Plan Review Details - Permit 20120587
Plan Review Stops For Permit 20120587
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-12-14 Cont ID  
Sent By shill Date 2020-12-14 Time 12:48 Rev Time 0.00
Received By shill Date 2020-12-14 Time 12:48 Sent To  
Notes
2020-12-14 12:48:42SEE 18100526
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2021-05-11 Cont ID  
Sent By scwelter Date 2021-05-11 Time 15:34 Rev Time 0.00
Received By scwelter Date 2021-05-11 Time 15:36 Sent To  
Notes
2021-05-11 15:36:09DEVELOPER SUBMITTED APPLICATION PASS CONTINGENT ON
 REVIEW BY ART COMMITTEE

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2023-05-03 Cont ID  
Sent By rmcdouga Date 2023-05-03 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2023-05-03 Time 15:44 Sent To  
Notes
2023-05-03 16:17:49FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 THE BEACH CLUB WAS PREVIOUSLY REVIEWED UNDER PERMIT
 #18100526. SOME OF THE CONSTRUCTION DOCUMENTS ARE WITH
 PERMIT #18100526.
  
 BUILDING PROVISO:
  
 1) PROPERTY TO BE REPLATTED PRIOR TO ISSUANCE OF THE
 FIRST C.O. PER SECTION 6(2)(E)(II) OF RESOLUTION NO.
 185-18 (THE "DEVELOPMENT ORDER").
  
 2) SUBMIT A BUILDING UNDER CONSTRUCTION ELEVATION
 CERTIFICATE WHEN THE FOUNDATION IS FORMED AND A
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE BEFORE THE
 FINAL INSPECTION.
  
 3) FLOOD PROOFING CERTIFICATE AND FINAL SURVEY TO BE
 SUBMITTED BEFORE FINAL INSPECTION.
  
 4) A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 5) DEFERRED SUBMITTALS REQUESTED BY ARCHITECT.
 DOCUMENTS SHOWING COMPLIANCE ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL (ARCHITECT OR
 ENGINEER FOR PRODUCT APPROVALS AND OTHER SPECIFICATION
 DOCUMENTS, STRUCTURAL ENGINEER OF RECORD APPROVAL AND
 REVIEW IS REQUIRED FOR DELEGATED ENGINEERING).
 SUBMITTAL, REVIEW AND APPROVAL ARE REQUIRED PRIOR TO
 INSTALLATION.
  
 6) COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S6.0 -
 S6.3 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS
 OPTIONS, INDICATE OPTION PROPOSED, ESPECIALLY IF NOT
 ALL OPTIONS COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 7) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2023-04-24 Cont ID  
Sent By rmcdouga Date 2023-04-24 Time 08:51 Rev Time 0.00
Received By rmcdouga Date 2023-04-21 Time 16:25 Sent To  
Notes
2023-04-24 08:41:25FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 6TH REVIEW
  
 DENIED - * NOTE: THE BEACH CLUB WAS PREVIOUSLY REVIEWED
 UNDER PERMIT #18100526. SOME OF THE CONSTRUCTION
 DOCUMENTS ARE WITH PERMIT #18100526.
  
 1) PROVISO. PROPERTY TO BE REPLATTED PRIOR TO ISSUANCE
 OF THE FIRST C.O. PER SECTION 6(2)(E)(II) OF RESOLUTION
 NO. 185-18 (THE "DEVELOPMENT ORDER").
  
 2) NOT RESOLVED. IN ORDER TO BE APPROVED FOR PERMIT,
 THE PRE-CONSTRUCTION WILL NEED TO BE CORRECTED. THE
 FLOOD PROOFING CERTIFICATE CAN BE DEFERRED UNTIL THE
 FINAL INSPECTION. ( FLOOD PROOFING CERTIFICATE AND
 FINAL SURVEY ARE BEING DEFERRED )
  
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
 **************************************************
 ( THE PRE-CONSTRUCTION ELEVATION CERTIFICATE THAT WAS
 SUBMITTED HAS THE FOLLOWING ERRORS:
 -1 SECTION C1 IS MARKED FOR FINISH CONSTRUCTION. THIS
 IS THE PRE-CONSTRUCTION E.C. WHICH IS BASED ON THE
 CONSTRUCTION DRAWINGS AND IS SUPPOSED TO BE SUBMITTED
 AND APPROVED BEFORE THE PERMIT IS ISSUED.
 -2 SECTION C2. E) IS FOR THE LOWEST EQUIPMENT THAT IS
 SERVICING THE BUILDING WHICH IS REQUIRED TO BE AT 9'-0"
 NAVD AND 7.3' IS SPECIFIED. THE COMMENT SECTION STATES
 THAT THIS IS FOR THE POOL EQUIPMENT PAD. THE POOL
 EQUIPMENT DOES NOT SERVICE THE BEACH CLUB BUILDING.
 THIS SHOULD BE EQUIPMENT FOR THE BUILDING ITSELF LIKE
 A/C.
 -3 THIS IS A PRE-CONSTRUCTION E.C. SO REMOVE THE PHOTOS
 OF THE BUILDING FROM THIS ONE, PHOTOS SHOULD ONLY BE
 ATTACHED TO THE UNDER CONSTRUCTION AND FINISHED
 CONSTRUCTION ELEVATION CERTIFICATES. )
  
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
 *******************************************************
 **************************************************
  
 CORRECTIONS REQUIRED FOR PRE-CONSTRUCTION ELEVATION
 CERTIFICATE:
 A) RESOLVED. SECTION A1. THE BUILDING OWNER IS RD IMV
 OWNER, LLC
 B) RESOLVED. SECTION A2. THE BUILDING STREET ADDRESS IS
 4328 N. FLAGLER DR.
 C) RESOLVED. SECTION C2 A) MAKE A NOTE IN THE COMMENTS
 SECTION THAT THE BUILDING IS TO BE DRY FLOOD PROOFED UP
 TO THE DFE OF 9'-0" NAVD
  
 CORRECTIONS REQUIRED FOR THE FLOODPROOFING CERTIFICATE:
 NOTE: FLOOD PROOFING CERTIFICATE TO BE SUBMITTED PRIOR
 TO RECIEVING THE CERTIFICATE OF OCCUPANCY.
 A) THE DRAWING NUMBER 1 OF 2 IN THE PACKAGE WILL NEED
 TO BE REPLACE BY THE CORRECTED DRAWING 1'-6" WATER
 HEIGHT TO THE DFE OF 9.00" NAVD. THE CORRECTED DRAWING
 IS REQUIRED TO BE DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER PREPARING THE FLOODPROOFING CERTIFICATE.
  
 WHEN THE BUILDING IS COMPLETED IN ORDER TO RECIEVE THE
 C.O. SUBMIT A COMPLETED ELEVATION CERTIFICATE FOR THE
 FINISHED CONSTRUCTION ALONG WITH A FINAL BOUNDARY
 SURVEY WITH ELEVATIONS THAT MATCHES THE E.C. AND THE
 FLOODPROOFING CERTIFICATE.
  
 [SUBMIT A CORRECTED FLOOD PROOFING FOR 9.0' NAVD AND A
 CORRECTED PRECONSTRUCTION ELEVATION CERTIFICATE. SEE
 THE NFIP REVIEW COMMENTS.] THE FLOOD PROOFING
 CERTIFICATE AND CALCULATIONS ARE FOR ONE FOOT ABOVE THE
 BFE WHICH IS 7.0 ' NAVD 88. THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE REQUIRES A TWO FOOT FREE BOARD.
 THIS SETS THE DFE AT 9.0' NAVD 88. YOU WILL NEED TO
 REVISE THE FLOOD PROOFING CERTIFICATE AND CALCULATIONS
 TO COMPLY WITH THE CITY'S TWO FOOT FREEBOARD
 REQUIREMENT.
  
