Plan Review Details - Permit 20120717
Plan Review Stops For Permit 20120717
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-05-20 Cont ID  
Sent By ccole Date 2021-05-20 Time 15:27 Rev Time 0.00
Received By ccole Date 2021-05-19 Time 07:05 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-04-13 Cont ID  
Sent By ccole Date 2021-04-13 Time 12:40 Rev Time 0.00
Received By ccole Date 2021-04-13 Time 10:22 Sent To  
Notes
2021-04-13 12:40:583RD REVIEW FBC-2017 RES.
 PERMIT- 20120717
 4/13/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 3RD REQUEST FOR THE BBQ GRILL AND FIREPLACE SPECS.
 THE SPECS MAY BE DEFERRED BY REQUEST, HOWEVER PLEASE
 NOTE THAT THE SPECS AND INSTALLATION MANUALS SHALL BE
 ONSITE AT INSPECTION AND ISSUANCE OF THE PERMIT WITHOUT
 REVIEW OF THE SPECS WILL BE AT YOUR OWN RISK. ALL
 GAS-FIRED APPLIANCES AND EQUIPMENT SHALL BE INSTALLED
 AS REQUIRED BY THE TERMS OF THEIR APPROVAL, IN
 ACCORDANCE WITH THE CONDITIONS OF LISTING, THE
 MANUFACTURER?S INSTRUCTIONS AND THIS CODE- SECTION
 G2408.1 FBC RES.
  
 2) 3RD REQUEST TO ADJUST THE VALUE TO INCLUDE THE COST
 OF THE WATER HEATER, BBQ GRILL, AND THE FIREPLACE.
 ACKNOWLEDGED THAT THE COSTS OF THE POOL HEATER AND
 GENERATOR WILL NOT BE INCLUDED. IN LIEU OF PROVIDING
 THE ACTUAL COSTS OF THE EQUIPMENT, THE REVIEWER WILL
 APPLY AN ESTIMATED COST BY REQUEST BASED ON CURRENT
 MARKET VALUES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By ccole Date 2021-03-09 Time 12:05 Rev Time 0.00
Received By ccole Date 2021-03-09 Time 11:22 Sent To  
Notes
2021-03-09 12:06:022ND REVIEW FBC-2017 RES.
 PERMIT- 20120717
 3/9/21
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH NOTES ADDED FOR FURTHER CLARIFICATION
 1) FAILED. GAS RISER: THE RESUBMITTED GAS RISER IS NOT
 LEGIBLE. THE PRINT AND DETAILS ARE TOO FAINT TO READ.
 PLEASE RESUBMIT A CLEAR COPY WITH EMBOLDENED PRINT FOR
 REVIEW AND FOR PUBLIC RECORD SCANNING- SECTION 107.2.1
 WPB.
 A) PROVIDE THE SIZE OF THE PIPE FROM THE METER TO THE
 1ST AND 2ND TEES- G2413.4.1 FBC RES.
 B) PROVIDE THE SIZE OF THE PIPE DROP FROM THE 2ND TEE
 TO THE LOW PRESSURE REGULATOR, AND THE BRANCH PIPE
 SIZES FROM THE REGULATOR TO THE WATER HEATER, DRYER AND
 RANGE- G2413.4.1 & G2413.4.2.
 C) PROVIDE THE TOTAL GAS LOAD OF THE SYSTEM AND THE
 TOTAL DEVELOPED LENGTH FROM THE METER TO THE MOST
 REMOTE OUTLET- G2413.1, G2413.2, & G2413.4.1.
 2) FAILED. THE TANKLESS WATER HEATER, BBQ, FIREPLACE,
 AND POOL HEATER WERE NOT INCLUDED IN THE MASTER PERMIT-
 20071263. PLEASE PROVIDE THE FOLLOWING ITEMS: THE SPECS
 FOR THE BBQ GRILL AND FIREPIT WERE NOT SUBMITTED.
 PLEASE DO NOT SUBMIT ENTIRE INSTALLATION MANUALS- THOSE
 CAN BE ONSITE. SUBMIT ONLY THE MANUFACTURER?S
 SPECIFICATIONS SHEETS WHICH ARE TYPICALLY ONE OR TWO
 DATA SHEETS THAT SHOW COMPLIANCE STANDARDS AND LISTING
 NUMBERS, BTUH CAPACITIES AND INPUT PRESSURES.
 A) FAILED. MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATER, BBQ GRILL, FIREPLACE, AND POOL HEATER-
 SECTIONS- G2408.1 & G2448.1. SEE NOTES UNDER ITEM 2
 ABOVE.
 C) FAILED. ADJUST THE $2000.00 VALUE ON THE APPLICATION
 TO INCLUDE THE COST OF THE NEW APPLIANCES- SECTION
 109.3 WPB. NO INCREASE IN VALUE OR DOCUMENTATION
 PROVIDED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By ccole Date 2021-01-28 Time 09:04 Rev Time 0.00
Received By ccole Date 2021-01-28 Time 07:53 Sent To  
Notes
2021-01-28 09:05:041ST REVIEW FBC-2017 RES.
 PERMIT- 20120717
 1/28/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER:
 A) PROVIDE THE SIZE OF THE PIPE FROM THE METER TO THE
 1ST AND 2ND TEES- G2413.4.1 FBC RES.
 B) PROVIDE THE SIZE OF THE PIPE DROP FROM THE 2ND TEE
 TO THE LOW PRESSURE REGULATOR, AND THE BRANCH PIPE
 SIZES FROM THE REGULATOR TO THE WATER HEATER, DRYER AND
 RANGE- G2413.4.1 & G2413.4.2.
 C) PROVIDE THE TOTAL GAS LOAD OF THE SYSTEM AND THE
 TOTAL DEVELOPED LENGTH FROM THE METER TO THE MOST
 REMOTE OUTLET- G2413.1, G2413.2, & G2413.4.1.
  
