Plan Review Details - Permit 20120569
Plan Review Stops For Permit 20120569
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-12 Cont ID  
Sent By cpuell Date 2021-01-12 Time 10:43 Rev Time 0.00
Received By cpuell Date 2021-01-12 Time 10:43 Sent To  
Notes
2021-01-12 10:44:01ADDRESS CHANGED FROM 3210 S OLIVE AVE TO 3218 S OLIVE
 AVE

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-12 Cont ID  
Sent By cpuell Date 2020-12-12 Time 08:40 Rev Time 0.00
Received By cpuell Date 2020-12-12 Time 08:40 Sent To  
Notes
2020-12-12 08:41:15PLEASE REACH OUT TO [email protected], TO DISCUSS ADDRESS
 CHANGES, PROPOERTY FOOTPRINT HAS CHANGED, WHICH MEANS
 THE ROAD CENTERLINE POSITIONS HAVE CHANGES, PROPERTY
 NEEDS A NEW ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-10 Cont ID  
Sent By cthroop Date 2021-03-10 Time 16:36 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 16:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 16:37 Rev Time 0.00
Received By cthroop Date 2021-03-09 Time 06:20 Sent To  
Notes
2021-03-09 16:38:55CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. RE-SUBMITTAL LETTER FROM DESIGNER SAYS TO SEE PLAN
 PAGES S-2 AND S-3 FOR CORRECTIONS. S-2 AND S-3 ARE
 MISSING FROM SUBMITTAL.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-14 Cont ID  
Sent By cthroop Date 2020-12-14 Time 13:16 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 06:12 Sent To  
Notes
2020-12-14 13:33:46CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: A SEPERATE DEMO PERMIT IS REQUIRED FOR EXISTING
 STRUCTURE.
  
 PROVISO'S:
  
 1. A SEPERATE PERMIT IS REQUIRED FOR SITE WALLS. PG
 A-101
  
 2. A SEPERATE PERMIT IS REQUIRED FOR ROOFING. PG A-203
  
 3. A SEPERATE PERMIT IS REQUIRED FOR FUEL GAS. PG P-1
  
 REVIEW COMMENTS:
  
 1. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2. THERE IS NO INSULATION TYPE OR R-VALUE ON PLANS.
 CEILING R-VALUE ON ENERGY SUBMITTAL IS 1.9. CEILING
 R-VALUE ON EPL CARD IS 38.0.
 PLEASE CLARIFY.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. PROVIDE A WINDOW SCHEDULE. INCLUDE DESIGN PRESSURES
 FOR EACH OPENING.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 4. PROVIDE A BEAM/ LINTEL SCHEDULE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 5. PROVIDE PRODUCT APPROVALS FOR PROPOSED LINTELS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 6. PROVIDE A TIE BEAM DETAIL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 7. PROVIDE WIND DESIGN PRESSURES FOR ROOF ASSEMBLEY.
 PROVIDE FASTENER SCHEDULE FOR ZONES 1, 2 & 3.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 8. INTERIOR PARTITION DETAIL AND 1 HOUR WALL DETAIL
 REFERENCE EXISTING BUILDING ELEMENTS. PLEASE CLARIFY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 9. PROVIDE DETAIL OF SITE BUILT FIREPLACE OR PROVIDE
 MANUFACTURERS INSTALLATION INSTRUCTIONS FOR PRE-FAB
 FIREPLACE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 16:34 Rev Time 0.00
Received By cthroop Date 2021-03-09 Time 06:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By cthroop Date 2020-12-15 Time 13:25 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 06:12 Sent To  
Notes
2020-12-15 13:26:43PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: SERVICE EQUIPMENT SHALL BE MARKED WITH THE
 MAXIMUM AVAILBLE SHORT CIRCUT CURRENT AVAILABLE PER NEC
 110.24; E3606.4.
  