 (OLD COMMENTS) YOU HAVE INDICATED THAT YOU WISH TO DRY
 FLOOD PROOF THE BEACH CLUB, PLEASE SUBMIT THE FOLLOWING
 ITEMS. FBC 1612
  
 [CORRECTIONS REQUIRED TO PRECONSTRUCTION ELEVATION
 CERTIFICATE. SEE NFIP REVIEW.] A) A NEW
 PRE-CONSTRUCTION ELEVATION CERTIFICATE FOR THE DRY
 FLOOD PROOFING.
  
 3) PROVISO. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR
 TO INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 4) PROVISO. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT.
 DOCUMENTS SHOWING COMPLIANCE ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL (ARCHITECT OR
 ENGINEER FOR PRODUCT APPROVALS AND OTHER SPECIFICATION
 DOCUMENTS, STRUCTURAL ENGINEER OF RECORD APPROVAL AND
 REVIEW IS REQUIRED FOR DELEGATED ENGINEERING).
 SUBMITTAL, REVIEW AND APPROVAL ARE REQUIRED PRIOR TO
 INSTALLATION.
  
 5) PROVISO. COMPONENT & CLADDING PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED TO
 THE BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES SHOWN
 ON SHEET S6.0 - S6.3 PRIOR TO SUBMITTAL. IF PRODUCT
 APPROVAL OFFERS OPTIONS, INDICATE OPTION PROPOSED,
 ESPECIALLY IF NOT ALL OPTIONS COMPLY WITH MINIMUM
 DESIGN PRESSURES.
  
 6) PROVISO. SEPARATE PERMITS (APPLICATIONS, PLANS, AND
 FEES) ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2023-04-11 Cont ID  
Sent By rmcdouga Date 2023-04-11 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2023-04-11 Time 16:50 Sent To  
Notes
2023-04-11 16:50:50FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 6TH REVIEW
  
 DENIED - * NOTE: THE BEACH CLUB WAS PREVIOUSLY REVIEWED
 UNDER PERMIT #18100526. SOME OF THE CONSTRUCTION
 DOCUMENTS ARE WITH PERMIT #18100526.
  
 1) PROVISO. PROPERTY TO BE REPLATTED PRIOR TO ISSUANCE
 OF THE FIRST C.O. PER SECTION 6(2)(E)(II) OF RESOLUTION
 NO. 185-18 (THE "DEVELOPMENT ORDER").
  
 2) NOT RESOLVED. IN ORDER TO BE APPROVED FOR PERMIT,
 THE PRE-CONSTRUCTION WILL NEED TO BE CORRECTED. THE
 FLOOD PROOFING CERTIFICATE CAN BE DEFERRED UNTIL THE
 FINAL INSPECTION.
  
 CORRECTIONS REQUIRED FOR PRE-CONSTRUCTION ELEVATION
 CERTIFICATE:
 A) SECTION A1. THE BUILDING OWNER IS RD IMV OWNER, LLC
 B) SECTION A2. THE BUILDING STREET ADDRESS IS 4328 N.
 FLAGLER DR.
 C) SECTION C2 A) MAKE A NOTE IN THE COMMENTS SECTION
 THAT THE BUILDING IS TO BE DRY FLOOD PROOFED UP TO THE
 DFE OF 9'-0" NAVD
  
 CORRECTIONS REQUIRED FOR THE FLOODPROOFING CERTIFICATE:
 A) THE DRAWING NUMBER 1 OF 2 IN THE PACKAGE WILL NEED
 TO BE REPLACE BY THE CORRECTED DRAWING 1'-6" WATER
 HEIGHT TO THE DFE OF 9.00" NAVD. THE CORRECTED DRAWING
 IS REQUIRED TO BE DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER PREPARING THE FLOODPROOFING CERTIFICATE.
  
 WHEN THE BUILDING IS COMPLETED IN ORDER TO RECIEVE THE
 C.O. SUBMIT A COMPLETED ELEVATION CERTIFICATE FOR THE
 FINISHED CONSTRUCTION ALONG WITH A FINAL BOUNDARY
 SURVEY WITH ELEVATIONS THAT MATCHES THE E.C. AND THE
 FLOODPROOFING CERTIFICATE.
  
 [SUBMIT A CORRECTED FLOOD PROOFING FOR 9.0' NAVD AND A
 CORRECTED PRECONSTRUCTION ELEVATION CERTIFICATE. SEE
 THE NFIP REVIEW COMMENTS.] THE FLOOD PROOFING
 CERTIFICATE AND CALCULATIONS ARE FOR ONE FOOT ABOVE THE
 BFE WHICH IS 7.0 ' NAVD 88. THE CITY OF WEST PALM
 BEACH'S FLOOD ORDINANCE REQUIRES A TWO FOOT FREE BOARD.
 THIS SETS THE DFE AT 9.0' NAVD 88. YOU WILL NEED TO
 REVISE THE FLOOD PROOFING CERTIFICATE AND CALCULATIONS
 TO COMPLY WITH THE CITY'S TWO FOOT FREEBOARD
 REQUIREMENT.
  
 (OLD COMMENTS) YOU HAVE INDICATED THAT YOU WISH TO DRY
 FLOOD PROOF THE BEACH CLUB, PLEASE SUBMIT THE FOLLOWING
 ITEMS. FBC 1612
  
 [CORRECTIONS REQUIRED TO PRECONSTRUCTION ELEVATION
 CERTIFICATE. SEE NFIP REVIEW.] A) A NEW
 PRE-CONSTRUCTION ELEVATION CERTIFICATE FOR THE DRY
 FLOOD PROOFING.
  
 3) PROVISO. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR
 TO INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 4) PROVISO. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT.
 DOCUMENTS SHOWING COMPLIANCE ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL (ARCHITECT OR
 ENGINEER FOR PRODUCT APPROVALS AND OTHER SPECIFICATION
 DOCUMENTS, STRUCTURAL ENGINEER OF RECORD APPROVAL AND
 REVIEW IS REQUIRED FOR DELEGATED ENGINEERING).
 SUBMITTAL, REVIEW AND APPROVAL ARE REQUIRED PRIOR TO
 INSTALLATION.
  
 5) PROVISO. COMPONENT & CLADDING PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED TO
 THE BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES SHOWN
 ON SHEET S6.0 - S6.3 PRIOR TO SUBMITTAL. IF PRODUCT
 APPROVAL OFFERS OPTIONS, INDICATE OPTION PROPOSED,
 ESPECIALLY IF NOT ALL OPTIONS COMPLY WITH MINIMUM
 DESIGN PRESSURES.
  
 6) PROVISO. SEPARATE PERMITS (APPLICATIONS, PLANS, AND
 FEES) ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-03-30 Cont ID  
Sent By rmcdouga Date 2023-03-30 Time 11:27 Rev Time 0.00
Received By rmcdouga Date 2023-03-30 Time 10:57 Sent To  
Notes
2023-03-30 11:27:04FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 5TH REVIEW
  
 DENIED - * NOTE: THE BEACH CLUB WAS PREVIOUSLY REVIEWED
 UNDER PERMIT #18100526. SOME OF THE CONSTRUCTION
 DOCUMENTS ARE WITH PERMIT #18100526.
  
 1) PROVISO. PROPERTY TO BE REPLATTED PRIOR TO ISSUANCE
 OF THE FIRST C.O. PER SECTION 6(2)(E)(II) OF RESOLUTION
 NO. 185-18 (THE "DEVELOPMENT ORDER").
  
 2) NOT RESOLVED. [SUBMIT A CORRECTED FLOOD PROOFING FOR
 9.0' NAVD AND A CORRECTED PRECONSTRUCTION ELEVATION
 CERTIFICATE. SEE THE NFIP REVIEW COMMENTS.] THE FLOOD
 PROOFING CERTIFICATE AND CALCULATIONS ARE FOR ONE FOOT
 ABOVE THE BFE WHICH IS 7.0 ' NAVD 88. THE CITY OF WEST
 PALM BEACH'S FLOOD ORDINANCE REQUIRES A TWO FOOT FREE
 BOARD. THIS SETS THE DFE AT 9.0' NAVD 88. YOU WILL NEED
 TO REVISE THE FLOOD PROOFING CERTIFICATE AND
 CALCULATIONS TO COMPLY WITH THE CITY'S TWO FOOT
 FREEBOARD REQUIREMENT.
  
