Plan Review Details - Permit 20120841
Plan Review Stops For Permit 20120841
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-10 Cont ID  
Sent By cthroop Date 2021-03-10 Time 09:04 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 06:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By cthroop Date 2021-01-06 Time 10:14 Rev Time 0.00
Received By cthroop Date 2021-01-06 Time 06:35 Sent To  
Notes
2021-01-06 10:29:04PLAN REVIEW / BUILDING
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REF: PLAN PAGE A.O1 - CHANGE CONSTRUCTION TYPE FROM
 V TO IIIB PER BUILDING OFFICIAL DIRECTIVE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. ELEVATION OF FINISHED FLOOR ON PLAN SHEET A.01 AND
 EC, SECTION C2 (A) ARE IN CONFLICT. PLEASE CLARIFY. SEE
 NFIP REVIEW COMMENTS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE A SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 4. PROVIDE INSTALLATION INSTRUCTIONS FOR EXTERIOR
 SWINGING DOOR PRODUCT APPROVAL FL6993-R5.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 NOTICE: VALUE HAS BEEN ADJUSTED FROM $425,000.00 TO
 $494,391.00 BASED ON THE ICC BUILDING VALUATION TABLES.
 UNDER AIR - 3109SF X $136.62 = $424,752.00
 STORAGE - 510SF X $78.85 = $ 40,214.00
 UTILITY - 487SF X $60.42 = $ 29,425.00
 NEW CALCULATED VALUE $494,391.00
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-10 Cont ID  
Sent By cthroop Date 2021-03-10 Time 09:04 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 06:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-30 Cont ID  
Sent By cthroop Date 2020-12-30 Time 15:35 Rev Time 0.00
Received By cthroop Date 2020-12-30 Time 13:37 Sent To  
Notes
2020-12-30 15:40:26PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ELECTRICAL LEGEND.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. SMOKE ALARM REQUIRED OUTSIDE BEDROOM #3.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 3. OUTLET REQUIRED AT SGD IN ART STUDIO.
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET. [210.52(A)(1)]
  
  
  
2020-12-30 14:30:20ADDED LOW VOLTAGE REVIEW. CT

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-12-30 Cont ID  
Sent By cthroop Date 2020-12-30 Time 15:34 Rev Time 0.00
Received By cthroop Date 2020-12-30 Time 14:29 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-03-24 Cont ID  
Sent By lcrespo Date 2021-03-24 Time 16:01 Rev Time 0.00
Received By lcrespo Date 2021-03-24 Time 16:01 Sent To  
Notes
2021-03-24 16:15:3003/24/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-03-22 Cont ID  
Sent By lcrespo Date 2021-03-22 Time 14:51 Rev Time 0.00
Received By lcrespo Date 2021-03-22 Time 14:51 Sent To  
Notes
2021-03-22 14:52:0803/22/21 3RD GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. MOST TANK-LESS UNITS CALL FOR A 10.5" WATER COLUMN.
 THE SERVICE METER DISCHARGES IS A TWO PSI REQUIRING A
 REGULATOR FOR THIS UNIT AS PER THE MANUFACTURER'S
 SPECIFICATION. THE LAST COMMENT SAID, ?TANKLESS WATER
 HEATER HAS A GAS APPLIANCE REGULATOR BUILT-IN.? THERE
 WAS NO DOCUMENTATION SUPPORTING THAT. PLEASE PROVIDE
 ALL THE INFORMATION BELOW TO COMPLETE THIS REVIEW.
  
 2. SECOND REQUEST, PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC.
 G2421.1.
  
 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. A NOTE ON PLANS THE LOCATION OF ONE THE TANK-LESS
 WATER HEATER WAS PLACED, AND THE OTHER TANLESS LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER IS NOT SHOWN. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. THRID REQUEST, PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT (RANGE, TANKLESS, GENERATOR, AND POLL HEATER)
 TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-02-23 Cont ID  
Sent By lcrespo Date 2021-02-23 Time 13:15 Rev Time 0.00
Received By lcrespo Date 2021-02-23 Time 13:15 Sent To  
Notes
2021-02-23 13:15:5302/23/21 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. MOST TANK-LESS UNITS CALL FOR A 10.5" WATER COLUMN.
 THE SERVICE METER DISCHARGES IS A TWO PSI REQUIRING A
 REGULATOR FOR THIS UNIT AS PER THE MANUFACTURER'S
 SPECIFICATION. THE LAST COMMENT SAID, ?TANKLESS WATER
 HEATER HAS A GAS APPLIANCE REGULATOR BUILT-IN.? THERE
 WAS NO DOCUMENTATION SUPPORTING THAT. PLEASE PROVIDE
 ALL THE INFORMATION BELOW TO COMPLETE THIS REVIEW.
  
 2. SECOND REQUEST, PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED
 FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC.
 G2421.1.
  
 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. A NOTE ON PLANS THE LOCATION OF ONE THE TANK-LESS
 WATER HEATER WAS PLACED, AND THE OTHER TANLESS LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER IS NOT SHOWN. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. SECOND REQUEST, PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT (RANGE, TANKLESS, GENERATOR, AND POLL HEATER)
 TO VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-12-30 Cont ID  
Sent By lcrespo Date 2020-12-30 Time 13:29 Rev Time 0.00
Received By lcrespo Date 2020-12-30 Time 13:29 Sent To  
Notes
2020-12-30 13:30:0012/30/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-3, THE ISOMETRIC DRAWING HAS SIGNAGE FOR
 EMERGENCY SHUT-OFF, WHICH IS NOT ON THE PLAN, AND NO
 REFERENCE CODE WAS CALLED OUT IN A.01. YOU MAY REMOVE
 IT OR CLARIFY ISOMETRIC AND CODE REFERENCE PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. THE EXPOSED GAS PIPING NOTE IS NOT REQUIRED FOR
 RESIDENTIAL USE. YOU MAY CHOOSE TO LEAVE IT THERE OR
 REMOVE IT.
  
