Plan Review Details - Permit 20120816
Plan Review Stops For Permit 20120816
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By jwitmer Date 2021-03-08 Time 12:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-03-08 12:13:44TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By jwitmer Date 2021-03-08 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2021-03-08 Time 11:31 Sent To  
Notes
2021-03-08 12:15:38WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120816 / APPLY DATE 12/16/2020/ 2017
 CODE
 ADD: 651 OKEECHOBEE BLVD. SUITE: 602
 CONT: WAJD INC.
 TEL: 954-536-4247
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 08TH/ 2021
 ACTION: DENIED
  
 1) THE (2) SUBMITTED FLOOR PLANS DOES NOT IDENTIFY THE
 AUTHOR OF THE PLANS. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) THE PERMIT APPLICATION DID NOT INDICATE TUB TO
 SHOWER CONVERSION, WAS ADDED TO THE DESCRIPTION OF
 WORK. ALSO A PLUMBING REVIEW WAS ADDED FOR THE TUB TO
 SHOWER CONVERSION. COMMENTS MAY APPEAR UNDER THE
 PLUMBING PLAN REVIEW.
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2A) PLEASE PROVIDE THE DIMENSIONS FOR THE NEW SHOWER,
 AND WHAT MATERIAL THE NEW CURB WILL BE MADE. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2B) THE FLOOR PLAN NOTATION INDICATES NEW TILE WALL BUT
 DOES NOT PROVIDE THE TYPE OF BACKER BOARD TO BE
 INSTALLED. PLEASE ADDRESS IF THIS IS A FIRE RATED
 TENANT SEPARATION PARTITION?
  
 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
 2017 FBC-B 708.3 FIRE-RESISTANCE RATING. FIRE
 PARTITIONS SHALL HAVE A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR.
  
 2C) THE FLOOR PLAN ALSO MISSING HOW HIGH THE NEW TILE
 WALL WILL EXTEND IN THE NEW SHOWER. 2017 FBC-B SHOWERS
 & TUBS 1210.3. SHOWER COMPARTMENTS AND BATHTUBS WITH
 INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A
 NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72
 INCHES ABOVE THE DRAIN INLET (THIS IS A MINIMUM).
  
 3) THE SUBMITTED FLOOR PLAN ALSO STATES THE REMOVAL OF
 FLOOR TILE AND NEW INSTALLED.
 FLOOR INSULATION (FBC-B 2017) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-03-09 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-12 Time 15:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-09 Cont ID  
Sent By ccole Date 2021-03-09 Time 09:16 Rev Time 0.00
Received By ccole Date 2021-03-09 Time 08:32 Sent To  
Notes
2021-03-09 09:18:271ST REVIEW FBC-2017 PLUMBING
 PERMIT #20120816
 3/9/2021
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS SHOW A BATHTUB TO SHOWER CONVERSION IN THE
 MASTER BATHROOM- COMPLIANCE WITH THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES IS REQUIRED. BECAUSE THE
 BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND
 THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING
 UNITS, THE ALTERATIONS THAT ARE PROPOSED IN THE
 BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES
 ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. COMPLIANCE WITH THE GUIDELINES REQUIRES
 THAT CLEAR FLOOR SPACES FOR WHEELCHAIR APPROACHES TO
 BATH FIXTURES SHALL EITHER BE MAINTAINED AS ORIGINALLY
 DESIGNED OR PROVIDED WHERE NEW FIXTURES ARE BEING
 INSTALLED.
  
 BASED ON THE DRAWINGS IT APPEARS SPECIFICATION A WAS
 CHOSEN AS THE ORIGINAL DESIGN- REFER TO EXAMPLE A
 BATHROOM ON PAGE 7.36 OF THE MANUAL. THE EXAMPLE
 DRAWING SHOWS A 30X48 INCH CLEAR FLOOR SPACE FORWARD
 APPROACH TO THE BATHTUB, HOWEVER THE NEW SHOWER IS
 REQUIRED TO HAVE A 30X48 INCH PARALLEL APPROACH
 POSITIONED IN ACCORDANCE WITH THE FIGURES SHOWN ON
 PAGES 7.56- 7.59. THE DESIGNER OF RECORD SHALL PROVIDE
 ENLARGED DIMENSIONED DRAWINGS OF THE BATHROOM WITH
 CLEAR FLOOR SPACE DIAGRAMS CONFIGURED FOR THE NEW
 SHOWER AND THE REPLACED TOILET AND VANITY. PLEASE NOTE
 THAT WHEN THE SHOWER IS THE ONLY BATHING FIXTURE IN THE
 RESIDENCE IT SHALL BE AT LEAST 36X36 INCHES IN SIZE-
 PAGE 7.58. IT IS ALSO IMPORTANT TO NOTE THAT THE
 EXISTING TOILET MAY HAVE TO BE RELOCATED IF IT
 ENCROACHES ON THE REQUIRED 30X48 INCH CLEAR FLOOR SPACE
 FOR THE SHOWER. SHOWER GRAB BAR REINFORCEMENTS ARE ALSO
 REQUIRED. THE DESIGNER SHALL REFER TO REFER TO THE
 FIGURES IN CHAPTER 6 OF THE MANUAL AND PROVIDE GRAB BAR
 REINFORCEMENT DETAILS SHOWING THE LOCATIONS, HEIGHTS,
 LENGTHS ETC. THE REINFORCEMENT DETAILS ARE ALSO SHOWN
 IN THE FLORIDA ACCESSIBILITY CODE FAIR HOUSING
 GUIEDLINES. PLEASE SEE REQUIREMENT 7 AND FIGURE 5.
  
 1A) AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE
 BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR
 THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE
 BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL
 TO [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT. IF CHOOSING THIS OPTION IT WOULD BE
 ADVISABLE AT A MINIMUM TO INSTALL THE SHOWER WALL
 REINFORCEMENTS.
  
 2) CONCERNING THE NEW SHOWER DRAIN OUTLET, PLEASE SHOW
 COMPLIANCE WITH ITEMS A, B, & C LISTED BELOW.
  
 A) REFER TO SECTION 1002.1 FBC P: THE HORIZONTAL
 DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN
 OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING
 TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE
 PLAN INDICATING COMPLIANCE.
  
 B) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE THE
 FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING
 STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A
 NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET-
 SECTION 1-07.2.1 WPB.
  
 C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION
 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By jwitmer Date 2021-03-08 Time 12:16 Rev Time 0.00
Received By jwitmer Date 2021-03-08 Time 11:31 Sent To  
Notes
2021-03-08 12:16:371) THE (2) SUBMITTED FLOOR PLANS DOES NOT IDENTIFY THE
 AUTHOR OF THE PLANS. THE CONTRACTOR (QUALIFIER) THAT
 CREATED / DREW THE SET OF PLANS WILL NEED TO IDENTIFY
 THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE PRINT
 YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  