 (OLD COMMENTS) YOU HAVE INDICATED THAT YOU WISH TO DRY
 FLOOD PROOF THE BEACH CLUB, PLEASE SUBMIT THE FOLLOWING
 ITEMS. FBC 1612
  
 [CORRECTIONS REQUIRED TO PRECONSTRUCTION ELEVATION
 CERTIFICATE. SEE NFIP REVIEW.] A) A NEW
 PRE-CONSTRUCTION ELEVATION CERTIFICATE FOR THE DRY
 FLOOD PROOFING.
  
 3) PROVISO. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR
 TO INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 4) PROVISO. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT.
 DOCUMENTS SHOWING COMPLIANCE ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL (ARCHITECT OR
 ENGINEER FOR PRODUCT APPROVALS AND OTHER SPECIFICATION
 DOCUMENTS, STRUCTURAL ENGINEER OF RECORD APPROVAL AND
 REVIEW IS REQUIRED FOR DELEGATED ENGINEERING).
 SUBMITTAL, REVIEW AND APPROVAL ARE REQUIRED PRIOR TO
 INSTALLATION.
  
 5) PROVISO. COMPONENT & CLADDING PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED TO
 THE BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES SHOWN
 ON SHEET S6.0 - S6.3 PRIOR TO SUBMITTAL. IF PRODUCT
 APPROVAL OFFERS OPTIONS, INDICATE OPTION PROPOSED,
 ESPECIALLY IF NOT ALL OPTIONS COMPLY WITH MINIMUM
 DESIGN PRESSURES.
  
 6) PROVISO. SEPARATE PERMITS (APPLICATIONS, PLANS, AND
 FEES) ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-02-21 Cont ID  
Sent By rmcdouga Date 2023-02-21 Time 14:55 Rev Time 0.00
Received By rmcdouga Date 2023-02-21 Time 14:55 Sent To  
Notes
2023-02-21 14:55:13FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 5TH REVIEW
  
 DENIED - * NOTE: THE BEACH CLUB WAS PREVIOUSLY REVIEWED
 UNDER PERMIT #18100526. SOME OF THE CONSTRUCTION
 DOCUMENTS ARE WITH PERMIT #18100526.
  
 1) WILL COMPLY. PROPERTY TO BE REPLATTED PRIOR TO
 ISSUANCE OF THE FIRST C.O. PER SECTION 6(2)(E)(II) OF
 RESOLUTION NO. 185-18 (THE "DEVELOPMENT ORDER").
  
 2) NOT RESOLVED. THE FLOOD PROOFING CERTIFICATE AND
 CALCULATIONS ARE FOR ONE FOOT ABOVE THE BFE WHICH IS
 7.0 ' NAVD 88. THE CITY OF WEST PALM BEACH'S FLOOD
 ORDINANCE REQUIRES A TWO FOOT FREE BOARD. THIS SETS THE
 DFE AT 9.0' NAVD 88. YOU WILL NEED TO REVISE THE FLOOD
 PROOFING CERTIFICATE AND CALCULATIONS TO COMPLY WITH
 THE CITY'S TWO FOOT FREEBOARD REQUIREMENT.
  
 (OLD COMMENTS) YOU HAVE INDICATED THAT YOU WISH TO DRY
 FLOOD PROOF THE BEACH CLUB, PLEASE SUBMIT THE FOLLOWING
 ITEMS. FBC 1612
  
 [CORRECTIONS REQUIRED TO PRECONSTRUCTION ELEVATION
 CERTIFICATE. SEE NFIP REVIEW.] A) A NEW
 PRE-CONSTRUCTION ELEVATION CERTIFICATE FOR THE DRY
 FLOOD PROOFING.
  
 COMPLIED. B) PROVIDE A DRY FLOOD PROOFING PLAN THAT
 INCLUDES WHERE THE PANELS ARE TO BE STORED AND WHO WILL
 BE RESPONSIBLE FOR INSTALLING THEM WHEN A FLOOD EVENT
 IS EXPECTED.
  
 [WATERPROOFING FOR THE WALLS IS NOT SHOWN OR SPECIFIED
 ON THE PLANS.] C) SHOW HOW THE WALLS WILL BE WATER
 PROOFED UP TO THE DESIGN FLOOD ELEVATION OF 9.0' NAVD
 88.
  
 [ ANY EQUIPMENT THAT CAN BE DAMAGED FROM FLOOD WATERS
 ARE REQUIRED TO BE PROTECTED.] D) THE PLANS SHOW
 KITCHEN EQUIPMENT AND A MEDIA CABINET IN THE OUTSIDE
 BAR AREA. SPECIFY HOW THAT AREA WILL BE PROTECTED FROM
 FLOOD WATERS.
  
 [ THERE IS NOTHING SHOWN ON THE PLANS OR ANY ENGINEER'S
 CALCULATIONS TO SHOW THAT THE WALLS ARE CAPABLE OF
 WITHSTANDING THE FORCES OF FLOOD WATERS. ] E) PROVIDE
 ENGINEERING TO SHOW THAT THE WALLS OF THE BEACH CLUB
 WILL BE ABLE TO WITHSTAND THE STATIC AND DYNAMIC
 PRESSURES FROM FLOOD WATERS UP TO THE DESIGN FLOOD
 ELEVATION OF 9.0' NAVD 88.
  
 I WILL SEND YOU THE REQUIRED FLOOD PROOFING CERTIFICATE
 FORM AND THE NFPI TECHNICAL BULLETIN ON THE
 REQUIREMENTS FOR DESIGN AND CERTIFICATION OF DRY FLOOD
 PROOFING... JUST LET ME KNOW WHERE TO SEND IT.
  
 (PREVIOUS COMMENT) SHEET A1.420 SPECIFIES THE FINISH
 FLOOR ELEVATION FOR THE BEACH CLUB AS 7.64' NAVD 88.
 SUBMIT THE PRE-CONSTRUCTION ELEVATION CERTIFICATE THAT
 WAS SUBMITTED FOR THE BEACH CLUB UNDER PERMIT #18100526
 HAS THE FFE AS 9.0' NAVD 88. PLEASE CLARIFY.
 THE PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A BASE
 FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD
 ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE
 DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL
 EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD
 POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES.
 THE PRECONSTRUCTION ELEV. CERT. BASED ON THE
 CONSTRUCTION DRAWING HAS BEEN SUBMITTED. THE SECOND, A
 CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR
 FORMS AND THE THIRD A FINAL ELEV. CERT. BASED ON THE
 FINISHED BUILDING ARE TO BE SUBMITTED IN A TIMELY
 MANNER. THE CITY'S FLOOD ORDINANCE ARTICLE XVII - FLOOD
 PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS FOR
 FLOOD HAZARD REDUCTION.
  
 3) WILL COMPLY. A SEPARATE ROOF PERMIT IS REQUIRED.
 PRIOR TO INSTALLATION, SUBMIT ROOF PERMIT APPLICATION
 WITH PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD
 AND ENGINEERING (IF APPLICABLE).
  
 4) WILL COMPLY. DEFERRED SUBMITTALS REQUESTED BY
 ARCHITECT. DOCUMENTS SHOWING COMPLIANCE ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL
 (ARCHITECT OR ENGINEER FOR PRODUCT APPROVALS AND OTHER
 SPECIFICATION DOCUMENTS, STRUCTURAL ENGINEER OF RECORD
 APPROVAL AND REVIEW IS REQUIRED FOR DELEGATED
 ENGINEERING). SUBMITTAL, REVIEW AND APPROVAL ARE
 REQUIRED PRIOR TO INSTALLATION.
  
