Plan Review Details - Permit 20120512
Plan Review Stops For Permit 20120512
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-09 Cont ID  
Sent By rmcphers Date 2021-03-09 Time 13:41 Rev Time 0.00
Received By rmcphers Date 2021-03-09 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-19 Cont ID  
Sent By rmcphers Date 2021-01-19 Time 09:39 Rev Time 0.00
Received By rmcphers Date 2021-01-19 Time 09:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-28 Cont ID  
Sent By rmcphers Date 2020-12-28 Time 14:58 Rev Time 0.00
Received By rmcphers Date 2020-12-28 Time 14:51 Sent To  
Notes
2020-12-28 15:00:48TEMP. CONSTRUCTION TRAILER
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A SITE PLAN/SURVEY SHOWING THE
 LOCATION OF THE CONSTRUCTION TRAILER.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-25 Cont ID  
Sent By jleahy Date 2021-02-25 Time 15:40 Rev Time 0.00
Received By jleahy Date 2021-02-25 Time 15:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-12 Cont ID  
Sent By jleahy Date 2021-02-12 Time 13:24 Rev Time 0.00
Received By jleahy Date 2021-02-12 Time 13:23 Sent To  
Notes
2021-02-12 13:25:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL SERVICE PLANS HAVE BEEN SUBMITTED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-02-23 Cont ID  
Sent By pleduc Date 2021-02-23 Time   Rev Time 0.00
Received By pleduc Date 2021-02-23 Time 11:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-05 Cont ID  
Sent By pleduc Date 2021-02-05 Time   Rev Time 0.00
Received By pleduc Date 2021-02-05 Time 13:33 Sent To  
Notes
2021-02-05 13:40:13FIRE PROVISO:
  
 ENSURE THAT SPRINKLER CANISTERS ARE INSTALLED PER THEIR
 MANUFACTURER'S SQ FT REQUIREMENTS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-01-19 Cont ID  
Sent By pleduc Date 2021-01-19 Time   Rev Time 0.00
Received By pleduc Date 2021-01-19 Time 11:14 Sent To  
Notes
2021-01-19 11:53:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE TRAILER LOCATED CLOSE
 TO THE PROPERTY LINE AND A SFH. THERE IS NO DIMENSION
 TO THIS SFH.
  
 THE TRAILER IS AN EXPOSURE HAZARD TO THE SFH AND NEEDS
 TO BE SEPARATED PER THE BELOW TABLE.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
 TURNING THE TRAILER SO THE SMALLER END WIDTH EXPOSES
 THE SFH WOULD ALLOW FOR A SHORTER SEPARATION DISTANCE
 OF APPROX. 15'-20'.
  
  
 2) THERE IS NO INDICATION OF A DIMENSION TO ANY
 PROPOSED STRUCTURE,
  
 PLEASE PROVIDE A DIMENSION IN COMPLIANCE WITH ABOVE
 NOTED CODE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-05-24 Cont ID  
Sent By ccole Date 2021-05-24 Time 13:35 Rev Time 0.00
Received By ccole Date 2021-05-14 Time 14:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-03-09 Cont ID  
Sent By rmcphers Date 2021-03-09 Time 13:42 Rev Time 0.00
Received By rmcphers Date 2021-02-17 Time 06:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-13 Cont ID  
Sent By cpuell Date 2021-02-13 Time 09:05 Rev Time 0.00
Received By cpuell Date 2021-02-03 Time 07:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-01-19 Time   Rev Time 0.00
Received By ccarvaja Date 2021-01-08 Time 18:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-28 Cont ID  
Sent By rmcphers Date 2020-12-28 Time 15:01 Rev Time 0.00
Received By rmcphers Date 2020-12-15 Time 14:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2021-05-21 Cont ID  
Sent By ccole Date 2021-05-21 Time 16:38 Rev Time 0.00
Received By ccole Date 2021-05-21 Time 15:58 Sent To  
Notes
2021-05-21 16:40:163RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20120512
 5/21/2021
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1) THE NEW PLUMBING PLAN SHALL BEAR THE EITHER THE
 TITLE BLOCK AND DIGITAL SIGNATURE AND SEAL OF THE FL.
 LICENSED DESIGN PROFESSIONAL WHO PREPARED THE DRAWING;
 OR THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF
 THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING-
 SECTION 107.2.1 WPB, FLORIDA STATUTES 471.003(2)(H) &
 471.025, AND SECTION 61G15-23.005 FAC.
  
 2) 3RD REQUEST TO INDICATE THE TYPE AND SIZE OF
 TEMPORARY SEPTIC TANK TO BE INSTALLED AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES- SECTIONS 107.2.1 & 108.1 WPB. PLEASE
 INCLUDE A COPY OF THE CONTRACT FOR THE TANKS THAT
 INCLUDES THE PUMP-OUT SCHEDULE.
  