 3. MOST TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION.
  
 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 6. PLEASE NOTE ON PLANS THE LOCATION OF THE TANK-LESS
 WATER HEATER AND THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT
 (RANGE, TANKLESS, GENERATOR, AND POLL HEATER) TO VERIFY
 COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 8. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 9. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1" OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2.
  
 10. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-02 Cont ID  
Sent By cthroop Date 2021-04-02 Time 11:34 Rev Time 0.00
Received By cthroop Date 2021-03-30 Time 15:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-24 Cont ID  
Sent By lcrespo Date 2021-03-24 Time 16:01 Rev Time 0.00
Received By lcrespo Date 2021-03-24 Time 16:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-22 Cont ID  
Sent By lcrespo Date 2021-03-22 Time 14:52 Rev Time 0.00
Received By lcrespo Date 2021-02-17 Time 05:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By kalexand Date 2021-02-01 Time 23:36 Rev Time 0.00
Received By lmarchan Date 2020-12-28 Time 09:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-03-19 Cont ID  
Sent By lmarchan Date 2021-03-19 Time 11:30 Rev Time 0.00
Received By lmarchan Date 2021-03-15 Time 13:03 Sent To  
Notes
2021-03-19 10:46:42RECEIPT MU-2021-12610 - $2491.56 - PAID
2021-03-15 13:03:513/15/21 EMAILED IMPACT OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By cthroop Date 2021-01-06 Time 08:21 Rev Time 0.00
Received By cthroop Date 2021-01-06 Time 08:21 Sent To  
Notes
2021-01-06 08:21:46PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-12 Cont ID  
Sent By medwards Date 2021-03-12 Time 06:02 Rev Time 0.00
Received By medwards Date 2021-03-12 Time 06:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-12-31 Cont ID  
Sent By medwards Date 2020-12-31 Time 12:02 Rev Time 0.00
Received By medwards Date 2020-12-31 Time 12:02 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2021-01-06 Cont ID  
Sent By cthroop Date 2021-01-06 Time 10:03 Rev Time 0.00
Received By cthroop Date 2021-01-06 Time 06:35 Sent To  
Notes
2021-01-06 10:13:35PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 1ST REVIEW
  
 RE: FINISHED CONSTRUCTION ELEVATION CERTIFICATE (EC).
 THIS PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA) AND DOES NOT REQUIRE AN ELEVATION
 CERTIFICATE. YOU MAY PROVIDE ONE FOR INSURANCE
 PURPOSES.
  
 1. SECTION C2 (E) STATES FINISHED FLOOR ELEVATION SHALL
 BE 12.60 FEET NAVD. PLAN PAGE A.05 STATES FINISHED
 FLOOR ELEVATION SHALL BE 7'6". PLEASE CLARIFY.
  
 2. ORIGINAL SIGNATURE AND SEAL OF SURVEYOR IS REQUIRED.
  
 3. SUBMIT A CORRECTED FINISHED CONSTRUCTION EC PRIOR TO
 CERTIFICATE OF OCCUPANCY. USE THE PLAN REVIEW SUBMITTAL
 FORM.
2020-12-30 14:22:58FLOOD ZONE X. EC SUBMITTED FOR REVIEW IS NOT REQUIRED.
 CT

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-22 Cont ID  
Sent By lcrespo Date 2021-03-22 Time 14:52 Rev Time 0.00
Received By lcrespo Date 2021-03-22 Time 14:52 Sent To  
Notes
2021-03-22 14:52:3903/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-23 Cont ID  
Sent By lcrespo Date 2021-02-23 Time 11:56 Rev Time 0.00
Received By lcrespo Date 2021-02-23 Time 11:53 Sent To  
Notes
2021-02-23 11:56:2302/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-12-30 Cont ID  
Sent By lcrespo Date 2020-12-30 Time 13:32 Rev Time 0.00
Received By lcrespo Date 2020-12-30 Time 13:32 Sent To  
Notes
2020-12-30 13:32:2712/30/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-04-02 Cont ID  
Sent By cthroop Date 2021-04-02 Time 11:34 Rev Time 0.00
Received By cthroop Date 2021-04-02 Time 11:27 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-03-10 Cont ID  
Sent By cthroop Date 2021-03-10 Time 09:04 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 08:45 Sent To  
Notes
2021-03-10 09:10:19PLAN REVIEW / ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1.PROVIDE ENHANCED FASTENER DENSITIES FOR ZONES 2 AND 3
 PER NOTE 7, PAGE 22 OF 22 OF NOA 17-1003.15.
 CALCULATIONS SHALL BE PREPARED BY A DESIGN
 PROFESSIONAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2021-01-06 Cont ID  
Sent By cthroop Date 2021-01-06 Time 09:47 Rev Time 0.00
Received By cthroop Date 2021-01-06 Time 06:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-02 Cont ID  
Sent By cthroop Date 2021-04-02 Time 11:34 Rev Time 0.00
Received By cthroop Date 2021-04-02 Time 11:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-10 Cont ID  
Sent By cthroop Date 2021-03-10 Time 08:40 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 07:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-06 Cont ID  
Sent By cthroop Date 2021-01-06 Time 10:13 Rev Time 0.00
Received By cthroop Date 2021-01-06 Time 06:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-02-01 Cont ID  
Sent By kalexand Date 2021-02-01 Time 23:20 Rev Time 0.00
Received By kalexand Date 2021-02-01 Time 23:20 Sent To I
Notes
2021-02-01 23:23:47NO RENTAL PERMITTED FOR GUEST ROOM OR ART STUDIO.