 5) WILL COMPLY. COMPONENT & CLADDING PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED TO
 THE BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES SHOWN
 ON SHEET S6.0 - S6.3 PRIOR TO SUBMITTAL. IF PRODUCT
 APPROVAL OFFERS OPTIONS, INDICATE OPTION PROPOSED,
 ESPECIALLY IF NOT ALL OPTIONS COMPLY WITH MINIMUM
 DESIGN PRESSURES.
  
 6) WILL COMPLY. SEPARATE PERMITS (APPLICATIONS, PLANS,
 AND FEES) ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) WILL COMPLY. CONSTRUCTION HOURS - 7AM TO 7PM
 MON-FRI, 8AM TO 8PM SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-12-22 Cont ID  
Sent By rmcdouga Date 2022-12-22 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2022-12-22 Time 06:22 Sent To  
Notes
2022-12-22 11:15:49FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 DENIED - * NOTE: THE BEACH CLUB WAS PREVIOUSLY REVIEWED
 UNDER PERMIT #18100526. SOME OF THE CONSTRUCTION
 DOCUMENTS ARE WITH PERMIT #18100526.
  
 1) WILL COMPLY. PROPERTY TO BE REPLATTED PRIOR TO
 ISSUANCE OF THE FIRST C.O. PER SECTION 6(2)(E)(II) OF
 RESOLUTION NO. 185-18 (THE "DEVELOPMENT ORDER").
  
 2) NOT RESOLVED. YOU HAVE INDICATED THAT YOU WISH TO
 DRY FLOOD PROOF THE BEACH CLUB, PLEASE SUBMIT THE
 FOLLOWING ITEMS. FBC 1612
  
 [CORRECTIONS REQUIRED TO PRECONSTRUCTION ELEVATION
 CERTIFICATE. SEE NFIP REVIEW.] A) A NEW
 PRE-CONSTRUCTION ELEVATION CERTIFICATE FOR THE DRY
 FLOOD PROOFING.
  
 COMPLIED. B) PROVIDE A DRY FLOOD PROOFING PLAN THAT
 INCLUDES WHERE THE PANELS ARE TO BE STORED AND WHO WILL
 BE RESPONSIBLE FOR INSTALLING THEM WHEN A FLOOD EVENT
 IS EXPECTED.
  
 [WATERPROOFING FOR THE WALLS IS NOT SHOWN OR SPECIFIED
 ON THE PLANS.] C) SHOW HOW THE WALLS WILL BE WATER
 PROOFED UP TO THE DESIGN FLOOD ELEVATION OF 9.0' NAVD
 88.
  
 [ ANY EQUIPMENT THAT CAN BE DAMAGED FROM FLOOD WATERS
 ARE REQUIRED TO BE PROTECTED.] D) THE PLANS SHOW
 KITCHEN EQUIPMENT AND A MEDIA CABINET IN THE OUTSIDE
 BAR AREA. SPECIFY HOW THAT AREA WILL BE PROTECTED FROM
 FLOOD WATERS.
  
 [ THERE IS NOTHING SHOWN ON THE PLANS OR ANY ENGINEER'S
 CALCULATIONS TO SHOW THAT THE WALLS ARE CAPABLE OF
 WITHSTANDING THE FORCES OF FLOOD WATERS. ] E) PROVIDE
 ENGINEERING TO SHOW THAT THE WALLS OF THE BEACH CLUB
 WILL BE ABLE TO WITHSTAND THE STATIC AND DYNAMIC
 PRESSURES FROM FLOOD WATERS UP TO THE DESIGN FLOOD
 ELEVATION OF 9.0' NAVD 88.
  
 I WILL SEND YOU THE REQUIRED FLOOD PROOFING CERTIFICATE
 FORM AND THE NFPI TECHNICAL BULLETIN ON THE
 REQUIREMENTS FOR DESIGN AND CERTIFICATION OF DRY FLOOD
 PROOFING... JUST LET ME KNOW WHERE TO SEND IT.
  
 (PREVIOUS COMMENT) SHEET A1.420 SPECIFIES THE FINISH
 FLOOR ELEVATION FOR THE BEACH CLUB AS 7.64' NAVD 88.
 SUBMIT THE PRE-CONSTRUCTION ELEVATION CERTIFICATE THAT
 WAS SUBMITTED FOR THE BEACH CLUB UNDER PERMIT #18100526
 HAS THE FFE AS 9.0' NAVD 88. PLEASE CLARIFY.
 THE PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A BASE
 FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD
 ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE
 DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL
 EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD
 POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES.
 THE PRECONSTRUCTION ELEV. CERT. BASED ON THE
 CONSTRUCTION DRAWING HAS BEEN SUBMITTED. THE SECOND, A
 CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR
 FORMS AND THE THIRD A FINAL ELEV. CERT. BASED ON THE
 FINISHED BUILDING ARE TO BE SUBMITTED IN A TIMELY
 MANNER. THE CITY'S FLOOD ORDINANCE ARTICLE XVII - FLOOD
 PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS FOR
 FLOOD HAZARD REDUCTION.
  
 3) WILL COMPLY. A SEPARATE ROOF PERMIT IS REQUIRED.
 PRIOR TO INSTALLATION, SUBMIT ROOF PERMIT APPLICATION
 WITH PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD
 AND ENGINEERING (IF APPLICABLE).
  
 4) WILL COMPLY. DEFERRED SUBMITTALS REQUESTED BY
 ARCHITECT. DOCUMENTS SHOWING COMPLIANCE ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL
 (ARCHITECT OR ENGINEER FOR PRODUCT APPROVALS AND OTHER
 SPECIFICATION DOCUMENTS, STRUCTURAL ENGINEER OF RECORD
 APPROVAL AND REVIEW IS REQUIRED FOR DELEGATED
 ENGINEERING). SUBMITTAL, REVIEW AND APPROVAL ARE
 REQUIRED PRIOR TO INSTALLATION.
  
 5) WILL COMPLY. COMPONENT & CLADDING PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD ARE TO BE SUBMITTED TO
 THE BUILDING DIVISION, REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES SHOWN
 ON SHEET S6.0 - S6.3 PRIOR TO SUBMITTAL. IF PRODUCT
 APPROVAL OFFERS OPTIONS, INDICATE OPTION PROPOSED,
 ESPECIALLY IF NOT ALL OPTIONS COMPLY WITH MINIMUM
 DESIGN PRESSURES.
  
 6) WILL COMPLY. SEPARATE PERMITS (APPLICATIONS, PLANS,
 AND FEES) ARE REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) WILL COMPLY. CONSTRUCTION HOURS - 7AM TO 7PM
 MON-FRI, 8AM TO 8PM SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-30 Cont ID  
Sent By rmcdouga Date 2022-09-30 Time 14:41 Rev Time 0.00
Received By rmcdouga Date 2022-09-30 Time 09:53 Sent To  
Notes
2022-09-30 13:13:03FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 DENIED - * NOTE: THE BEACH CLUB WAS PREVIOUSLY REVIEWED
 UNDER PERMIT #18100526. SOME OF THE CONSTRUCTION
 DOCUMENTS ARE WITH PERMIT #18100526.
  
 1) PROPERTY TO BE REPLATTED PRIOR TO ISSUANCE OF THE
 FIRST C.O. PER SECTION 6(2)(E)(II) OF RESOLUTION NO.
 185-18 (THE "DEVELOPMENT ORDER").
  