 1. PROVIDE NUMBER OF 3/0 CONDUCTORS BETWEEN THE METER
 AND NEW 200 AMP PANEL.
 NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1
  
 2. MAIN DISCONNECT (MDC) SHALL BE LOCATED AT POINT OF
 ENTRY OF SERVICE CONDUCTORS.
 E3601.6.2SERVICE DISCONNECT LOCATION.
 THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR INSIDE NEAREST THE POINT OF ENTRANCE OF THE
 SERVICE CONDUCTORS. SERVICE DISCONNECTING MEANS SHALL
 NOT BE INSTALLED IN BATHROOMS. EACH OCCUPANT SHALL HAVE
 ACCESS TO THE DISCONNECT SERVING THE DWELLING UNIT IN
 WHICH THEY RESIDE. [230.70(A)(1), 230.72(C)]
  
 3. IDENTIFY LOCATION OF SERVICE AND C/U DISCONNECTS ON
 PLAN PAGE E-1. PROVIDE KEYED NOTES.
 SERVICE & METER
 FPL ELECTRIC SERVICE STANDARDS ? SECTION IV, A., 1.
 GENERAL. PG 1 OF 24
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. AFCI OUTLET NOTE # 2 ON PLAN PAGE E-3 SHOULD INCLUDE
 KITCHENS.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC
 210.12; FBC RE E3902.16
  
 5. HIGH EFFICACY LAMP NOTE # 5 ON PLAN PAGE E-3 SHOULD
 READ AS FOLLOWS:
 : "A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS". A NOTE WILL SUFFICE. FBC EC R404.1
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-12-14 Cont ID  
Sent By cthroop Date 2020-12-14 Time 11:28 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 08:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-12-14 Cont ID  
Sent By cthroop Date 2020-12-14 Time 09:26 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 08:18 Sent To  
Notes
2020-12-14 09:27:36PROVISO: A SEPERATE GAS PERMIT AND PLANS ARE REQUIRED.
 CT

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-12-28 Cont ID  
Sent By fmittner Date 2020-12-28 Time 13:41 Rev Time 0.00
Received By fmittner Date 2020-12-28 Time 13:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-11 Cont ID  
Sent By medwards Date 2021-03-11 Time 07:39 Rev Time 0.00
Received By medwards Date 2021-02-24 Time 18:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-29 Cont ID  
Sent By cpuell Date 2020-12-29 Time 12:51 Rev Time 0.00
Received By cpuell Date 2020-12-11 Time 05:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2021-03-17 Cont ID  
Sent By lmarchan Date 2021-03-17 Time 13:36 Rev Time 0.00
Received By lmarchan Date 2021-03-11 Time 09:15 Sent To  
Notes
2021-03-16 07:55:59RECEIPT MU-2021-11739 - $2491.56 - PAID
2021-03-11 09:15:293/11/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-12-14 Cont ID  
Sent By medwards Date 2020-12-14 Time 13:03 Rev Time 0.00
Received By medwards Date 2020-12-14 Time 11:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By cthroop Date 2020-12-15 Time 14:08 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 06:12 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-12-14 Cont ID  
Sent By cthroop Date 2020-12-14 Time 09:26 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 06:12 Sent To  
Notes
2020-12-14 09:26:49PROVISO: A SEPERATE ROOFING PERMIT IS REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By cthroop Date 2021-03-09 Time 16:34 Rev Time 0.00
Received By cthroop Date 2021-03-09 Time 06:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-14 Cont ID  
Sent By cthroop Date 2020-12-14 Time 08:30 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 06:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By fmittner Date 2021-03-01 Time 10:18 Rev Time 0.00
Received By fmittner Date 2021-03-01 Time 10:18 Sent To  
Notes
2021-03-01 10:19:19CONDITIONAL APPROVA LANDSCAPEL FORM PROVIDED

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-28 Cont ID  
Sent By fmittner Date 2020-12-28 Time 13:41 Rev Time 0.00
Received By fmittner Date 2020-12-28 Time 13:41 Sent To  
Notes
2020-12-28 13:42:07REQUIRES SUBMITTAL OF SEPARATE LANDSCAPE PERMIT.
 QUESTIONS CONTACT RAY CARANCI AT 822-1462