 3) AS PREVIOUSLY NOTED A SEPARATE PERMIT IS REQUIRED
 FOR THE BACKFLOW PREVENTER. PLEASE PLACE A NOTE ON THE
 PLAN.
 BACKFLOW PREVENTER: A FLORIDA LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND
 SECTION 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE WPB BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT. AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-02-24 Cont ID  
Sent By ccole Date 2021-02-24 Time 12:13 Rev Time 0.00
Received By ccole Date 2021-02-24 Time 11:32 Sent To  
Notes
2021-02-24 12:16:393RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20120512
 2/24/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST AND
 2ND REVIEW LISTED BELOW WERE NOT ADDRESSED AND THE
 REQUESTED RESPONSE NARRATIVE WAS NOT PROVIDED. PLEASE
 ADDRESS THE COMMENTS.
  
 1) PROVIDE A SITE PLAN AND A PLUMBING PLAN SHOWING THE
 WATER SERVICE AND SANITARY DRAINAGE SYSTEMS FOR THE
 PROPOSED TRAILER. PROVIDE DETAILS INCLUDING:
  
 A) POTABLE WATER SERVICE PIPE RUN FROM POINT OF
 CONNECTION AT THE CITY MAIN TO THE TEMPORARY TRAILER-
 SECTIONS 602.1 & 602.2 FBC P.
  
 B) TYPE, SIZE AND BURIAL DEPTH OF WATER SERVICE PIPE-
 SECTIONS 602.1, 602.2, 603.1 AND TABLE 605.3 FBC P.
  
 C) BACKFLOW PREVENTER LOCATION AND TYPE TO BE
 INSTALLED. PLEASE NOTE THAT THE BACKFLOW PREVENTER
 SHALL BE INSTALLED UNDER A SEPARATE PERMIT- 608.1 FBC
 P.
  
 D) LOCATION AND TYPE OF MAIN SHUTOFF VALVE- 606.1 FBC
 P.
  
 E) SANITARY SEWER LINE RUN FROM THE TRAILER TO THE
 POINT OF CONNECTION TO THE CITY SEWER LINE- 701.3 FBC
 P.
  
 F) TYPE, SIZE, BURIAL DEPTH OF THE SANITARY SEWER PIPE
 AND LOCATIONS OF CLEANOUTS- TABLE 702.3. AND SECTIONS
 708.1.2 & 708.1.3 FBC P.
  
 2) PLEASE NOTE IF HOLDING TANKS ARE TO BE INSTALLED FOR
 SANITY SEWER IN LIEU OF CONNECTING TO THE CITY SEWER,
 PLEASE SHOW THEIR LOCATIONS AND SIZES ON THE PLAN AND
 ALL PIPING RUNS. SUBMIT A COPY OF THE CONTRACT FOR THE
 TANKS THAT INCLUDES THE PUMP-OUT SCHEDULE- SECTION
 108.1 WPB.
  
 3) BACKFLOW PREVENTER: A FLORIDA LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND
 SECTION 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE WPB BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT. AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-11 Cont ID  
Sent By ccole Date 2021-02-11 Time 13:41 Rev Time 0.00
Received By ccole Date 2021-02-11 Time 12:51 Sent To  
Notes
2021-02-11 13:42:092ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20120512
 2/11/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW LISTED BELOW WERE NOT ADDRESSED AND THE
 REQUESTED RESPONSE NARRATIVE WAS NOT PROVIDED. PLEASE
 ADDRESS THE COMMENTS.
  
 1) PROVIDE A SITE PLAN AND A PLUMBING PLAN SHOWING THE
 WATER SERVICE AND SANITARY DRAINAGE SYSTEMS FOR THE
 PROPOSED TRAILER. PROVIDE DETAILS INCLUDING:
  
 A) POTABLE WATER SERVICE PIPE RUN FROM POINT OF
 CONNECTION AT THE CITY MAIN TO THE TEMPORARY TRAILER-
 SECTIONS 602.1 & 602.2 FBC P.
  
 B) TYPE, SIZE AND BURIAL DEPTH OF WATER SERVICE PIPE-
 SECTIONS 602.1, 602.2, 603.1 AND TABLE 605.3 FBC P.
  
 C) BACKFLOW PREVENTER LOCATION AND TYPE TO BE
 INSTALLED. PLEASE NOTE THAT THE BACKFLOW PREVENTER
 SHALL BE INSTALLED UNDER A SEPARATE PERMIT- 608.1 FBC
 P.
  
 D) LOCATION AND TYPE OF MAIN SHUTOFF VALVE- 606.1 FBC
 P.
  
 E) SANITARY SEWER LINE RUN FROM THE TRAILER TO THE
 POINT OF CONNECTION TO THE CITY SEWER LINE- 701.3 FBC
 P.
  