 2) YOU HAVE INDICATED THAT YOU WISH TO DRY FLOOD PROOF
 THE BEACH CLUB, PLEASE SUBMIT THE FOLLOWING ITEMS. FBC
 1612
 A) A NEW PRE-CONSTRUCTION ELEVATION CERTIFICATE FOR THE
 DRY FLOOD PROOFING.
 B) PROVIDE A DRY FLOOD PROOFING PLAN THAT INCLUDES
 WHERE THE PANELS ARE TO BE STORED AND WHO WILL BE
 RESPONSIBLE FOR INSTALLING THEM WHEN A FLOOD EVENT IS
 EXPECTED.
 C) SHOW HOW THE WALLS WILL BE WATER PROOFED UP TO THE
 DESIGN FLOOD ELEVATION OF 9.0' NAVD 88.
 D) THE PLANS SHOW KITCHEN EQUIPMENT AND A MEDIA CABINET
 IN THE OUTSIDE BAR AREA. SPECIFY HOW THAT AREA WILL BE
 PROTECTED FROM FLOOD WATERS.
 E) PROVIDE ENGINEERING TO SHOW THAT THE WALLS OF THE
 BEACH CLUB WILL BE ABLE TO WITHSTAND THE STATIC AND
 DYNAMIC PRESSURES FROM FLOOD WATERS UP TO THE DESIGN
 FLOOD ELEVATION OF 9.0' NAVD 88.
 I WILL SEND YOU THE REQUIRED FLOOD PROOFING CERTIFICATE
 FORM AND THE NFPI TECHNICAL BULLETIN ON THE
 REQUIREMENTS FOR DESIGN AND CERTIFICATION OF DRY FLOOD
 PROOFING... JUST LET ME KNOW WHERE TO SEND IT.
  
 (PREVIOUS COMMENT) SHEET A1.420 SPECIFIES THE FINISH
 FLOOR ELEVATION FOR THE BEACH CLUB AS 7.64' NAVD 88.
 SUBMIT THE PRE-CONSTRUCTION ELEVATION CERTIFICATE THAT
 WAS SUBMITTED FOR THE BEACH CLUB UNDER PERMIT #18100526
 HAS THE FFE AS 9.0' NAVD 88. PLEASE CLARIFY.
 THE PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A BASE
 FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD
 ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE
 DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL
 EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD
 POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES.
 THE PRECONSTRUCTION ELEV. CERT. BASED ON THE
 CONSTRUCTION DRAWING HAS BEEN SUBMITTED. THE SECOND, A
 CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR
 FORMS AND THE THIRD A FINAL ELEV. CERT. BASED ON THE
 FINISHED BUILDING ARE TO BE SUBMITTED IN A TIMELY
 MANNER. THE CITY'S FLOOD ORDINANCE ARTICLE XVII - FLOOD
 PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS FOR
 FLOOD HAZARD REDUCTION.
  
 3) A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 4) DEFERRED SUBMITTALS REQUESTED BY ARCHITECT.
 DOCUMENTS SHOWING COMPLIANCE ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL (ARCHITECT OR
 ENGINEER FOR PRODUCT APPROVALS AND OTHER SPECIFICATION
 DOCUMENTS, STRUCTURAL ENGINEER OF RECORD APPROVAL AND
 REVIEW IS REQUIRED FOR DELEGATED ENGINEERING).
 SUBMITTAL, REVIEW AND APPROVAL ARE REQUIRED PRIOR TO
 INSTALLATION.
  
 5) COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S6.0 -
 S6.3 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS
 OPTIONS, INDICATE OPTION PROPOSED, ESPECIALLY IF NOT
 ALL OPTIONS COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 6) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-13 Cont ID  
Sent By rmcdouga Date 2022-07-13 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2022-07-13 Time 10:38 Sent To  
Notes
2022-07-13 14:24:53FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 DENIED - * NOTE: THE BEACH CLUB WAS PREVIOUSLY REVIEWED
 UNDER PERMIT #18100526. SOME OF THE CONSTRUCTION
 DOCUMENTS ARE WITH PERMIT #18100526.
  
 1) PROPERTY TO BE REPLATTED PRIOR TO ISSUANCE OF THE
 FIRST C.O. PER SECTION 6(2)(E)(II) OF RESOLUTION NO.
 185-18 (THE "DEVELOPMENT ORDER").
  
 2) SHEET A1.420 SPECIFIES THE FINISH FLOOR ELEVATION
 FOR THE BEACH CLUB AS 7.64' NAVD 88. THE
 PRE-CONSTRUCTION ELEVATION CERTIFICATE THAT WAS
 SUBMITTED FOR THE BEACH CLUB UNDER PERMIT #18100526 HAS
 THE FFE AS 9.0' NAVD 88. PLEASE CLARIFY.
 THE PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A BASE
 FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD
 ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE
 DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL
 EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD
 POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES.
 THE PRECONSTRUCTION ELEV. CERT. BASED ON THE
 CONSTRUCTION DRAWING HAS BEEN SUBMITTED. THE SECOND, A
 CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR
 FORMS AND THE THIRD A FINAL ELEV. CERT. BASED ON THE
 FINISHED BUILDING ARE TO BE SUBMITTED IN A TIMELY
 MANNER. THE CITY'S FLOOD ORDINANCE ARTICLE XVII - FLOOD
 PREVENTION AND CONTROL SEC. 94-546 - PROVISIONS FOR
 FLOOD HAZARD REDUCTION.
  
 3) A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 4) DEFERRED SUBMITTALS REQUESTED BY ARCHITECT.
 DOCUMENTS SHOWING COMPLIANCE ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL (ARCHITECT OR
 ENGINEER FOR PRODUCT APPROVALS AND OTHER SPECIFICATION
 DOCUMENTS, STRUCTURAL ENGINEER OF RECORD APPROVAL AND
 REVIEW IS REQUIRED FOR DELEGATED ENGINEERING).
 SUBMITTAL, REVIEW AND APPROVAL ARE REQUIRED PRIOR TO
 INSTALLATION.
  
 5) COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SHOWN ON SHEET S6.0 -
 S6.3 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS
 OPTIONS, INDICATE OPTION PROPOSED, ESPECIALLY IF NOT
 ALL OPTIONS COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 6) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS AND SPAS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 7) CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By rmcdouga Date 2021-04-21 Time 16:00 Rev Time 0.00
Received By rmcdouga Date 2021-04-21 Time 16:00 Sent To  
Notes
2020-12-14 12:48:58SEE 18100526
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-13 Cont ID  
Sent By jleahy Date 2021-12-13 Time 11:08 Rev Time 0.00
Received By jleahy Date 2021-12-13 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By jleahy Date 2021-04-22 Time 07:54 Rev Time 0.00
Received By jleahy Date 2021-04-22 Time 07:54 Sent To  
Notes
2021-04-22 08:00:31CONTACTED FRED GRAY FOR LOCATION OF PLANS FOR KITCHEN
 LAYOUT. 4/23/21 JL
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) AREA OUTSIDE OF THE BATHROOM, LOOKS LIKE A KITCHEN
 HAS NO ELECTRICAL PLAN I CAN FIND, PLEASE DIRECT TO OR
 SUBMIT PLAN. IT HAS A RISER WITH TWO PANELS SHOWING
 ICEMAKER AND OTHER EQUIPMENT NOT SHOWN ON PLANS.
  
 2) IS THERE ANY LIGHTING OUTSIDE AT KITCHEN/BAR?