 2) THE TANKLESS WATER HEATER, BBQ, FIREPLACE, AND POOL
 HEATER WERE NOT INCLUDED IN THE MASTER PERMIT-
 20071263. PLEASE PROVIDE THE FOLLOWING ITEMS:
 A) MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATER,
 BBQ GRILL, FIREPLACE, AND POOL HEATER- SECTIONS-
 G2408.1 & G2448.1.
 B) PROVIDE A SITE PLAN SHOWING THE LOCATIONS OF THE NEW
 APPLIANCES- G2406.3
 C) ADJUST THE $2000.00 VALUE ON THE APPLICATION TO
 INCLUDE THE COST OF THE NEW APPLIANCES- SECTION 109.3
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-05-20 Time   Rev Time 0.00
Received By aoliver Date 2021-05-17 Time 08:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-04-13 Time   Rev Time 0.00
Received By aoliver Date 2021-04-09 Time 09:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-03-09 Time   Rev Time 0.00
Received By ccarvaja Date 2021-03-02 Time 08:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-01-28 Time   Rev Time 0.00
Received By ccarvaja Date 2021-01-25 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2021-05-20 Cont ID  
Sent By ccole Date 2021-05-20 Time 15:42 Rev Time 0.00
Received By ccole Date 2021-05-19 Time 07:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-04-13 Cont ID  
Sent By ccole Date 2021-04-13 Time 12:42 Rev Time 0.00
Received By ccole Date 2021-04-13 Time 10:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-03-09 Cont ID  
Sent By ccole Date 2021-03-09 Time 11:38 Rev Time 0.00
Received By ccole Date 2021-03-09 Time 11:22 Sent To  
Notes
2021-03-09 12:08:27PLUMBING FOR TANKLESS WATER HEATER UNDER PERMIT-
 20071263.
 POOL HEATER PLUMBING SHALL BE UNDER PERMIT- 21010921.
 CCOLE
 3/9/2021

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-01-28 Cont ID  
Sent By ccole Date 2021-01-28 Time 09:06 Rev Time 0.00
Received By ccole Date 2021-01-28 Time 07:52 Sent To  
Notes
2021-01-28 09:07:01PLUMBING UNDER MASTER PERMIT- 20071263.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-03-09 Cont ID  
Sent By ccole Date 2021-03-09 Time 12:06 Rev Time 0.00
Received By ccole Date 2021-03-09 Time 11:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-28 Cont ID  
Sent By ccole Date 2021-01-28 Time 09:06 Rev Time 0.00
Received By ccole Date 2021-01-28 Time 07:53 Sent To  
Notes
***NONE***