 F) TYPE, SIZE, BURIAL DEPTH OF THE SANITARY SEWER PIPE
 AND LOCATIONS OF CLEANOUTS- TABLE 702.3. AND SECTIONS
 708.1.2 & 708.1.3 FBC P.
  
 2) PLEASE NOTE IF HOLDING TANKS ARE TO BE INSTALLED FOR
 SANITY SEWER IN LIEU OF CONNECTING TO THE CITY SEWER,
 PLEASE SHOW THEIR LOCATIONS AND SIZES ON THE PLAN AND
 ALL PIPING RUNS. SUBMIT A COPY OF THE CONTRACT FOR THE
 TANKS THAT INCLUDES THE PUMP-OUT SCHEDULE- SECTION
 108.1 WPB.
  
 3) BACKFLOW PREVENTER: A FLORIDA LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND
 SECTION 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE WPB BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT. AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-19 Cont ID  
Sent By ccole Date 2021-01-19 Time 14:48 Rev Time 0.00
Received By ccole Date 2021-01-19 Time 14:33 Sent To  
Notes
2021-01-19 14:48:301ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120512
 1/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SITE PLAN AND A PLUMBING PLAN SHOWING THE
 WATER SERVICE AND SANITARY DRAINAGE SYSTEMS FOR THE
 PROPOSED TRAILER. PROVIDE DETAILS INCLUDING:
  
 A) POTABLE WATER SERVICE PIPE RUN FROM POINT OF
 CONNECTION AT THE CITY MAIN TO THE TEMPORARY TRAILER-
 SECTIONS 602.1 & 602.2 FBC P.
  
 B) TYPE, SIZE AND BURIAL DEPTH OF WATER SERVICE PIPE-
 SECTIONS 602.1, 602.2, 603.1 AND TABLE 605.3 FBC P.
  
 C) BACKFLOW PREVENTER LOCATION AND TYPE TO BE
 INSTALLED. PLEASE NOTE THAT THE BACKFLOW PREVENTER
 SHALL BE INSTALLED UNDER A SEPARATE PERMIT- 608.1 FBC
 P.
  
 D) LOCATION AND TYPE OF MAIN SHUTOFF VALVE- 606.1 FBC
 P.
  
 E) SANITARY SEWER LINE RUN FROM THE TRAILER TO THE
 POINT OF CONNECTION TO THE CITY SEWER LINE- 701.3 FBC
 P.
  
 F) TYPE, SIZE, BURIAL DEPTH OF THE SANITARY SEWER PIPE
 AND LOCATIONS OF CLEANOUTS- TABLE 702.3. AND SECTIONS
 708.1.2 & 708.1.3 FBC P.
  
 2) PLEASE NOTE IF HOLDING TANKS ARE TO BE INSTALLED FOR
 SANITY SEWER IN LIEU OF CONNECTING TO THE CITY SEWER,
 PLEASE SHOW THEIR LOCATIONS AND SIZES ON THE PLAN AND
 ALL PIPING RUNS. SUBMIT A COPY OF THE CONTRACT FOR THE
 TANKS THAT INCLUDES THE PUMP-OUT SCHEDULE- SECTION
 108.1 WPB.
  
 3) BACKFLOW PREVENTER: A FLORIDA LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND
 SECTION 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE WPB BUILDING
 DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL
 OPERATIONS DEPT. AT 561-822-2210 FOR FURTHER
 INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By rmcphers Date 2021-03-09 Time 13:41 Rev Time 0.00
Received By rmcphers Date 2021-03-09 Time 13:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-12-28 Cont ID  
Sent By rmcphers Date 2020-12-28 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2020-12-28 Time 15:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-02-12 Cont ID  
Sent By elevesqu Date 2021-02-12 Time 16:52 Rev Time 0.00
Received By elevesqu Date 2021-02-12 Time 16:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-01-13 Cont ID  
Sent By elevesqu Date 2021-01-13 Time 14:35 Rev Time 0.00
Received By elevesqu Date 2021-01-13 Time 14:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-17 Cont ID  
Sent By elevesqu Date 2020-12-17 Time 10:51 Rev Time 0.00
Received By elevesqu Date 2020-12-17 Time 10:51 Sent To  
Notes
2020-12-17 10:51:36PLEASE PROVIDE SITE PLAN INDICATING LOCATION OF TRAILER
 PLEASE INCLUDE SITE IMAGES INDICATING LOCATION IN
 PROXIMITY TO EXISTING LANDSCAPE ON SITE
  
 PLEASE PROVIDE FENCE DETAIL IF SITE SHALL BE FENCED
 PLEASE ILLUSTRATE MEANS OF INGRESS AND EGRESS TO SITE
 AND PROPOSED PARKING FOR EMPLOYEES/CONTRACTORS
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]