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-04-22 Cont ID  
Sent By rrossano Date 2021-04-22 Time   Rev Time  
Received By rrossano Date 2021-04-22 Time   Sent To  
Notes
2021-04-22 07:09:05REVIEWED UNDER ENGINEERING SUBMITTAL E17090009.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-21 Cont ID  
Sent By pleduc Date 2021-04-21 Time   Rev Time 0.00
Received By pleduc Date 2021-04-21 Time 16:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-05-28 Cont ID  
Sent By rwbrown Date 2022-05-28 Time 10:04 Rev Time 0.00
Received By rwbrown Date 2022-05-28 Time 10:04 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-11-19 Cont ID  
Sent By lcrespo Date 2021-11-19 Time 12:56 Rev Time 0.00
Received By lcrespo Date 2021-11-19 Time 12:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2023-05-03 Cont ID  
Sent By rmcdouga Date 2023-05-03 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2023-05-03 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2023-04-24 Cont ID  
Sent By rmcdouga Date 2023-04-24 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2023-04-18 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2023-04-13 Cont ID  
Sent By aoliver Date 2023-04-13 Time 08:46 Rev Time 0.00
Received By aoliver Date 2023-04-03 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2023-03-30 Cont ID  
Sent By rmcdouga Date 2023-03-30 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2023-03-17 Time 12:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-02-22 Cont ID  
Sent By rmcdouga Date 2023-02-22 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2023-02-14 Time 16:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-12-22 Cont ID  
Sent By rmcdouga Date 2022-12-22 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2022-12-12 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-04 Cont ID  
Sent By lmarchan Date 2022-10-04 Time 15:57 Rev Time 0.00
Received By lmarchan Date 2022-08-17 Time 06:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-14 Cont ID  
Sent By aoliver Date 2022-07-14 Time 07:58 Rev Time 0.00
Received By aoliver Date 2022-05-24 Time 11:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-10 Cont ID  
Sent By lmarchan Date 2022-04-10 Time 07:00 Rev Time 0.00
Received By lmarchan Date 2021-10-21 Time 12:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-26 Cont ID  
Sent By lmarchan Date 2021-08-26 Time 15:28 Rev Time 0.00
Received By lmarchan Date 2021-04-21 Time 15:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2022-07-15 Cont ID  
Sent By aoliver Date 2022-07-15 Time 10:04 Rev Time 0.00
Received By aoliver Date 2021-04-21 Time 15:08 Sent To  
Notes
2022-07-13 16:52:097/13/22 IMPACT FEES PAID UNDER 18100526. EMAIL FROM
 PBCGOV UPLOADED AO
2022-07-13 11:54:477/13/22 EMAILED IMPACT AGAIN FOR REVIEW-AO
2021-04-21 15:09:5304/21/21 IMPACT FEES QUESTIONNAIRE UPLOADED IN
 PROJECTDOX. EMAILED PBC IMPACT FEES OFFICE.CC

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-11-04 Cont ID  
Sent By medwards Date 2021-11-04 Time 09:47 Rev Time 0.00
Received By medwards Date 2021-11-04 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-21 Cont ID  
Sent By medwards Date 2021-04-21 Time 15:53 Rev Time 0.00
Received By medwards Date 2021-01-27 Time 14:49 Sent To  
Notes
2021-04-21 15:53:431) PER PRIVISO ON THE MASTER PERMIT PLEASE PROVIDE THE
 KITCHEN EQUIPMENT.
 2) PLEASE PROVIDE THE SHEET NUMBER FOR THE BEACH CLUB
 ON THE MASTER PLANS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2021-01-27 14:50:24PLEASE SEE PERMIT #18100526

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 8 Status P Date 2023-05-03 Cont ID  
Sent By rmcdouga Date 2023-05-03 Time 15:45 Rev Time 0.00
Received By rmcdouga Date 2023-05-03 Time 15:44 Sent To  
Notes
2023-05-03 16:21:171) SUBMIT A BUILDING UNDER CONSTRUCTION ELEVATION
 CERTIFICATE WHEN THE FOUNDATION IS FORMED AND A
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE BEFORE THE
 FINAL INSPECTION.
  
 2) FLOOD PROOFING CERTIFICATE AND FINAL SURVEY TO BE
 SUBMITTED BEFORE FINAL INSPECTION.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 7 Status F Date 2023-04-24 Cont ID  
Sent By rmcdouga Date 2023-04-24 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2023-04-21 Time 16:25 Sent To  
Notes
2023-04-24 08:54:06THE PRE-CONSTRUCTION ELEVATION CERTIFICATE THAT WAS
 SUBMITTED HAS THE FOLLOWING ERRORS:
 -1 SECTION C1 IS MARKED FOR FINISH CONSTRUCTION. THIS
 IS THE PRE-CONSTRUCTION E.C. WHICH IS BASED ON THE
 CONSTRUCTION DRAWINGS AND IS SUPPOSED TO BE SUBMITTED
 AND APPROVED BEFORE THE PERMIT IS ISSUED.
 -2 SECTION C2. E) IS FOR THE LOWEST EQUIPMENT THAT IS
 SERVICING THE BUILDING WHICH IS REQUIRED TO BE AT 9'-0"
 NAVD AND 7.3' IS SPECIFIED. THE COMMENT SECTION STATES
 THAT THIS IS FOR THE POOL EQUIPMENT PAD. THE POOL
 EQUIPMENT DOES NOT SERVICE THE BEACH CLUB BUILDING.
 THIS SHOULD BE EQUIPMENT FOR THE BUILDING ITSELF LIKE
 A/C. )
 -3 THIS IS A PRE-CONSTRUCTION E.C. SO REMOVE THE PHOTOS
 OF THE BUILDING FROM THIS ONE, PHOTOS SHOULD ONLY BE
 ATTACHED TO THE UNDER CONSTRUCTION AND FINISHED
 CONSTRUCTION ELEVATION CERTIFICATES.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 6 Status F Date 2023-04-11 Cont ID  
Sent By rmcdouga Date 2023-04-11 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2023-04-11 Time 16:51 Sent To  
Notes
2023-04-11 16:52:31IN ORDER TO BE APPROVED FOR PERMIT, THE
 PRE-CONSTRUCTION WILL NEED TO BE CORRECTED. THE FLOOD
 PROOFING CERTIFICATE CAN BE DEFERRED UNTIL THE FINAL
 INSPECTION.
  
 CORRECTIONS REQUIRED FOR PRE-CONSTRUCTION ELEVATION
 CERTIFICATE:
 A) SECTION A1. THE BUILDING OWNER IS RD IMV OWNER, LLC
 B) SECTION A2. THE BUILDING STREET ADDRESS IS 4328 N.
 FLAGLER DR.
 C) SECTION C2 A) MAKE A NOTE IN THE COMMENTS SECTION
 THAT THE BUILDING IS TO BE DRY FLOOD PROOFED UP TO THE
 DFE OF 9'-0" NAVD
  
 CORRECTIONS REQUIRED FOR THE FLOODPROOFING CERTIFICATE:
 A) THE DRAWING NUMBER 1 OF 2 IN THE PACKAGE WILL NEED
 TO BE REPLACE BY THE CORRECTED DRAWING 1'-6" WATER
 HEIGHT TO THE DFE OF 9.00" NAVD. THE CORRECTED DRAWING
 IS REQUIRED TO BE DIGITALLY SIGNED AND SEALED BY THE
 ENGINEER PREPARING THE FLOODPROOFING CERTIFICATE.
  
 WHEN THE BUILDING IS COMPLETED IN ORDER TO RECIEVE THE
 C.O. SUBMIT A COMPLETED ELEVATION CERTIFICATE FOR THE
 FINISHED CONSTRUCTION ALONG WITH A FINAL BOUNDARY
 SURVEY WITH ELEVATIONS THAT MATCHES THE E.C. AND THE
 FLOODPROOFING CERTIFICATE.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 5 Status F Date 2023-03-30 Cont ID  
Sent By rmcdouga Date 2023-03-30 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2023-03-30 Time 10:57 Sent To  
Notes
2023-03-30 11:13:55ELEVATION CERTIFICATE REVIEW
 DENIED
  
 THESE REQUESTED CORRECTIONS HAVE NOT BEEN MADE. PLEASE
 MAKE THE FOLLOWING CORRECTIONS.
  
 SECTION A1. THE OWNERS NAME IS SHOULD BE RD IMV OWNER
 LLC
  
 SECTION A2. THE ADDRESS SHOULD BE 4328 N. FLAGLER DR.
  
 SECTION A4. THIS SHOULD STATE NON-RESIDENTIAL.
  
