Plan Review Details - Permit 20120790
Plan Review Stops For Permit 20120790
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-04-26 Cont ID  
Sent By rmcdouga Date 2021-04-26 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2021-04-26 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-07 Cont ID  
Sent By rmcdouga Date 2021-04-07 Time 10:35 Rev Time 0.00
Received By rmcdouga Date 2021-04-07 Time 10:35 Sent To  
Notes
2021-04-07 10:44:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 OPENINGS INTO A BUILDING. REVISE NOTE ON THE SURVEY.
 FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 2) SEE SIGNATURE COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-05 Cont ID  
Sent By jleahy Date 2021-04-05 Time 15:44 Rev Time 0.00
Received By jleahy Date 2021-04-05 Time 15:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-05-18 Cont ID  
Sent By ccole Date 2021-05-18 Time 17:47 Rev Time 0.00
Received By ccole Date 2021-05-18 Time 16:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-04-29 Cont ID  
Sent By ccole Date 2021-04-29 Time 17:29 Rev Time 0.00
Received By ccole Date 2021-04-29 Time 14:41 Sent To  
Notes
2021-04-29 17:32:262ND REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 20120790
 4/29/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED RISER SHOWS A NATURAL GAS SYSTEM HOWEVER
 THE NOTES ON THE RISER INDICATE THE AN LP SYSTEM
 SUPPLIED BY AN 500-GALLON LP TANK- PLEASE CORRECT THE
 NOTES AND THE LP PIPE SIZING TABLES SHOWN.
  
 2) 2ND REQUEST TO PROVIDE THE TOTAL LOAD OF THE SYSTEM
 AND THE TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE
 METER TO THE MOST REMOTE OUTLET- SECTIONS G2413.2 &
 G2413.4.1 FBC RES.
  
 3) PROVIDE THE SIZE OF THE MAIN SUPPLY PIPE FROM THE
 METER TO THE TEE- SECTION G2413.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-09 Cont ID  
Sent By ccole Date 2021-04-09 Time 17:34 Rev Time 0.00
Received By ccole Date 2021-04-09 Time 17:03 Sent To  
Notes
2021-04-09 17:34:381ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 20120790
 4/9/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: PLEASE UPDATE THE FBC- 2017 CODE
 REFERENCES. THE FBC -2020 7TH EDITION CODES WENT INTO
 EFFECT ON 12/31/2020.
  
 2) GAS RISER: PLEASE ADD THE BBQ GRILL TO THE RISER
 THAT WAS INSTALLED UNDER PERMIT- 13020828- SECTION
 G2413.2 FBC RES.
  
 3) PLEASE PROVIDE THE TOTAL BTU LOAD OF THE SYSTEM AND
 THE TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER
 TO MOST REMOTE OUTLET- SECTION G2413.4.1 FBC RES.
  
 4) SUBMIT UPDATED GENERATOR SPECS. THE SPECS SUBMITTED
 ARE OUTDATED AND SHOW AN INCORRECT BTU LOAD FOR THE
 GENERATOR- SECTION G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-05-18 Time   Rev Time 0.00
Received By aoliver Date 2021-05-11 Time 12:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-10 Cont ID  
Sent By equinone Date 2021-05-10 Time 14:18 Rev Time 0.00
Received By equinone Date 2021-04-23 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-22 Cont ID  
Sent By rmcphers Date 2021-04-22 Time 08:41 Rev Time 0.00
Received By rmcphers Date 2021-03-26 Time 15:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-05-18 Cont ID  
Sent By ccole Date 2021-05-18 Time 17:47 Rev Time 0.00
Received By ccole Date 2021-05-18 Time 16:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-04-29 Cont ID  
Sent By ccole Date 2021-04-29 Time 14:45 Rev Time 0.00
Received By ccole Date 2021-04-29 Time 14:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-04-09 Cont ID  
Sent By ccole Date 2021-04-09 Time 17:34 Rev Time 0.00
Received By ccole Date 2021-04-09 Time 17:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status N Date 2021-05-11 Cont ID  
Sent By medwards Date 2021-05-11 Time 16:03 Rev Time 0.00
Received By medwards Date 2021-05-11 Time 16:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-10 Cont ID  
Sent By equinone Date 2021-05-10 Time 14:18 Rev Time 0.00
Received By equinone Date 2021-05-10 Time 14:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-10 Cont ID  
Sent By equinone Date 2021-04-23 Time 15:50 Rev Time 0.00
Received By equinone Date 2021-04-23 Time 15:50 Sent To  
Notes
2021-04-23 15:52:52SAME COMMENTS AS REVIEW NO. 1 BY MR. MCDOUGAL. NEW
 ORIGINALS SUBMITTED DID NOT INCLUDE THE PRECAST PAD
 DRAWING SO THE DIGITAL SIGNATURE IS STILL MISSING.
  
 THE GENERATOR PAD DRAWING DOES NOT HAVE THE ENGINEER'S
 DIGITAL SIGNATURE. ELECTRONICALLY SUBMITTED DRAWINGS
 ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE
 ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED
 AND SEALED PAPER VERSION OF DRAWINGS. AFTER THE
 ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS.
 NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 471 & 61G15
  
 ELECTRICAL SIGNATURE IS GOOD JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-10 Cont ID  
Sent By rmcdouga Date 2021-04-07 Time 10:35 Rev Time 0.00
Received By equinone Date 2021-05-10 Time 14:17 Sent To  
Notes
2021-04-07 10:39:36THE GENERATOR PAD DRAWING DOES NOT HAVE THE ENGINEER'S
 DIGITAL SIGNATURE. ELECTRONICALLY SUBMITTED DRAWINGS
 ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE
 ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED
 AND SEALED PAPER VERSION OF DRAWINGS. AFTER THE
 ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS.
 NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 471 & 61G15
  
2021-04-05 15:45:16ELECTRICAL SIGNATURE IS GOOD JLEAHY

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By kalexand Date 2021-05-10 Time   Rev Time 0.00
Received By   Date 2021-05-10 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By kalexand Date 2021-04-21 Time 15:11 Rev Time 0.00
Received By kalexand Date 2021-04-21 Time 15:11 Sent To I
Notes
***NONE***