACT)
  
  
  
 2) THERE ARE NO INDICATIONS OF FUEL SUPPLY FOR THE
 FIREPIT.
  
 PLEASE PROVIDE DETAILS, AS WELL AS, A MANUFACTURER'S
 SPEC SHEET FOR REVIEW.
  
  
  
 3) THERE ARE NO INDICATIONS OF AN EMERGENCY SHUTOFF FOR
 THE FUEL SUPPLY.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 4) THERE ARE NO INDICATIONS OF FUEL SUPPLY FOR THE
 GRILLS.
  
 PLEASE PROVIDE DETAILS, AS WELL AS, A MANUFACTURER'S
 SPEC SHEET FOR REVIEW.
  
  
 4A) SHEET LA 1.10 - THERE IS AN INDICATION OF GRILL
 LOCATED NEAR AN AREA OF TREES AND AN OUTLINE OF A
 BUILDING.
  
 WHAT ARE THE DIMENSIONS TO THESE OBJECTS?
  
 10.10.6 COOKING EQUIPMENT.
 10.10.6.1 FOR OTHER THAN ONE- AND TWO-FAMILY DWELLINGS,
 NO
 HIBACHI, GRILL, OR OTHER SIMILAR DEVICES USED FOR
 COOKING, HEATING,
 OR ANY OTHER PURPOSE SHALL BE USED OR KINDLED ON ANY
 BALCONY,
 UNDER ANY OVERHANGING PORTION, OR WITHIN 10 FT (3 M) OF
 ANY
 STRUCTURE.
  
 THE OPERATION OF A GRILL WILL PRODUCE SMOKE/VAPORS THAT
 MAY ENTER AREA APARTMENTS WITH APPLICABLE COMPLAINTS.
  
 WHAT IS THE PROPOSED REMEDY SHOULD THIS OCCUR?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 5) THERE ARE NO FIRE EXTINGUISHERS INDICATED NEAR THE
 FIREPIT NOR THE BBQ GRILLS.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-02-23 Cont ID  
Sent By abelisle Date 2021-02-23 Time 21:14 Rev Time 0.00
Received By abelisle Date 2021-02-23 Time 21:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-02-23 Cont ID  
Sent By abelisle Date 2020-12-28 Time 19:14 Rev Time 0.00
Received By abelisle Date 2020-12-28 Time 19:14 Sent To  
Notes
2021-02-23 19:15:201ST REVIEW FBC-2017 PLUMBING
 PERMIT-20120859
 12/29/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR
 2017 FBC FUEL GAS RES. SEC. G2408.1.
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 3) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.4.1.
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 6) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE
 THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED,
 THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. 2017 FBC FUEL GAS SEC. 401.4, 401.8,
 402.1, 402.2, 402.3 OR 2017 FBC FUEL GAS SECS.G2412.4,
 G2412.8, G2413.1, G2413.2, G2413.3.
 7) GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.5.1.5 (9) COMMERCIAL GAS
 8) SUBMIT COPY OF THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF
 PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL
 GAS RES. SEC. G2413.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-04 Cont ID  
Sent By rmcphers Date 2021-03-04 Time 10:34 Rev Time 0.00
Received By rmcphers Date 2021-02-11 Time 14:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-06 Cont ID  
Sent By rmcphers Date 2021-01-06 Time 08:39 Rev Time 0.00
Received By rmcphers Date 2020-12-21 Time 13:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-01-06 Cont ID  
Sent By rmcphers Date 2021-01-06 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2021-01-06 Time 08:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2021-02-18 Cont ID  
Sent By medwards Date 2021-02-18 Time 17:11 Rev Time 0.00
Received By medwards Date 2021-02-18 Time 17:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-12-22 Cont ID  
Sent By medwards Date 2020-12-22 Time 16:23 Rev Time 0.00
Received By medwards Date 2020-12-22 Time 16:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-02-23 Cont ID  
Sent By abelisle Date 2021-02-23 Time 21:29 Rev Time 0.00
Received By abelisle Date 2021-02-23 Time 20:06 Sent To  
Notes
2020-12-29 17:50:59 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-04 Cont ID  
Sent By rmcphers Date 2021-03-04 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-03-04 Time 10:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By rmcphers Date 2021-01-06 Time 08:37 Rev Time 0.00
Received By rmcphers Date 2021-01-06 Time 08:37 Sent To  
Notes
2021-01-06 08:39:13THE STRUCTURAL PAVILION DRAWINGS = SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By awooten Date 2021-02-22 Time   Rev Time 0.00
Received By awooten Date 2021-02-22 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-30 Cont ID  
Sent By awooten Date 2020-12-30 Time   Rev Time  
Received By awooten Date 2020-12-30 Time   Sent To  
Notes
2020-12-30 12:25:37*************ZONING REVIEW FAILED***************
  
 THIS PERMIT REQUIRES A MINOR AMENDMENT TO THE LAGUNA
 LAKES PLANNED DEVELOPMENT, DUE TO THE CHANGES BEING
 MADE TO THE APPROVED LANDSCAPE PLAN.
  
 A SEPARATE LANDSCAPE PERMIT WILL BE REQUIRED.
  
 PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON THE
 PROPERTY, A TREE ALTERATION PERMIT SHALL BE SUBMITTED,
 REVIEWED, AND APPROVED BY THE DEVELOPMENT SERVICES
 DEPARTMENT, PLANNING DIVISION.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  