 SECTION C2 F). SPECIFY THE LOWEST ADJACENT GRADE NEXT
 TO THE BUILDING. (LAG)
  
 SECTION C2 G) SPECIFY THE HIGHEST ADJACENT GRADE NEXT
 TO THE BUILDING. (HAG)
  
 THE COMMENTS SECTION SHOULD SPECIFY THAT THE STRUCTURE
 IS BEING DRY FLOOD PROOFED UP TO THE DFE OF 9.0' NAVD
 88, SEE FLOOD PROOFING CERTIFICATE.
  
 THE FLOOD PROOFING CERTIFICATE AND OTHER DOCUMENTS ARE
 REQUIRED TO BE AT 9.0' NAVD 88 IN ORDER TO MEET THE
 CITY OF WEST PALM BEACHES MORE STRINGENT REQUIREMENT OF
 A 2' FREEBOARD ABOVE BFE.
  
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status F Date 2023-02-22 Cont ID  
Sent By rmcdouga Date 2023-02-22 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2023-02-21 Time 14:55 Sent To  
Notes
2023-02-21 14:57:42NOT RESULTED PENDING PEER REVIEW.
  
 ELEVATION CERTIFICATE REVIEW
 DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS.
  
 SECTION A1. THE OWNERS NAME IS SHOULD BE RD IMV OWNER
 LLC
  
 SECTION A2. THE ADDRESS SHOULD BE 4328 N. FLAGLER DR.
  
 SECTION A4. THIS SHOULD STATE NON-RESIDENTIAL.
  
 SECTION C2 E). SPECIFY THE LOWEST ELEVATION OF THE
 MACHINERY OR EQUIPMENT SERVICING THE BUILDING.
  
 SECTION C2 F). SPECIFY THE LOWEST ADJACENT GRADE NEXT
 TO THE BUILDING. (LAG)
  
 SECTION C2 G) SPECIFY THE HIGHEST ADJACENT GRADE NEXT
 TO THE BUILDING. (HAG)
  
 THE COMMENTS SECTION SHOULD SPECIFY THAT THE STRUCTURE
 IS BEING DRY FLOOD PROOFED UP TO THE DFE OF 9.0' NAVD
 88.
 THE COMMENT (INCLUDING TYPE OF EQUIPMENT AND LOCATION,
 PER C2(E), IF APPLICABLE ) NEEDS TO BE CLEARIFIED. DO
 YOU MEAN THAT THE EQUIPMENT WILL BE LOCATED AT DFE OF
 9.0' NAVD 88?
  
 DID NOT SEE THIS ON THE DRAWINGS FBC 1612.5 FLOOD
 HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
 1.3.FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24.
  
 THE FLOOD PROOFING CERTIFICATE AND OTHER DOCUMENTS ARE
 REQUIRED TO BE AT 9.0' NAVD 88 IN ORDER TO MEET THE
 CITY OF WEST PALM BEACHES MORE STRINGENT REQUIREMENT OF
 A 2' FREEBOARD ABOVE BFE.
  
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2022-12-22 Cont ID  
Sent By rmcdouga Date 2022-12-22 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2022-12-22 Time 11:17 Sent To  
Notes
2022-12-22 12:46:12ELEVATION CERTIFICATE REVIEW
 DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS.
  
 SECTION A1. THE OWNERS NAME IS SHOULD BE RD IMV OWNER
 LLC
  
 SECTION A2. THE ADDRESS SHOULD BE 4328 N. FLAGLER DR.
  
 SECTION A4. SHOULD BE NON-RESIDENTIAL.
  
 SECTION C2(E). SHOULD SPECIFY THE LOWEST ELEVATION OF
 EQUIPMENT SERVICING THE BUILDING.
  
 THE DIGITAL SIGNATURE OF THE SURVEYOR COULD NOT BE
 VERIFIED.
  
 DID NOT SEE THIS ON THE DRAWINGS ??? FBC 1612.5 FLOOD
 HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
 1.3.FOR DRY FLOODPROOFED NONRESIDENTIAL BUILDINGS,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DRY FLOODPROOFING IS DESIGNED IN ACCORDANCE WITH
 ASCE 24.
  
 SUBMIT THE FLOOD PROOFING CERTIFICATE FORM.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-09-30 Cont ID  
Sent By rmcdouga Date 2022-09-30 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2022-09-30 Time 09:53 Sent To  
Notes
2022-09-30 11:01:12SHEET A1.420 SPECIFIES THE FINISH FLOOR ELEVATION FOR
 THE BEACH CLUB AS 7.64' NAVD 88. SUBMIT A
 PRE-CONSTRUCTION ELEVATION FOR DRY FLOOD PROOFING. THE
 PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A BASE
 FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD
 ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE
 DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL
 EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD
 POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES.
 THE PRECONSTRUCTION ELEV. CERT. BASED ON THE
 CONSTRUCTION DRAWING HAS BEEN SUBMITTED. THE SECOND, A
 CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR
 FORMS AND THE THIRD A FINAL ELEV. CERT. BASED ON THE
 FINISHED BUILDING ARE TO BE SUBMITTED IN A TIMELY
 MANNER. A CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED
 FOR THE PROJECT UNTIL THE FINAL ELEVATION CERTIFICATE
 HAS BEEN REVIEWED AND APPROVED BY THIS OFFICE. THE
 CITY'S FLOOD ORDINANCE ARTICLE XVII - FLOOD PREVENTION
 AND CONTROL SEC. 94-546 - PROVISIONS FOR FLOOD HAZARD
 REDUCTION.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-07-13 Cont ID  
Sent By rmcdouga Date 2022-07-13 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2022-07-13 Time 14:25 Sent To  
Notes
2022-07-13 14:29:57SHEET A1.420 SPECIFIES THE FINISH FLOOR ELEVATION FOR
 THE BEACH CLUB AS 7.64' NAVD 88. THE PRE-CONSTRUCTION
 ELEVATION CERTIFICATE THAT WAS SUBMITTED FOR THE BEACH
 CLUB UNDER PERMIT #18100526 HAS THE FFE AS 9.0' NAVD
 88. PLEASE CLARIFY.
 THE PROPERTY IS LOCATED IN AN AE FLOOD ZONE WITH A BASE
 FLOOD ELEVATION OF 7' NAVD88. THE CITY'S FLOOD
 ORDINANCE REQUIRES A 2' FREEBOARD WHICH MAKES THE
 DESIGN FLOOD ELEVATION FOR THIS PROJECT 9.0'. ALL
 EQUIPMENT SERVICING THE BUILDING IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD. ELEVATION CERTIFICATES WILL BE
 REQUIRED TO SHOW COMPLIANCE WITH THE CITY'S FLOOD
 POLICY. THE CITY REQUIRES THREE ELEVATION CERTIFICATES.
 THE PRECONSTRUCTION ELEV. CERT. BASED ON THE
 CONSTRUCTION DRAWING HAS BEEN SUBMITTED. THE SECOND, A
 CONSTRUCTION ELEV. CERT. BASED ON THE LOWEST FLOOR
 FORMS AND THE THIRD A FINAL ELEV. CERT. BASED ON THE
 FINISHED BUILDING ARE TO BE SUBMITTED IN A TIMELY
 MANNER. A CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED
 FOR THE PROJECT UNTIL THE FINAL ELEVATION CERTIFICATE
 HAS BEEN REVIEWED AND APPROVED BY THIS OFFICE. THE
 CITY'S FLOOD ORDINANCE ARTICLE XVII - FLOOD PREVENTION
 AND CONTROL SEC. 94-546 - PROVISIONS FOR FLOOD HAZARD
 REDUCTION.

