Plan Review Details - Permit 20120783
| Plan Review Stops For Permit 20120783 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-11-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-23 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-22 |
Time |
07:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-03-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-03-18 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-03-10 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-02-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2021-02-02 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2021-01-27 |
Time |
07:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-11-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-23 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-23 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-02-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2021-02-02 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2021-02-02 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2021-02-02 09:51:42 | PLAN DENIED | | | 1) REFER TO SECTION M1602.2 RETURN AIR OPENINGS # 4. | | | 2020 RESIDENTIAL CODE. ( RETURN AIR SHALL NOT BE TAKEN | | | FROM A CLOSET. | | | 2) PROVIDE CFM ON ALL SUPPLY DROPS. | | | SECTION 107 FBC. | | | 3) PROVIDE A VALUE OF WORK ON THE APPLICATION. | | | 4) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS | | | ALL INFORMATION,DRAWINGS,SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL | | | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. | | | FBC 2020. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2021-02-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2021-02-02 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2021-02-02 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2021-02-02 10:07:46 | AIR CONDITIONING CONTRACTOR DID NOT SINE THE PLAN |
|
|
|