Review Stop P PLUMBING
Rev No 6 Status P Date 2023-02-15 Cont ID  
Sent By rwbrown Date 2023-02-15 Time 15:24 Rev Time 0.00
Received By rwbrown Date 2023-02-15 Time 15:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2022-09-07 Cont ID  
Sent By rwbrown Date 2022-09-07 Time 10:37 Rev Time 0.00
Received By rwbrown Date 2022-09-07 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2022-08-22 Cont ID  
Sent By rwbrown Date 2022-08-22 Time 07:41 Rev Time 0.00
Received By rwbrown Date 2022-08-22 Time 07:41 Sent To  
Notes
2022-08-22 07:48:034TH PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. DONE
  
 3. THERE NEEDS TO BE ONE AT EACH HOT WATER SOURCE
 INCLUDING THE WATER HEATER. THIS REQUIREMENT IS FOR ALL
 HOT WATER, NOT JUST TEMPERED WATER AT PUBLIC HAND
 WASHING STATIONS. 2020 FPC - 607.1.1 TEMPERATURE
 LIMITING MEANS - THE THERMOSTAT CONTROL ON THE WATER
 HEATER CANNOT BE THE LIMITING DEVICE FOR HOT WATER
 DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE
 FOR THE PURPOSE OF HOT WATER DELIVERY. THIS WOULD BE IN
 ADDITION TO THE REQUIREMENTS FOR TEMPERED WATER FOR
 PUBLIC HANDWASHING 607.1.2/419.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-05-28 Cont ID  
Sent By rwbrown Date 2022-05-28 Time 10:04 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-05-28 10:04:253RD PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.1 - THE GREASE INTERCEPTOR SHALL
 ONLY RECEIVE DISCHARGE FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. THE
 HANDSINKS AND ICEMAKER CANNOT DISCHARGE INTO THE GREASE
 WASTE.
  
 2. CITY ORDINANCE SEC. 90 - 126 - THE POOL BACKWASH
 DISCHARGE CANNOT GO DIRECTLY INTO THE SANITARY UNLESS
 SPECIFICALLY AUTHORIZED BY THE CITY IN WRITING OR
 OTHERWISE TREATED 1ST.
  
 3. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-11-19 Cont ID  
Sent By lcrespo Date 2021-11-19 Time 11:52 Rev Time 0.00
Received By lcrespo Date 2021-11-19 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By lcrespo Date 2021-04-22 Time 14:51 Rev Time 0.00
Received By lcrespo Date 2021-04-22 Time 11:59 Sent To  
Notes
2021-04-22 14:52:3404/22/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A SET OF PLANS FOR THE KITCHEN/BAR
 AREA THAT INCUR SANITARY, WATER, AND GAS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2020-12-14 Cont ID  
Sent By shill Date 2020-12-14 Time 12:49 Rev Time 0.00
Received By shill Date 2020-12-14 Time 12:49 Sent To  
Notes
2020-12-14 12:49:34SEE 18100526
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-12-14 Cont ID  
Sent By shill Date 2020-12-14 Time 12:49 Rev Time 0.00
Received By shill Date 2020-12-14 Time 12:49 Sent To  
Notes
2020-12-14 12:50:24PLANS WITH 18100526
 **PROVISO** PRODUCT APPROVALS DEFERRED; SUBMIT WITH
 ROOF SUB PERMIT APPLICATION
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-03-30 Cont ID  
Sent By rmcdouga Date 2023-03-30 Time 11:32 Rev Time 0.00
Received By rmcdouga Date 2023-03-30 Time 11:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-02-15 Cont ID  
Sent By rwbrown Date 2023-02-15 Time 15:26 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-12-22 Cont ID  
Sent By rmcdouga Date 2022-12-22 Time 12:55 Rev Time 0.00
Received By rmcdouga Date 2022-12-22 Time 12:55 Sent To  
Notes
2022-12-22 13:25:07I COULD NOT VERIFY THE ENGINEER'S DIGITAL SIGNATURE ON
 THE BOILER DRAWINGS SHEET P6.04.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-22 Cont ID  
Sent By rwbrown Date 2022-08-22 Time 07:54 Rev Time 0.00
Received By rwbrown Date 2022-08-22 Time 07:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-13 Cont ID  
Sent By rmcdouga Date 2022-07-13 Time 14:58 Rev Time 0.00
Received By rmcdouga Date 2022-07-13 Time 14:58 Sent To  
Notes
2022-07-13 15:01:18SEE 18100526
 PLANS WITH 18100526
 DIGITAL SIGNATURES ON PLANS SUBMITTED WITH 20120587 ARE
 OKAY.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-12-14 Cont ID  
Sent By shill Date 2020-12-14 Time 12:50 Rev Time 0.00
Received By shill Date 2020-12-14 Time 12:50 Sent To  
Notes
2020-12-14 12:50:49SEE 18100526
 PLANS WITH 18100526
  

Review Stop Z ZONING
Rev No 4 Status P Date 2022-10-04 Cont ID  
Sent By jroach Date 2022-10-04 Time 14:43 Rev Time 0.00
Received By jroach Date 2022-10-04 Time 14:43 Sent To  
Notes
2022-10-04 14:46:13ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 10.04.2022
 PERMIT NO.: 20120587
 ________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THIS PERMIT REVIEW IS LIMITED TO THE BEACH CLUB
 ONLY.
  
 2. ALL DEVELOPMENT WITHIN THE MARINA COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD) SHALL BE SUBJECT TO ALL
 DEVELOPMENT ORDER CONDITIONS, DESIGN GUIDELINES, ETC.,
 AS OUTLINED IN RESOLUTION NO. 66-22, AND AS MAY BE
 AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY THE
 DEVELOPMENT ORDER SHALL BE ADDRESSED WITHIN THE
 APPROPRIATE SPECIFIED TIMEFRAMES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ??? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-06-13 Cont ID  
Sent By jroach Date 2022-06-13 Time 11:05 Rev Time 0.00
Received By jroach Date 2022-06-13 Time 10:57 Sent To  
Notes
2022-06-13 11:05:59ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 06.13.2023
 PERMIT NO.: 20120587
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE SITE PLAN SUBMITTED DOES NOT MATCH THE LATEST
 SITE PLAN SUBMITTED AS PART OF THE COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD). ALL PLANS SHALL MATCH THAT
 WHICH WAS SUBMITTED/APPROVED AS PART OF THE CMPD.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-04-08 Cont ID  
Sent By jroach Date 2022-04-08 Time 12:39 Rev Time 0.00
Received By jroach Date 2022-04-08 Time 12:39 Sent To  
Notes
2022-04-08 12:40:33CHANGES ARE BEING SUBMITTED, ZONING REVIEW WILL BE
 COMPLETED WITH THE RESUBMITTAL.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-08-26 Cont ID  
Sent By jroach Date 2021-08-26 Time 14:45 Rev Time 0.00
Received By jroach Date 2021-08-26 Time 14:45 Sent To  
Notes
2021-08-26 14:45:47ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 08.23.2021
 PERMIT NO.: 20120587
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE SITE PLAN SUBMITTED DOES NOT MATCH THE LATEST
 SITE PLAN SUBMITTED AS PART OF THE COMMERCIAL MARINE
 PLANNED DEVELOPMENT (CMPD). ALL PLANS SHALL MATCH THAT
 WHICH WAS SUBMITTED/APPROVED AS PART OF THE CMPD.
  
 2. ACCORDING TO THE LATEST SITE PLAN SUBMITTED AS PART
 OF THE CMPD, THE SIZE OF THE BEACH CLUB (OVERHANG) HAS
 INCREASED. PURSUANT TO THE DESIGN GUIDELINES, THE BEACH
 CLUB IS TO BE A MINIMUM OF 20 FEET FROM THE SEAWALL. AS
 THE OVERHANG HAS SUPPORT POSTS, THE MINIMUM 20 FOOT
 SETBACK (AS DEFINED BY THE ZLDRS) IS TO BE FROM THE
 SUPPORT COLUMN TO THE SEAWALL. EITHER THE PLAN SHALL BE
 REVISED TO MEET THE MINIMUM SETBACK REQUIREMENT, OR A
 MAJOR AMENDMENT TO THE CMPD SHALL BE APPROVED TO MODIFY
 THE SETBACK REQUIREMENTS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  